Tagalog - Generator Main Switchboard Aconis CPU system fail. PMS controller fail Troubleshooting

Поделиться
HTML-код
  • Опубликовано: 18 сен 2024
  • Tagalog - Generator Main Switchboard Aconis CPU system fail. PMS controller fail Troubleshooting

Комментарии • 2

  • @erabhishekgupta7651
    @erabhishekgupta7651 3 месяца назад

    But let suppose if we need to change this Module what is the procedure need to do blackout to replace this module or how to do that please explain.

    • @BarkoTv
      @BarkoTv  3 месяца назад

      No need to black out, just use another generator to Synchro in bus bar, then now you can replace the module that is the Generator have problem