This functionality is supported by S7 1200. The HART functionality will require remote IO that supports HART pass trough. the mA scaling will work on S71200 PLC with IO cards or built-in AI. Right click the PLC on hardware view and select change PLC.
@@IOTConnectivity Actually it is the Ready for use of the WP321. I right click on the PLC in the hardware view and select Change PLC, and I am only sold S7-1500 options
Sorry got my videos mixed up. I know the S71200 has it's own WP231, I'm not 100% sure the WP321 is compatible with the S71200. Have you tried adding it into a blank project rather than a reference project. Add the PLC , the IO card with WP321, see if this compiles.
@@IOTConnectivity Yes, as you said, it has its own WP. But the WP321 connects to the ET 200SP, and there it is compatible with all S7 devices. However, the Ready for Use program appears as an S7-1500 and cannot be changed directly for another device. I would have to redo the program. Thank you for your response!
It works on S7-1500 with siwarex wp231?
hello sir
can you send me link of this project
I can't download from siemens
Thank you in advance
Excellent video. How can I change the device to an S7-1200?
This functionality is supported by S7 1200. The HART functionality will require remote IO that supports HART pass trough. the mA scaling will work on S71200 PLC with IO cards or built-in AI. Right click the PLC on hardware view and select change PLC.
@@IOTConnectivity Actually it is the Ready for use of the WP321.
I right click on the PLC in the hardware view and select Change PLC, and I am only sold S7-1500 options
Sorry got my videos mixed up. I know the S71200 has it's own WP231, I'm not 100% sure the WP321 is compatible with the S71200. Have you tried adding it into a blank project rather than a reference project. Add the PLC , the IO card with WP321, see if this compiles.
@@IOTConnectivity Yes, as you said, it has its own WP. But the WP321 connects to the ET 200SP, and there it is compatible with all S7 devices. However, the Ready for Use program appears as an S7-1500 and cannot be changed directly for another device. I would have to redo the program.
Thank you for your response!