Partial discharge testing on power transformers

Поделиться
HTML-код
  • Опубликовано: 22 авг 2024
  • Learn about the importance of partial discharge testing (PD testing) on power transformers. Partial discharge is a major cause and reliable indication of developing insulation defects in power transformer bushings and windings, which can cause their eventual failure and costly outages. PD testing is an effective diagnosis method used to detect and localize insulation defects and to evaluate the overall insulation condition and risk of failure in power transformers during factory testing, site acceptance testing (commissioning), as well as in-service troubleshooting for effective maintenance planning. For highly reliable, industry-standard PD testing on power transformers, OMICRON recommends the MPD 800 universal partial discharge measurement and analysis system.
    ☝️ Learn more about MPD 800 on our website: www.omicronener...
    ☝️ Learn more about PD testing on our website: www.omicronener...
    ▶️Interested in PD testing? - Watch all of our videos: • Partial Discharge Test...
    _
    Would you like to find out more about OMICRON, our passions, and our products?
    🌐Check out our website: www.omicronene...
    Or follow us on social media:
    👉On LinkedIn: / omicron-electronics
    👉On our podcast Energy Talks: www.omicronene...
    👉On RUclips: / @omicronenergy

Комментарии • 15

  • @romitshah8399
    @romitshah8399 4 года назад +1

    Which are the different methods for the measurement of partial discharge (PD) in power transformer.

    • @omicronenergy
      @omicronenergy  4 года назад +2

      Dear Romit,
      There are many different methods to perform PD measurements on power transformers.
      Main offline methods:
      - According to IEC 60270: using coupling capacitor or bushing tap (single and three phase)
      - UHF measurement using UVS 610 sensor at the valve (ultra-high frequency antenna)
      - Acoustical localization using PDL 650
      Best Regards
      your OMICRON team

  • @sueandlindsay1777
    @sueandlindsay1777 2 года назад

    For a site test what is the detection bandwidth of the MPD800 ?

    • @omicronenergy
      @omicronenergy  2 года назад

      Dear Sue and Lindsay,
      thanks for your comment and for your interest to our videos :)
      The MPD 800 offers a wide range of filters. The bandwidth and center frequency can be adjusted for the best signal to noise ratio at site or can be kept the same as for the FAT result to have comparable settings. For the charge measurement (QIEC value), the center frequency and the bandwidth are usually set in alinement with IEC 60270. For RIV testing the CISPR or NEMA standards are followed. For more information, please visit: www.omicronenergy.com/en/products/mpd-800/
      Best regards,
      your OMICRON team

  • @pawankumar-gj7sb
    @pawankumar-gj7sb 4 года назад +1

    Sir is this online or offline testing on transformer.

    • @omicronenergy
      @omicronenergy  4 года назад

      Dear pawan kumar,
      thank you for your interest!
      There are only offline measurements shown in this video but online measurements are possible as well.
      Best Regards,
      your OMICRON team

  • @asishthanapati7614
    @asishthanapati7614 3 года назад

    Good sir

  • @himariarosa
    @himariarosa 4 года назад

    Good day sir, if online measurement is possible.. can I ask if Mathematical model of PD in transformer is possible?

    • @himariarosa
      @himariarosa 4 года назад

      Thank you because it's my topic for our thesis 🙏

    • @omicronenergy
      @omicronenergy  4 года назад +1

      Dear Mary,
      thank you for your interest!
      Simulating PD is a topic of research and the question highly depends on your goal. A model can only show influences, which are considered by the modelling approach. It would be rather difficult to cover all influences.
      So, the question is, what should the be considered within the model? PD are highly dependent on many influences (structure of the asset, geometry of electrodes, insulation material, quality and age of the insulation, by products, defects, temperature, voltage level, rise time dU/dt of the test voltage, electrical field distribution, start electron) and much more. In theory models can be found for physical effects, but it takes a lot research to get a valid model. For this reason, it makes sense to define the terms and conditions for finding a model and to focus on a specific effect.
      We recommend discussing the goal and following up on research based on the definition of your thesis.
      We hope this answer could clear some things up already! If you want some more information please contact our technical support team: www.omicronenergy.com/en/support/technical-support/
      or use the following link to see all the training classes currently scheduled: www.omicronenergy.com/en/training/courses/f1/language:English/f3/application:Partial%20Discharge+Analysis+on+Power+Transformers/
      Best regards,
      Your OMICRON team

    • @himariarosa
      @himariarosa 4 года назад +1

      @@omicronenergy thank you sir/ma'am.. the transformer model that possible we can use is the Distribution transformer three phase .. We are conducting more datas regarding this topic.. thank you for your response

    • @mohamedayoub6064
      @mohamedayoub6064 3 года назад

      @@himariarosa hi mary
      my research topic is about this too
      can i know where can i read about the results of your lab team?

  • @gaspermilonge5121
    @gaspermilonge5121 Год назад

    Wow...