Not change any sensor and not renewed module and not change address also but received LMX12 No answer fault. No spares onboard. Is it possible to use third problem’s solutions you gave for this fault? Like put off all dip switch and then connect it wait for three times blinking and then again put back same address?
You can try it, no harm in that but this process only rescan the new sensors. If this process does not work try swapping lmx12 with other and see if problem swap to confirm exact problem.
@@sailorsrikantsingh yes exactly. Easiest way to find out where is fault instead of checking whole lot of sensors in the loop. Already swapped and found module itself faulty and raised requisition.
For cable break check that loop continuity and for unknown loop device u must have changes anything or check manual or try to recall what changes u have done in past and based on it u can judge
Where will I get manual including all types of fault code in the consilum m4.3 central panel
❤❤❤❤😊
For your last issue I think you can also just rescan the loop from the service menu without removing the card.
I will try next time, thanks
How to set the address in the address unit of consillium while using the dip switches, address unit which is installed in the circuit separately
Thanks bro. Im having the same problem, no answer & i was hoping to restart module as you did
ur welcome
Nice bro ❤❤
Thanks
Not change any sensor and not renewed module and not change address also but received LMX12 No answer fault. No spares onboard. Is it possible to use third problem’s solutions you gave for this fault? Like put off all dip switch and then connect it wait for three times blinking and then again put back same address?
You can try it, no harm in that but this process only rescan the new sensors. If this process does not work try swapping lmx12 with other and see if problem swap to confirm exact problem.
@@sailorsrikantsingh yes exactly. Easiest way to find out where is fault instead of checking whole lot of sensors in the loop. Already swapped and found module itself faulty and raised requisition.
I'm facing so many problems and some one removed wire and left the company
Go slowly slowly and step by step u will solve it...
Im having problem sir, found LOOP ANALOGUE 1CBALE BREAK and UNKNOW LOOP DEVICE
For cable break check that loop continuity and for unknown loop device u must have changes anything or check manual or try to recall what changes u have done in past and based on it u can judge