Brother, I have installed this inverter for 1 year, nothing happened, As far as the ampere of the battery is zero, if your battery is fully charged then why will it show u amp
Dear Bhai, AOA! Your inverter is working fine. It will produce as per your running load. It is a hybrid inverter with no net metering. The charging current is zero since batteries are fully charged. Hope that solves the issue. The Solar Inverter companies are not supposed to get the settings of your inverter done, it is the job of your solar installer.❤
AoA, Dear , aap ki video dekhi, good thi, aap nyy 6 pannel + 1 Zeiwnic 4.5KV 6500PV + 2 Tubular 185 Amps Series myy lagai, Wire's yakinun standerd ki lagai ho gi. Phir aap ny Pannels 10 kara liye, Q1. aap ka system aab sahi hua ya nahi? Q2. aap ka load kitna hyy? Day time and Night Time Q3. aap ky Pannels kitnay watt ky hain? aur sab same watt ky hain ya nahi?. Q4. aap ki expectations kya hain backup syy? e.g. 500Watt sari raat chaly? kindly reply, as I was in same situation, now all working fine. and willing to help you.
Mere pass bhi yahi hy Bhai Jaan Jab load ni chal rahs to production kese hogi Aap jese hi load daalo ge foran production barh jaygi Our aap ki battery jab full hoti hen 1 baat to battery 27v par ruk jaati hy
@@SaeedFlicksap jo mrzi setting krlen backup thora sa he improve hoga jo mene 1 comment k reply me setting btayin unke siva problem solve nai hogi. beshak u can try all settings.
Assalamualaikum 13 number setting 27 volt pr hai or agar ap ye chah rahe ho ke battery or zayda charge kare to ap aysa karo number setting ko use pr rakho or 26 ya shayid 27 number settings pr akar floating charge volt 28.5 kar do ya 27 se hat kr 28.5 pr charge kar de ga
I know but batteries fully charge ni ho rahi na hi backup proper mil raha. Batteries ko examine kraya hai.. 💯 percent ok hain mgr system ki settings ka masla hai I guess.
@@SaeedFlicks sir, agaar user manual hai to usme de kar ap battery charge settings me battery ki voltage proper rakhien jo tubular battery ki hoti hain. Tubular aur flat olate battery ki voltage setting me bohat difference hai
@@SaeedFlicks float charge 27v... Bulk charging 29.2 krden for tubular......equalization voltage 30v krden..... Ap rat wapda sy battery charging off krty hain????
The second thing is that if you add the same amount of load, solar will generate you If your house is not getting the load then solar will not generate electricity The mechanism of this inverter is like this
Bhai yehi inervter me ne bhi Lia tha, installers system lga k chale gae phir mujhe same aapki trha backup nhe mil rha tha. Boht khajjl khuwar hony k bad RUclips se he sekha. Aap simple bulk charge aur float charge change kr de. Mera masla bhi esi trha se hal hua. Bulk charge es inverter me 29 se zyada nhe jata 26th numbr p setting hai so bulk charge 29 kr de aur float charge setting 27 p kr de.
Inverter me setting to kro battery wali...29 Volt tak charge krwao aur inverter mei OSO(charge only solar) option..baqi 30 A ya 20 A py batteries charge krwao
Bhai is ki charging ki setting set nahi hy maximum charge cut off 30 per set kro phir apko battery backup mile ga aur load setting main ja ke USB (utility solar battery)set kro.
ہم ااپنے شوق کیلئے لاکھوں روپے کا سسٹم تو لے آتے ہیں لیکن یہاں پہ آکر مار کھ جاتے ہیں کہ ایک اچھے انسٹالر سے انسٹال نہیں کراتے کیونکہ وہ ذرا مہنگا ہوتا ہے اس لئے بعد میں روتے رہتے ہیں
@@pervezlashari dear installer acha hai pr kbi kbi ye electornic ki chezain masla krti hain. Ap neechy comment parhyn. Aik bhai ny kea hai iss company k inverter k bary mei
bhaya, baat samjhnay ki hai, jab battery full charge ho ge tu inverter will not further charge it, IQ.....!!!.... don't make vlog without understanding things.......
بھائی آپ یو ٹیوب اور ساتھ منال سے سمجھ کر سیٹنگ آیا اس سے سیٹنگ کی ۔الحمدلللہ 9 سے 10 ampairs لوڈ اٹھایا اس نے ۔جیسے جیسے لوڈ بڑھاے گے واٹ زیادہ ہو جاتے ۔ یاد . رہے میں نے 6800 واٹ تک کے سولر penal لگاے ہوے ہیں ۔۔
السلام علیکم Dear merey pass bhi ziewnic ka 6kw ka inverter he ab germi buht zyada he to jb us pr load zyada daala jaye to wo heatup ho jata he iska hull bataye plz
Bhai 24v system he apka.. apki batteries abhi full he. System ki intelligence ne notice kia he thats why wo batteries ko over charge se mana kr rhy he. Jo screen pe battery charging blink kr 4ha he wo serf apki battery ko floating charge dai rha he.
G bhai expert sy hi lgwaya hai and ap zra tameez sy baat kryn. Iss company k aur bhi complains aa ri comments mei.. jis baat ka ilm nahi tou baat b mt kryn
Back nahe milraha, to is ka matlab batteries purani hogai hain. Lakin batteries fully charged hain to mazeed charge q lega. Basic si cheez hey ap is ko itna hypyde k logon ko missguide to naa karain, thanks! @@SaeedFlicks
Sir modal me ne be lagai hai. Sir screen ki option change karne ki videos apload kare. Aur bettry jab heavy load se cut off hoti hai os ki screen option ka method bata de ka kitne percent par heavy load off ho jaye....
Uploader theek keh rahay hain bhai tum logo ko bas comment Mai muu marnay ki aadat hai pata tum logo ko takay ka kuch nahi hota negativity ki baat nahi hai dunya pagal nahi jo double price mai inverex sirf isi liye leti hai ku k uski after sales service bihat achi hai warna us k pankhay mai se lata k gaano ki awazein nahi aati
السلام علیکم ورحمۃ اللہ وبرکاتہ بھائی جان اپ بات بالکل صحیح بتا رہے ہیں گائیڈ کسی کو کرنا چاہیے اور رہی بات ہائر والوں کی تو ہائر والوں کی جو سروس ہے وہ واقعی بہت اچھی ہے میرا بھی اس کا ایکسپیرینس اچھا رہا ہے
Sir hybrid system he jitna load hoga utni hi production ziada ho jaye gi and battery fully charged hai apki settings pe .es lie system ne charging band kr di . Sir user manual parh lein ek dafa
Bhai ap jetna use kari gi hos si 100 or 200 watts solar di ga ap apni ghar ka load ziada kari solar ka current be ziada aia ga jetni kw ka system ha ap ka ap use 90 watt kar rhi ha to inverter ni pv si pi kam current lena ha
Kahan se purchase kia bhai Inverter? Aur kitne price m mila apko? Batteries shyd apke full hain, isliye ampere show nahe ho rahe. Ap wapda off kr k batteries ka backup check karm, complete drain karn aur dobara check karn,. Phr ampere show honge apko
Bhai jha etna khrcha kr lia batteries k sath aik chota dc volt meter b lga lo us sy apko pta chlay ga battery voltage kiya ha charging prh volts 28.5 tak ho skty ha or discharge prh km hoty hay gay us sy apko sahi pta chlay ga battery ke state ka or eski settings SBU prh rakho phly Solar phir battery or phir utility phir thik kam kry ga
Jab battery gravity ka masla ata hay to battery jaldi full hojate hay or backup time kam hojata hay. Or ye 27 volt normal acid battery ke floot charging seting hay. Ye kam hay. Setting sahe kare.
اس وقت اپکی بیٹریٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕاں چرجڈ ہے چارج کا نشان اپنی جگہ پر قایم ہے اپ اس پر لوڈ بڑھایں تو یہ پروڈکشن زیادہ کے گا اپ نے بتایا نہیں کہ کتنے پینل لگإے ہیں اگر اپ سیٹنگ میں جایں گے تو پھر پتہ چلے گا انورٹر کے مینول سے اپ با اسانی خود سارے سیٹنگ کر سکتے ہیں کوشش کرے
Bhai es inverter ko koi masla nahi hai. Jab jab load dalain gay tab output ziada show hogi. 75w consumtion k sath 3 kva show nahi karay ga ye system. Ap iron on kar k phir dekhain. Output 1 kva k pas ho jaye gi. Esi tarha jesay jesay load dalain gay tab tab output increase hogi.
Sir ye masla nai koi , its in programming whrn you use it as off grid mode it will generate power as per load demand only , and batteries charging settings not done proper by your installer or you have shut down battery breaker after their setting saved , bec it Will delete settings when disconnected batteries.
Tubbler battery ki setting No 5 user set kary No 26 29.6 set Kary No 27 27v set Kary No 29 21v default rehnyday Or battery ki gravity check kary Ik dafa ager low hy to no 26 ma JA k charging voltage full kerdy k gravity pora hojayega. Ye setting 24 hour k bad wapis no 26.. 29.6 pay set kary
AOA! Sir Its a simple issue. I faced this issue way back also. The thing is your system is 3.5 kilowatt. At peak hour like 11am-3pm it will generate power at 70% efficiency which is in between 2 to 2.5 kw. So, After 3pm the production decreases and to run the load the inverter takes power from batteries to run your load. Therefore, when sun sets your batteries are already at 40-50% of its capacity. And after sunset when there is load shedding your batteries will not provide Backup. For this Inverter Maximum PV Current is 27 A and MAximum Voltage is 450v. Check your PV strings they might be connected in a wrong way. But """""the simple solution to your problem is increase your solar panels use the full potential of the inverter install up to 6.5 kw Solar panels.""""""""" Also, How many panels have you connected and there power ratings. The thing is solar power is very inefficient and you have to install solar panels double the power you consume. lets say you consume 5kw then you should install 10kw which will charge your batteries and will run your load. Hope it will help you.
Bahi battery ap ki fully charged ha 27.0 floating charge pa ha iss liya 0 amp ja rahye... Our 2nd jitna ap ka agay load chal raha ho ga solar utni he production bnaye ga na.. same gab ap garie chalatay jitna ap acceleration datay usi hisab sa engine zor lagata our garie bagtie .. asa to nai hta k ap ki speed 40 ho our engine rpm 9000 pa ho... Hope so samj aa gye ho gi
@@SaeedFlicks ap setting shai karain first battery type ki setting ko use pa karain our us k bad 26,27 no setting dakhain idr jo bulk voltages ki setting ha usay 29.2 karain our floating charge k voltages 27.5 karain
I think, it is worth the price it offers. There are three voltages in a battery, low, floating and full. The voltage is you see is the floating voltage, it is considered fully charged
Dear, company ki services sy shikwa hai.. Baki abi iski performance py kuch ni keh skta.. ye tou proper settings k baad koi expert bta skta hai k issue kis chez ka hai.
As sallam o alakom bahi. Ap battery ko discharge kare without battery and solar os pa load daly jasy he down jojaye. Is wapda on kare ya solar charging kay lena. Pir ap time note kare. Aga 1 ganty may ampare zero tak ata hay. To pir ye charging setting or ya battery Acid specific gravity ka madla hay.
@@SaeedFlicks bahi jan battery TYPe FLD pay rakhy. Ya sahe technician sa setting kardy. Baqi sab kuch teek chal raha hay. Inver ter battery full hony ya flootine charging pay 0 ya 1 ampare leta hay.
Piary bhai 2 batteries mein just 1800 sy 2000 watt store hoty agr 300 watt load dalo gy 6 hour chaly ga agr 500 watt dalo gy 4 hour chaly ga...raat ko load na dala kro batteries farig ho jaein gi jald hi
Only lithium batteries give true backup. Ye tall tubular and lead acid batteries fail hain in Solar system giving backup. Ap SUB mode per Inverter ki setting rakhein. Baqi in inverters me MPPT laga hota ye solar say utni hi power produce kertay jitni gher me load chal raha hota. Apka system bohat zaberdast hai laganay walay ki tareef kerni chahiyay. Shuker Kerein k apko ye naimat hasil hai.
Muhjay Rawalpindi market may saray shops walon nay bout tareef kithi k acha inverter hai even jis k pas ye inverter nae ta wo bue keh raha ta k acha inverter hai but social media pay story kuch or hai. I purchased 8500kw 10000pv Ab may pareshan k kia keron?
Wash kartay hway solar breaker iss liya nechay kiya jata ha k jo banda wash kar raha usay current lagta ha halka halka sa us sa safe rahnay k liya breaker off kiya jata ha .. barish sa kia masla hna no isue
Ap preshan nhi ho battery usd nahi horahi is wajha se battery volt 27 hai jaha battery se current jaye ga battery volt drop honge ye charging pr ajaye ga
AoA, Bhai jaan, may b ye wala inverter lay k phas gya hu, after sale service hai nhi, or jinho nay install kia system wo jawab day gye hain k unhay samj nhi aa rha, or mujay bill ziada aa rha hai, earth light b on hai meter pay. 😢
@@SaeedFlicks bhai mere apne jinko payment ki hai installation ki wo aker deke observation karengy ager faulty howa tu ap claim kar sakte hai otherwise koi b company apke liye aise nai ayegi chahye inverex ho ya Jo b ho
@@tayyabraza2803 bhai ye mppt different types k hote he or in me sb functions available hote he me ne b abi 3kw system k lie lena he mppt us k bare me research kr raha hu
@@tayyabraza2803raat ke time ,yes, ups will charge the battery and only use if load shedding. but after the load shedding, it will start to charge the battery and hence till morning your battery may get charged only on wapda which is not optimal. and there will not be commendable bill reduction.
@asifshadowofdarkness dear I recommend k ap uss company k inverter lyn jiski after sale service boht hi achii ho.. ye aap ko market research sy maloom hoga.
@@SaeedFlicks brother inverex ka budget nai hai jo sbse behtreen hai lakin is inverter ki wese kaafi mashoori hui hai isilye me sochra hu isko lganay ka..isilye ap se pucha hai k ispe load agr solar se chalay to sai chalta rehta ya nai
Toyota se gari lo, agar kharab ho jae to Toyota ne engineer ko ghar bhejna hota hai ? woh bhi free main ? it doesnt work like that, nothing is free for life
Dear, wo mene video mei explain ki hai.. ab cost kum ho gae hai.. jo fix cost thi mene btae thi.. for example iron structure.. Baki inverter ki price bhi btae aur panels k current rates bhi.
Kuch din pehlay youtube video mein kisi ney backup ka hisab bataya tha k 300 watts ka load ho tow 4 battery wala agar system hai tow battery backup (phoenix tx 1800) 3 hour chalay ga night mein. 2 battery ka bhi bataya tha lakin mujhey yaad nahi. Sha-ed 2 ghantay bataya tha. Aap ney ye first check karna hai k raat mein aap ka battery per kitna load chalta hai. Meray pas bhi zeiwenic ka 4 battery wala system hai 6 panels wala. Din mein 600 ya 650 watt chalata hai solar sey aur battery bhi charge karta hai, lakin sham sey battery per 200 ya 250 watt bhi bohat jsldi battery ko down kar deta hai aur inverter beep karnay lagta hai.
bhi ap ye dekhe na apke inverter ki battery charging current kitne amperes pe set hai q ke apne 2 batteries lgai hoi hai to 27 28 amperes pe battery full hoti hai nhi to inbox ajai mai apko bta deta hu
Sir your solar system is working properly. There is no issue because your batteries are fully charged ,so there will be no charging current drawn.
JazakAllah😊
Right 27 is a full charge of state, so obviously no more current will flow in, otherwise drawing more current means overcharged. Ok
Brother, I have installed this inverter for 1 year, nothing happened, As far as the ampere of the battery is zero, if your battery is fully charged then why will it show u amp
Batteries backup nahi dy rahi hain. Lets see kea issue nikalta hai. Batteries tou check krwa chuka hu.
@@SaeedFlicksto ap battery ki settings main charging mode solor and wada dono se select kare charge ho jae gi or phr supply mode b SUB select kar le
Bhai ap ko agr kuch smjh ni araha mujh say contact kr lein mai khud bhi yehi inverter use kr raha hu
Bhi mara bi yahi masla hy plz halp
@@clickart8981mara b yahi masla hy plz hlp
Dear Bhai, AOA!
Your inverter is working fine. It will produce as per your running load. It is a hybrid inverter with no net metering. The charging current is zero since batteries are fully charged.
Hope that solves the issue. The Solar Inverter companies are not supposed to get the settings of your inverter done, it is the job of your solar installer.❤
JazakAllah 😊
👍
@@SaeedFlicks How many hours battery backup at night or load shed time.
@@muhammadahmedahmed8025 Not according to the expectation.
Ap ki video ka is liye w8 tha k main bi ziewnic ka inveter k bary soach raha tha but ap ki baten son k dil bar geya is inverter se
👍
👍
Agr hmara masla hal hota hai tou mei again video mei btaonga apko. InshaAllah.
❤❤Thanks
inverters k bht role hote hen me recommend kru ga k ups plus mppt controller le lo thore energy losses hon ge but bht paidar kaam ho ga
AoA, Dear , aap ki video dekhi, good thi, aap nyy 6 pannel + 1 Zeiwnic 4.5KV 6500PV + 2 Tubular 185 Amps Series myy lagai, Wire's yakinun standerd ki lagai ho gi. Phir aap ny Pannels 10 kara liye,
Q1. aap ka system aab sahi hua ya nahi?
Q2. aap ka load kitna hyy? Day time and Night Time
Q3. aap ky Pannels kitnay watt ky hain? aur sab same watt ky hain ya nahi?.
Q4. aap ki expectations kya hain backup syy? e.g. 500Watt sari raat chaly?
kindly reply, as I was in same situation, now all working fine. and willing to help you.
JazakAllah
@@SaeedFlicks matlab abb sab sahi chall raha hyy?
True, they dont come in in Lahore. I have also faced same issue regarding settings. And finally I learnt after watching hundreds of videos on youtube.
Yup. Allah Pakistan mei customer ko empower kry. Ameen
@@SaeedFlicks if you are facing any issues with settings let me know. I have learnt a lot regarding this inverter and it is working well for me.
Mojy b same issue h yar btry backup ni Dy rhi plz let me know if you know
@@moosamashooq-v3l dua hai dear bs..
@@moosamashooq-v3l channel subscribe kr dena shayed iski barkat sy kuch farq par jaye
سیٹنگ کا مثلہ ہے اپ پوری طرع اس کو سیکھ لیں زیونک کے انورٹر بہترین چل رہے ہیں ہم نے تیںن لگا رکھے ہیں بلکل درست جا رہے ہیں شکریہ
@@aslamnadeem52 JazakAllah 🙂
Mere pass bhi yahi hy Bhai Jaan
Jab load ni chal rahs to production kese hogi
Aap jese hi load daalo ge foran production barh jaygi
Our aap ki battery jab full hoti hen 1 baat to battery 27v par ruk jaati hy
Eid Mubarik, ❤dear brother.
Very nice and informative vlog 😊
Thanks.
seting main ja kr
5 no...main tubler sa hat kr ...(user) per rakhe....
seting 26.... 29v
27.....27.8v
29....20.6 ko thek kre...
Ok mei try krta
27.8 zyada hy......27 thek hy......
@@SaeedFlicksap jo mrzi setting krlen backup thora sa he improve hoga jo mene 1 comment k reply me setting btayin unke siva problem solve nai hogi. beshak u can try all settings.
@@ahmadghori6836stng btauo plz
Assalamualaikum
13 number setting 27 volt pr hai or agar ap ye chah rahe ho ke battery or zayda charge kare to ap aysa karo number setting ko use pr rakho or 26 ya shayid 27 number settings pr akar floating charge volt 28.5 kar do ya 27 se hat kr 28.5 pr charge kar de ga
Thanks brother. And subscribe my channel as well 🙃
Floating voltage hamesha bulk charging say kam rakhtay hain
@@farhanameer1771 bilkul theek kaha ap ne lekin Kuch log ye chahte hain battery hr waqt charging show Karen isliye ye messages unke liye the
Jab batteries full hon to charge ni hoti.....
Plus jab load ata hy to solar generation barhti hy.....
I know but batteries fully charge ni ho rahi na hi backup proper mil raha. Batteries ko examine kraya hai.. 💯 percent ok hain mgr system ki settings ka masla hai I guess.
@@SaeedFlicks sir, agaar user manual hai to usme de kar ap battery charge settings me battery ki voltage proper rakhien jo tubular battery ki hoti hain.
Tubular aur flat olate battery ki voltage setting me bohat difference hai
@@nomanshah6761 28 volt py rakha hai abi.
@@SaeedFlicks float charge 27v...
Bulk charging 29.2 krden for tubular......equalization voltage 30v krden.....
Ap rat wapda sy battery charging off krty hain????
@wajeehulhassan2182 g raat mei wapda pr sy tou charge ni hoti I think. And ye settings mei dikhata hu kisi ko k kr dy mujy.
Sab se best inverter meri nazar mei TESLA BRAND HAI
Tesla k hain inverters???
I'm also using it in my home.
@@Blueworld950 Nice
Bhai maine b ye lagwaya hai bht zabadast raspons hai ke bilkol off
@@deartistic3952 mtlb?
Nic
@@MArshad-m8r 😊
The second thing is that if you add the same amount of load, solar will generate you If your house is not getting the load then solar will not generate electricity The mechanism of this inverter is like this
There is no problem, it is going well If your battery is not charging you increase charging amps
Yes. Load generation ka mechanism tou maloom hai.
Dear ap ny kitna system lgaya hai and uska output kitna hai??
Bhai yehi inervter me ne bhi Lia tha, installers system lga k chale gae phir mujhe same aapki trha backup nhe mil rha tha. Boht khajjl khuwar hony k bad RUclips se he sekha. Aap simple bulk charge aur float charge change kr de. Mera masla bhi esi trha se hal hua. Bulk charge es inverter me 29 se zyada nhe jata 26th numbr p setting hai so bulk charge 29 kr de aur float charge setting 27 p kr de.
Thanks dear. Ye mene aagy send kea hai. Lets see kea reply aata.
Inverter me setting to kro battery wali...29 Volt tak charge krwao aur inverter mei OSO(charge only solar) option..baqi 30 A ya 20 A py batteries charge krwao
Ok
Bhai is ki charging ki setting set nahi hy maximum charge cut off 30 per set kro phir apko battery backup mile ga aur load setting main ja ke USB (utility solar battery)set kro.
@@pervezlashari JazakAllah ❤
ہم ااپنے شوق کیلئے لاکھوں روپے کا سسٹم تو لے آتے ہیں لیکن یہاں پہ آکر مار کھ جاتے ہیں کہ ایک اچھے انسٹالر سے انسٹال نہیں کراتے کیونکہ وہ ذرا مہنگا ہوتا ہے اس لئے بعد میں روتے رہتے ہیں
@@pervezlashari dear installer acha hai pr kbi kbi ye electornic ki chezain masla krti hain. Ap neechy comment parhyn. Aik bhai ny kea hai iss company k inverter k bary mei
bhaya, baat samjhnay ki hai, jab battery full charge ho ge tu inverter will not further charge it, IQ.....!!!.... don't make vlog without understanding things.......
Jb charge ho gae full tou backup q nai mil raha. Please ap guide kr dyn q k 2 engineers fail ho gye mamla set krny meii.
Best inverter inverex
Unki after sale service ka suna hai k achii hai.. unky representative aa k masla hal kr dete hain.
بھائی آپ یو ٹیوب اور ساتھ منال سے سمجھ کر سیٹنگ آیا اس سے سیٹنگ کی ۔الحمدلللہ 9 سے 10 ampairs لوڈ اٹھایا اس نے ۔جیسے جیسے لوڈ بڑھاے گے واٹ زیادہ ہو جاتے ۔
یاد . رہے میں نے 6800 واٹ تک کے سولر penal لگاے ہوے ہیں ۔۔
👍
@@SaeedFlicks یوزر مینول سامنے رکھیں اور youtube کھول کر سمجھتے جاییں ۔لکھتے جاےیوزر مینول کے اوپر ۔پھر جا کر یوزر مینوئل سے سیٹنگ کر لیں
@@moonbhatti1577 G zrur.
Thanks for good information
Welcome and JazakAllah for motivating 😊
السلام علیکم
Dear merey pass bhi ziewnic ka 6kw ka inverter he ab germi buht zyada he to jb us pr load zyada daala jaye to wo heatup ho jata he iska hull bataye plz
Wa alaikum salam.
Ye tou company ee bta skti hai. Ap wevsite sy complain number ly k rabta kryn.
Es ky filters saf karyn or uper ky fan lagayn to heatup nai hoga
@@faisal3374 g filters tou saaf krta hi hu.
Setting mein ja k ye setting kr dain First Solar/Battery/ Wapda Number 1 (SBU)
JazakAllah. Already yehi hai. 😊
I am installer
Number 5 setting ko use pr kar ke 26 27 settings ko change kar do phir ye har waqt charge kare ga
Ap subscribe ni kr ry iss liye preshan hu mei 😊
Kis city sy hain ap?
@@SaeedFlicks Karachi
@@electricwork-cj6oq behtr
Thanks for your alert
Welcome dear. Logon tk sahi info pohnchana mera farz hai
Very nice information ❤❤❤
Thanks.
Bro ap ki batteries ful charge hn. Jb ap ka load increase ho ga solar b increase ho ga. Dont worry
InshaAllah
❤GooD
Thanks 😊
Bhai 24v system he apka.. apki batteries abhi full he. System ki intelligence ne notice kia he thats why wo batteries ko over charge se mana kr rhy he. Jo screen pe battery charging blink kr 4ha he wo serf apki battery ko floating charge dai rha he.
Dear batteries 2 ghanty ka backup bhi mushkil sy dy ri q k charging ni ho ri
like for your Vlogger cat
@@rabiakhan4050 👍
Asi bilwaja ki complains ki waja sy hi companies nahi ati. Khud sayana banaye ki bajaye kissi expert sy lagva latay .
G bhai expert sy hi lgwaya hai and ap zra tameez sy baat kryn. Iss company k aur bhi complains aa ri comments mei.. jis baat ka ilm nahi tou baat b mt kryn
Bhai jaan battery full hai aapki
Pr backup nahi mil raha
Back nahe milraha, to is ka matlab batteries purani hogai hain. Lakin batteries fully charged hain to mazeed charge q lega. Basic si cheez hey ap is ko itna hypyde k logon ko missguide to naa karain, thanks! @@SaeedFlicks
@shoukatalihunzai1 basic ni hai.
1- batteries are brand new. Tall tubular.
2- why its not giving backup.
3- Post sale service experience is poor.
Sir modal me ne be lagai hai. Sir screen ki option change karne ki videos apload kare. Aur bettry jab heavy load se cut off hoti hai os ki screen option ka method bata de ka kitne percent par heavy load off ho jaye....
Try kru ga
Some people are made to spread negativity only
Thanks. If you dont you think that showing reality is an act of negativity then its really negativity.
Uploader theek keh rahay hain bhai tum logo ko bas comment Mai muu marnay ki aadat hai pata tum logo ko takay ka kuch nahi hota negativity ki baat nahi hai dunya pagal nahi jo double price mai inverex sirf isi liye leti hai ku k uski after sales service bihat achi hai warna us k pankhay mai se lata k gaano ki awazein nahi aati
Mary pass zewnic Z5 PV 6500 laga howa hai 4 months sa mara experience bht krab hai. Wapda sa sharing lata hai har wakt. Wapda cutoff nai krta.
Hm.Sad
السلام علیکم ورحمۃ اللہ وبرکاتہ بھائی جان اپ بات بالکل صحیح بتا رہے ہیں گائیڈ کسی کو کرنا چاہیے اور رہی بات ہائر والوں کی تو ہائر والوں کی جو سروس ہے وہ واقعی بہت اچھی ہے میرا بھی اس کا ایکسپیرینس اچھا رہا ہے
JazakAllah. 😊
Sir hybrid system he jitna load hoga utni hi production ziada ho jaye gi and battery fully charged hai apki settings pe .es lie system ne charging band kr di .
Sir user manual parh lein ek dafa
👍
Bhai ap jetna use kari gi hos si 100 or 200 watts solar di ga ap apni ghar ka load ziada kari solar ka current be ziada aia ga jetni kw ka system ha ap ka ap use 90 watt kar rhi ha to inverter ni pv si pi kam current lena ha
Gg
Battery charging ki settings check karein .. sabi systems mein battery charging ki settings hoti hain
Ki hai
Kahan se purchase kia bhai Inverter? Aur kitne price m mila apko? Batteries shyd apke full hain, isliye ampere show nahe ho rahe. Ap wapda off kr k batteries ka backup check karm, complete drain karn aur dobara check karn,. Phr ampere show honge apko
Multan sy lya hai hussain agahi mei aik shop sy. 1.5 ka
Ap ke battery charge hai to or charge kaisy kary, or jetna load dalogy othne production dega
Hm.
Sir ap ki bettry ki settings theek ni hy.many b yahi lagwaya hy.but wo to bilkul ok hy
Ap ny iss py kitny panels lgaye hain?
Bhai jha etna khrcha kr lia batteries k sath aik chota dc volt meter b lga lo us sy apko pta chlay ga battery voltage kiya ha charging prh volts 28.5 tak ho skty ha or discharge prh km hoty hay gay us sy apko sahi pta chlay ga battery ke state ka or eski settings SBU prh rakho phly Solar phir battery or phir utility phir thik kam kry ga
Settings already yehi hai dear.
@@SaeedFlicks bhai battery fully charge state ma ha low ho ge to charge kray ga na 24v pr battery low hona shuro hoti ha
@@fahadshah8086 ok
Jab battery gravity ka masla ata hay to battery jaldi full hojate hay or backup time kam hojata hay. Or ye 27 volt normal acid battery ke floot charging seting hay. Ye kam hay. Setting sahe kare.
Dear, gravity check krwa k aye hain. Wo sb ok hai.
Floating charging kitni honi chahie.
Tubular batteries mein.
Best chal raha hy ziewnic
Allah kry hmara issue bhi resolve ho jaye. Ameen.
اس وقت اپکی بیٹریٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕٕاں چرجڈ ہے چارج کا نشان اپنی جگہ پر قایم ہے اپ اس پر لوڈ بڑھایں تو یہ پروڈکشن زیادہ کے گا اپ نے بتایا نہیں کہ کتنے پینل لگإے ہیں اگر اپ سیٹنگ میں جایں گے تو پھر پتہ چلے گا انورٹر کے مینول سے اپ با اسانی خود سارے سیٹنگ کر سکتے ہیں کوشش کرے
Brother 6 panels lgaye hain.
Bhi app ka masla hal howa k nihi mara b yahi masla hy agar howa hy to tora rehnomye kary k kasy tek howa
Assalam u alaikum. 2 engr sy ni hua tou mene mitti daal di.
Bhai es inverter ko koi masla nahi hai.
Jab jab load dalain gay tab output ziada show hogi.
75w consumtion k sath 3 kva show nahi karay ga ye system.
Ap iron on kar k phir dekhain. Output 1 kva k pas ho jaye gi.
Esi tarha jesay jesay load dalain gay tab tab output increase hogi.
Pr batteries charge ni ho ri. Backup ni mil raha.
Sir ye masla nai koi , its in programming whrn you use it as off grid mode it will generate power as per load demand only , and batteries charging settings not done proper by your installer or you have shut down battery breaker after their setting saved , bec it Will delete settings when disconnected batteries.
G inshaAllah.
Eid mubarak to you ❤
Tubbler battery ki setting
No 5 user set kary
No 26 29.6 set Kary
No 27 27v set Kary
No 29 21v default rehnyday
Or battery ki gravity check kary Ik dafa ager low hy to no 26 ma JA k charging voltage full kerdy k gravity pora hojayega. Ye setting 24 hour k bad wapis no 26.. 29.6 pay set kary
JazakAllah ❤
Jaldi mei video bna li bhai ny 😂
👍
Bhai battery 27v pr he mtlb k battery charged he to overcharge q kre ga
The issue is something else.
AOA! Sir Its a simple issue. I faced this issue way back also. The thing is your system is 3.5 kilowatt. At peak hour like 11am-3pm it will generate power at 70% efficiency which is in between 2 to 2.5 kw. So, After 3pm the production decreases and to run the load the inverter takes power from batteries to run your load. Therefore, when sun sets your batteries are already at 40-50% of its capacity. And after sunset when there is load shedding your batteries will not provide Backup. For this Inverter Maximum PV Current is 27 A and MAximum Voltage is 450v. Check your PV strings they might be connected in a wrong way. But """""the simple solution to your problem is increase your solar panels use the full potential of the inverter install up to 6.5 kw Solar panels.""""""""" Also, How many panels have you connected and there power ratings. The thing is solar power is very inefficient and you have to install solar panels double the power you consume. lets say you consume 5kw then you should install 10kw which will charge your batteries and will run your load. Hope it will help you.
Yes, exactly. I have bought more panels and that will increase the system to 5.85 kw. And thanks for your detail guidance. 🙂
Malik battery full charge hy 27v .
Automatic cut off hota hy inverter ma. Battery drain hogi to inverter charging show kerga.
Backup ni dy rahi. Means full charge ni.. just show ho raha k ho gae charge.
Bahi battery ap ki fully charged ha 27.0 floating charge pa ha iss liya 0 amp ja rahye... Our 2nd jitna ap ka agay load chal raha ho ga solar utni he production bnaye ga na.. same gab ap garie chalatay jitna ap acceleration datay usi hisab sa engine zor lagata our garie bagtie .. asa to nai hta k ap ki speed 40 ho our engine rpm 9000 pa ho... Hope so samj aa gye ho gi
G lekin battery k backup ka issue hai.
@@SaeedFlicks ap setting shai karain first battery type ki setting ko use pa karain our us k bad 26,27 no setting dakhain idr jo bulk voltages ki setting ha usay 29.2 karain our floating charge k voltages 27.5 karain
@@rameezyousafofficial4449 ok inshaAllah.
Inverex is much better 👍
Agreed.
Assalam o alaikum,
I have installed the same inverter, I can guide you through the phone. If you haven't figured it out.
Ok. InshaAllah.
Please share with us your experience as well. JazakAllah.
I think, it is worth the price it offers.
There are three voltages in a battery, low, floating and full.
The voltage is you see is the floating voltage, it is considered fully charged
@@ThisIsAllFake ye tou long term experience sy hi maloom hota k chez ki quality kesi hai.
Dear ziewnic Solar Inverter kasa ja Raha ha.
Update
Alhamdulillah abi tk ok hai. But kbi ham ny koi major load ni chalaya abi tk..
بھائی ۔ اِس انورٹر کی رسید کی کاپی لگا کر Consumer Court میں شکایت کر دیں۔ کمپنی والے کچھ ٹھیک ہوجائیں گے۔
Dear, company ki services sy shikwa hai..
Baki abi iski performance py kuch ni keh skta.. ye tou proper settings k baad koi expert bta skta hai k issue kis chez ka hai.
bhai Jan is ki inverter copy sy battery ki settings solar wali full kray ap ki battery ki limited solar or Wapda pr 27.1 fix hai
G inshaAllah.
As sallam o alakom bahi. Ap battery ko discharge kare without battery and solar os pa load daly jasy he down jojaye. Is wapda on kare ya solar charging kay lena. Pir ap time note kare. Aga 1 ganty may ampare zero tak ata hay. To pir ye charging setting or ya battery Acid specific gravity ka madla hay.
Specific gravity check krwae hai mene. Uska masla ni hai.
Flooting chargeing 28 volt kardy pir ampare zeyada khayega. Lkn pr battery life ma kami ajate hay
@@SaeedFlicks bahi jan battery TYPe FLD pay rakhy. Ya sahe technician sa setting kardy. Baqi sab kuch teek chal raha hay. Inver ter battery full hony ya flootine charging pay 0 ya 1 ampare leta hay.
@@shiningstar7677 thanks
Bhai jb battery charge ho jati hai to inverter automatically charging sto kr de ga. Agr charge e krta jae to btteries over charge hongi..
Yes.
Ye wifi say kesay connect hosakta hai? Display setting ki koi video ho to mehrabani hogi
Mei try krta hu koi mil jaye.. lekin I guess inka wifi alg sy purchase krna prta hai.
Domgle lene parte ha separate 11000.ke@@SaeedFlicks
Battery float charging option check kary user mannual sy shyed o band hu
👍
Piary bhai 2 batteries mein just 1800 sy 2000 watt store hoty agr 300 watt load dalo gy 6 hour chaly ga agr 500 watt dalo gy 4 hour chaly ga...raat ko load na dala kro batteries farig ho jaein gi jald hi
Ok
Only lithium batteries give true backup. Ye tall tubular and lead acid batteries fail hain in Solar system giving backup. Ap SUB mode per Inverter ki setting rakhein. Baqi in inverters me MPPT laga hota ye solar say utni hi power produce kertay jitni gher me load chal raha hota. Apka system bohat zaberdast hai laganay walay ki tareef kerni chahiyay. Shuker Kerein k apko
ye naimat hasil hai.
Lets see k batteries kea kaam krti hain.
Bulk changing 28v krdo lga rahy ga charging per
👍
Muhjay Rawalpindi market may saray shops walon nay bout tareef kithi k acha inverter hai even jis k pas ye inverter nae ta wo bue keh raha ta k acha inverter hai but social media pay story kuch or hai.
I purchased 8500kw 10000pv
Ab may pareshan k kia keron?
Kis hawaly sy preshan hain ap? Koi issue kr raha inverter???
واش کرنے کے لئیے بریکر نیچے کریں اور اگر رات میں لوگ سوۓ ہوۓ ہوں اور بارش ہو جاۓ تو کیا کریں ؟
Barish ki koi bhi tension nahi hai.
Wash kartay hway solar breaker iss liya nechay kiya jata ha k jo banda wash kar raha usay current lagta ha halka halka sa us sa safe rahnay k liya breaker off kiya jata ha .. barish sa kia masla hna no isue
@rameezyousafofficial4449 exactly
❤@@rameezyousafofficial4449
🤣😂🤣😂🤣 bohat khoob
Assalamoalaikum. Apka battery wala problem solve hoa??
Wa alaikum salam. No.
Its already fully charged, if CHG icon blinking it means charging, if it stays still it means fully charged.
@@danishriaz8416 dear, only 3 hrs backup..
Assalamu Alikum,Bro apka battery Ka problem solve howa
Agar problem solve Nahi howa to send me your wattsapp number
Ap preshan nhi ho battery usd nahi horahi is wajha se battery volt 27 hai jaha battery se current jaye ga battery volt drop honge ye charging pr ajaye ga
AoA, Bhai jaan, may b ye wala inverter lay k phas gya hu, after sale service hai nhi, or jinho nay install kia system wo jawab day gye hain k unhay samj nhi aa rha, or mujay bill ziada aa rha hai, earth light b on hai meter pay. 😢
Hm. Kea keh skty bs. Ap company walo ko check krwayn.
Bro your satting issue
Zewnic inverter best hy I use last 7 month
G inshaAllah ye aaj kal mei resolve ho jyega.
Janab Inverter ki sitting wahi karega jinko apne installation charges diye hai ab Inverter company fault ki zimadar hai apki sittings ki nai
Inverter mei fault hai ya nahi..ye tou khud company decide krti na.. aur ye aa k dekh k pta chalta.. na k istikhara kr k.
@@SaeedFlicks bhai mere apne jinko payment ki hai installation ki wo aker deke observation karengy ager faulty howa tu ap claim kar sakte hai otherwise koi b company apke liye aise nai ayegi chahye inverex ho ya Jo b ho
@@armaan00795 inverex waly aaty hain. Mene maloom kea hai. And haeir waly bhi aaty hain.
@@SaeedFlicks acha chalo achi baat hai lakin ap setting main changes karo waha se masla hal na ho tu phr alag baat hai
@@armaan00795 InshaAllah ho jyega. ALLAH khair kry ga 😊
Don't use Ziewnic Inverters 😢 bad experience 🤨
👍
inverters k bht role hote hen me recommend kru ga k ups plus mppt controller le lo thore energy losses hon ge but bht paidar kaam ho ga
@@desiknightsofficialMppt systrm me, kya Wapda on hony pr battery silent mode ma rhy ge oor serf load shedding k duran he use ho GI?
@@tayyabraza2803 bhai ye mppt different types k hote he or in me sb functions available hote he me ne b abi 3kw system k lie lena he mppt us k bare me research kr raha hu
@@tayyabraza2803raat ke time ,yes, ups will charge the battery and only use if load shedding. but after the load shedding, it will start to charge the battery and hence till morning your battery may get charged only on wapda which is not optimal. and there will not be commendable bill reduction.
Bhai mery ghar be yahi ha ya jo 0 a raha ha battery ma as ka mtlb ha ka battery full ha battery kuch be charging ni ly rhi ya koi issue ni ha
Dear, backup ni mil raha
Bhai Kitna backup mil raha ha apko tubular ka backup normal hi hota ha
@ABDULREHMAN-bz2si still trying to figure out.
(NO16.....CSO) (NO11.....20A) (NO5.......USE) (NO3.....UPS) (NO1.......SUB) settings ok
👍
Quick question: Can this ziewnic inverter work without batteries?
Its hybrid so I guess it require batteries. Further, I will confirm tomorrow.
@@SaeedFlicks Please confirm brother. I am about to buy this inverter. Should I buy? Do you get your problems solved or not?🤔
@@SEO_GUY No. I have confirmed. It cant work without batteries
@@SEO_GUY not recommended.
@@SEO_GUY Only on-grid inverter chaly ga without batteries.
Solarmax best company for services. I purchased onyx pv9000 model. Evertime I needed help Mr Saeed was always available.
Thanks for guiding the community ❤
Bhi gee camera uthay Kay insaf Karo. Zwenic is working perfectly. Aap ki settings proper Nahi hai.
My dear. Mei inverter py abi tk negative review ni dya.. mene sirf company ki after sales py review dya hai k unho ny cooperate ni kea..
Kia ye inverter khreedna chahye?
@asifshadowofdarkness dear I recommend k ap uss company k inverter lyn jiski after sale service boht hi achii ho.. ye aap ko market research sy maloom hoga.
@@SaeedFlicks brother inverex ka budget nai hai jo sbse behtreen hai lakin is inverter ki wese kaafi mashoori hui hai isilye me sochra hu isko lganay ka..isilye ap se pucha hai k ispe load agr solar se chalay to sai chalta rehta ya nai
@@asifshadowofdarkness dear mei iski specs py video bnaonga. Phir ap decide krna k ye apki needs ko fulfill krta hai k ni.
Bhai sb Apka inverter bilkul sahi chal rha hy. Inverter mn automatic system hota hy jb load increase hota hy to production bhi brh jati hy. Batteries full charge hn isliay wo batteries charge nhi kr rha
Dear, batteries show ho ri full charge but actually hain ni.
@@SaeedFlicks apko kysy maloom?
@@kashifmahar9199 backup ni dy rahi. Check b krwaya hai.
@@SaeedFlicks OK
Ye issue zeiwnic k har inverter mai hai mera b bad experiance raha
Sad.
Toyota se gari lo, agar kharab ho jae to Toyota ne engineer ko ghar bhejna hota hai ? woh bhi free main ? it doesnt work like that, nothing is free for life
Car chal k ja skti.. inverter ham utar k ly ja skty? Ni na..
you must change the battery bulk charging voltage and floating charge volt
How to do this?
Don't you have instructions book ?
@@jamesmike9475 I have it.
Mn ye inverter lyna chah rha hn. Already tubular batteries install hn
Agr 12V wali 4 batteries installed hain tou 48V mei apko inverters k boht options mil jayngy.
24 volt 3.5
@@kashifmahar9199 12v ki 2 hain???
12 volt ki 2
G
Panels tu btay nh kitny install kiy
@@rashidhayat1 tb 6 thy total. Ab 10 hain.
total cost with installation ap ne nahi batai
Dear, wo mene video mei explain ki hai.. ab cost kum ho gae hai.. jo fix cost thi mene btae thi.. for example iron structure..
Baki inverter ki price bhi btae aur panels k current rates bhi.
Best chal raha hy ....inverex b ghar nai ati
Allah kher kry customers ki 😊
Fronus +zienewic =local inverters
I have same opinion.
Battery full hai charging ruuk gai hai. Battery voltage kum ho gi tow solar charge karey ga.
Dear ye backup ni dy ri.
Kuch din pehlay youtube video mein kisi ney backup ka hisab bataya tha k 300 watts ka load ho tow 4 battery wala agar system hai tow battery backup (phoenix tx 1800) 3 hour chalay ga night mein. 2 battery ka bhi bataya tha lakin mujhey yaad nahi. Sha-ed 2 ghantay bataya tha. Aap ney ye first check karna hai k raat mein aap ka battery per kitna load chalta hai. Meray pas bhi zeiwenic ka 4 battery wala system hai 6 panels wala. Din mein 600 ya 650 watt chalata hai solar sey aur battery bhi charge karta hai, lakin sham sey battery per 200 ya 250 watt bhi bohat jsldi battery ko down kar deta hai aur inverter beep karnay lagta hai.
@@k.m.9724 Oh. Ham ny tubular li hi iss liye k long backup ho. 🥲
Sir ziewnic na he lein to behtar ha is k bahut issues samny aa rahy hain
Oh. Allah rehm kry. We are facing issues.
آ پ کو پتہ ھی نہیں
@@waqarhussain7755 👍
In Pakistan every thing 2nambry 😮
Allah khair farmaye. Ameen.
💯
@@AliHaider-hq4kf 👍
Bhai me bhi bhot tang hun ziewnic ka invetor le ker
Bs Allah reham farmaye.
جب بیٹریز فل چارج ہیں تو پھر کیسے سولر سے پاور لے
Backup ni deti na
bhi ap ye dekhe na apke inverter ki battery charging current kitne amperes pe set hai q ke apne 2 batteries lgai hoi hai to 27 28 amperes pe battery full hoti hai nhi to inbox ajai mai apko bta deta hu
Boht setting krawae lekin masla hal ni hua
O bhai ap ki 2 battery 27 volts show ho rhe hn iska matlab ha k battery's full charge ho gie hm
😅
App consumer court main jaky application dain
Allah na kry aesi nobst aye. Settings ka masla hai tou kisi achy bndy sy khud krwa lyngy.
Nahi ap ko Karni chahiye kay 5years ki service ka keh rahy hain per dey nahi rahy
Apnay shaher main say ksy be achay solar mechanic ko lay ain wo masla hal ker dega
G inshaAllah.