This is such a great video, we were having trouble until I came across this video. Thanks so much for taking the time to go through controlling via Modbus RTU! Thanks!
@@alirezakazemini hi sir.. I need your help for commissioning drive.. can I get your mail address or contact number that I can send you my abb drive issue
Thanks for the video! I have a question, I have a ACS880-01 and I want to connect to the EFB Modbus RTU. From my PLC, do you have an explanation on how to get the right register address that I want to read or write? My experience with Modbus = 0, so any help is appreciated.
Yes, I should accept that part of video is passing so fast. So better I explain what is happening at 10:23 of the video. I explain it as a new comment below the video
How to read frequency, current, voltage and so on from Modbus RTU? Watch the video from 10:23 , it is going fast, so I'm explaining what is happening. I'm reading Modbus registry list from 40001 to 40012. Addresses from 1 to 4 are set by factory, however you can continue this setting to get whatever you want in number 5 or 6 or whatever you choose here. Now pause the video at 10:44 , here I have set the address 40009 to show me frequency on 32bits integer. This is whey when I went for laptop it could show me frequency at address 9 You can different formats, I choose 32bit to get more accuracy. You can choose current instead of frequency. You can even choose something which is not parameter, from other lists. From the time 10:44 to 10:50 , 4 times I pushed exit button, by following this path also you can see how I set address 9 to show me frequency.
Hello, that error appears for some other possibilities also. You will need to go through diagnostic steps. I have no time but contact me by insta or whatsapp let’s see.
In the complete list of parameters 58.01 Embedded fieldbus, you enabling a protocol, and depending on which protocol you choose corresponding setup will appear. Then you just need to set these communication parameters match with other device which is going to communicate with this VFD. Profibus also is a serial communication similar to modbus RTU
In the video only 20 seconds from the time 6:20 to 6:40 are about protocol parameters. Even these parameters are similar for all serial communications like modbus RTU ot Profibus. So if you planning to set your VFD for Profibus all your parameters will be the same as in this video. You can get more help if write me in which time of video you need more information
Hello, sorry for late reply. Sure you can do that. Just consider Alarm and Interlock are different, Alarm will need resetting, Interlock doesn't need resetting. And both of them give you chances for NC or NO triggering. So you can apply any SOP scenario for a fire alarm.
Hi, do you need to wire up I/O terminals even when you want to run a machine from control display/keypad attached to the drive? ( I don’t do any external control). I just connected 3 phase input and 3 phase motor connection.
Boss i have question my vfd.same model but frequency is not working. hand and auto whats is the solution? Now temporary working freq.input set to 40hz .
How to connect ACS880 drive to Pc through Fibre optic cable ? Does RUSB-02 DDCS adapter is compatible for communication? Which channel is used in FDCO-01 card for Drive composer communication through Fibre optic?? Com port numbers are not showing..
Yes, RUSB-02 DDCS adaptor can help but basic ACS880 suppor requires that you have the DriveDA OPC server (included in Drive composer pro) installed. DDCS communication protocol also is not available for ACS880. You can check working manual "DriveWindow 2 User Manual - ABB"
Are you going to have a redundant plc in your network and 13 inverters in one serial communication? contact me through WhatsApp maybe I can help you with TeamViewer also. +90 536 471 54 64
Hello Alireza, First of all thank you for this great demonstration, I have a question regarding the access level. I would like to change the modbus RTU settings (address, baudrate...) but it doesnt give me access to edit. I have only one password (10000000). I think that there is a service password. I would appreciate it if you can help me on this Thank you!
this error appears when there is no connection between the control side and the power side of your driver. I need the code and the serial number of your Driver. how old is it? you need to check whether the controller is faulty or it's the communication shield or the connector cable. is the driver wall mount type? if the connection is fiber optic and its age is more than 4 years I recommend changing fiber cables. If this info is not enough send me pictures on my WhatsApp at 0090 536 471 54 64
Hi i want to control VFD like this : start and stop using from DI and DI2 and referance from Modbus For doing this :First I must to do Enable Embedded Fieldbus from 58 parameters then i must to chose Data I/O Output Frequency end the end i must to change AI Referance from Embedded Fieldbus Did I understand correctly ? If you help me i will be happy Thank you.
Yes, one of DI should be set to start by default but looks like you want to start and stop by pulse, so it's better to check the list of DI in I/O menu . You can also contact me through WhatsApp while setting your VFD. +90 549 415 3320
This is such a great video, we were having trouble until I came across this video. Thanks so much for taking the time to go through controlling via Modbus RTU! Thanks!
Super sir
Very informative, with the help of this video, I was able to commissioned my 580 drive. thanks again from California.
Your success is my pleasure
@@alirezakazemini hi sir.. I need your help for commissioning drive.. can I get your mail address or contact number that I can send you my abb drive issue
استاد عالی بود
Thanks for the video! I have a question, I have a ACS880-01 and I want to connect to the EFB Modbus RTU. From my PLC, do you have an explanation on how to get the right register address that I want to read or write? My experience with Modbus = 0, so any help is appreciated.
ممنون استاد در مورد تنظبمات سنسور فشار و دود سوال داشتم
Thank you sir
Fantastic video...could u inform us how we can read current/ rpm/torque of motor through modbus rtu
Yes, I should accept that part of video is passing so fast. So better I explain what is happening at 10:23 of the video. I explain it as a new comment below the video
How to read frequency, current, voltage and so on from Modbus RTU?
Watch the video from 10:23 , it is going fast, so I'm explaining what is happening.
I'm reading Modbus registry list from 40001 to 40012.
Addresses from 1 to 4 are set by factory, however you can continue this setting to get whatever you want in number 5 or 6 or whatever you choose here.
Now pause the video at 10:44 , here I have set the address 40009 to show me frequency on 32bits integer. This is whey when I went for laptop it could show me frequency at address 9
You can different formats, I choose 32bit to get more accuracy.
You can choose current instead of frequency.
You can even choose something which is not parameter, from other lists.
From the time 10:44 to 10:50 , 4 times I pushed exit button, by following this path also you can see how I set address 9 to show me frequency.
Please sir contact number share us❤
My ACS880 VFD shows the alarm check connection but everything is normal and so good so far.pls help me
Hello, that error appears for some other possibilities also. You will need to go through diagnostic steps. I have no time but contact me by insta or whatsapp let’s see.
What parameters have to be entered by connecting ABB Acs 580 VFD to Pofibus?
In the complete list of parameters 58.01 Embedded fieldbus, you enabling a protocol, and depending on which protocol you choose corresponding setup will appear. Then you just need to set these communication parameters match with other device which is going to communicate with this VFD. Profibus also is a serial communication similar to modbus RTU
What parameters do you need to enter to connect to profibus in VFD 580 and what codes do you need to enter?
In the video only 20 seconds from the time 6:20 to 6:40 are about protocol parameters. Even these parameters are similar for all serial communications like modbus RTU ot Profibus. So if you planning to set your VFD for Profibus all your parameters will be the same as in this video. You can get more help if write me in which time of video you need more information
Can I connect this drive to relay module of fire alarm for tripping the motor on receiving fire alarm signal ?
Hello, sorry for late reply. Sure you can do that. Just consider Alarm and Interlock are different, Alarm will need resetting, Interlock doesn't need resetting. And both of them give you chances for NC or NO triggering. So you can apply any SOP scenario for a fire alarm.
Hi, do you need to wire up I/O terminals even when you want to run a machine from control display/keypad attached to the drive? ( I don’t do any external control). I just connected 3 phase input and 3 phase motor connection.
No, just make sure your control source is on local and then push the green button.
Great Job!, i need to support for VFD integration MOdel ACH580
I will try to help
@@alirezakazeminicould you please send test email, so that I will send you the details please
@@alirezakazemini mohammedmga@gmail.com
Ok, i sent
Boss i have question my vfd.same model but frequency is not working. hand and auto whats is the solution? Now temporary working freq.input set to 40hz .
you cant change the frequency? contanct me in whatsapp 00905494153320 explain by photo, please
Great job!
Thanks!
How to connect ACS880 drive to Pc through Fibre optic cable ? Does RUSB-02 DDCS adapter is compatible for communication?
Which channel is used in FDCO-01 card for Drive composer communication through Fibre optic??
Com port numbers are not showing..
Yes, RUSB-02 DDCS adaptor can help but basic ACS880 suppor requires that you have the DriveDA OPC server (included in Drive composer pro) installed. DDCS communication protocol also is not available for ACS880. You can check working manual "DriveWindow 2 User Manual - ABB"
Thanks for uploading this video. Somalia
Hello Good time I intend to network 13 580 inverters with Madbas with 2 delta plc by dlink. How do I read or write information now?
Are you going to have a redundant plc in your network and 13 inverters in one serial communication? contact me through WhatsApp maybe I can help you with TeamViewer also. +90 536 471 54 64
Hello Alireza,
First of all thank you for this great demonstration,
I have a question regarding the access level. I would like to change the modbus RTU settings (address, baudrate...) but it doesnt give me access to edit. I have only one password (10000000). I think that there is a service password. I would appreciate it if you can help me on this
Thank you!
Sure, may I know the name of your driver? you can share its pictures on my Instagram or Whatsapp
@@alirezakazemini dear sir can we have your number because I’m facing some problems need your help
Aoa sir we have a abb vfd ACS880-250kw we faced a problem
Pu communication fault 5681
Sir can you tell how to fix it
this error appears when there is no connection between the control side and the power side of your driver. I need the code and the serial number of your Driver. how old is it? you need to check whether the controller is faulty or it's the communication shield or the connector cable. is the driver wall mount type? if the connection is fiber optic and its age is more than 4 years I recommend changing fiber cables. If this info is not enough send me pictures on my WhatsApp at 0090 536 471 54 64
Please explain vedio share
🙏👏
با عرض درود
مهندس من نیاز به یک دوره تخصصی اینورتر دارم، شما می تونید کمکم کنید ؟
Hello dear friend, if you are able to travel to Istanbul, maybe I can arrange a training.
@@alirezakazemini Alireza Jan ,Is there any other ways for training i can't travel to istanbul,مچکر از ویدیو عالی
Hi i want to control VFD like this : start and stop using from DI and DI2 and referance from Modbus
For doing this :First I must to do Enable Embedded Fieldbus from 58 parameters then i must to chose Data I/O Output Frequency end the end i must to change AI Referance from Embedded Fieldbus
Did I understand correctly ? If you help me i will be happy Thank you.
Yes, one of DI should be set to start by default but looks like you want to start and stop by pulse, so it's better to check the list of DI in I/O menu . You can also contact me through WhatsApp while setting your VFD.