Setting Reference Using APC Test Reference Cords on the Fluke Networks CertiFiber® Pro

Поделиться
HTML-код
  • Опубликовано: 9 янв 2025

Комментарии • 5

  • @markakrellcom3184
    @markakrellcom3184 2 года назад +1

    Excellent video instructions. Thank you! 😊

  • @danielaguirre3490
    @danielaguirre3490 Год назад

    VERRY helpful on fiber terminations 😤🚀🚀🚀😤😤

  • @kylebaylor4226
    @kylebaylor4226 10 месяцев назад

    Can you explain explain what to do if your TRC values come up negative?

    • @MikePennacchi
      @MikePennacchi  10 месяцев назад

      Negative TRC Verification values are typically caused by not waiting long enough for the modules to warm up. As they warm up the power output increases. It is best to wait 5 minutes after turning them on to set reference. Another cause can be having the TRCs coiled up when you set reference, then uncoiling them to do the TRC Verification. The coils add loss that is removed when they are uncoiled.

  • @SeihingSei
    @SeihingSei 8 месяцев назад