For Example 12v100Amp two batteries are used... If connected in series then 24v100Amp , setting 02 is 100/10=10Amp if connected in parallel then 12v200Amp, setting 02 is 200/10=20Amp
زبردست بھائ جواب نہیں آپ کی تحقیق کا, بھائ آپ لیتیھم بیٹری پر بھی مکمل معلومات کی ویڈیو بنائیں, اور یہ بھی بتائیں اگر اتنی مہنگی بیٹری لگائ جائے تو اس کا کوئ فائدہ بھی ہے ,
Salam boss aap ne bohat ache tareke se inverter ki setting samjhai hain bohat bohat shukariya aap ka. Sir mere inverter utility se battery charge nhi kar rha please mjhe guide kare.
Bhai bohtt ache se samjha ya apne Mashallah bohht alaa Bhai mere yahi inverter inverex veron 2 Uss me raat ko reverse ki light on ho jati he meter pr Kindly ye masla kese hal kro
Asif Bhai good video I have two tall tubular batteries TX 2500 and 4KVA inverter. I have set the battery charging at 20 ampere....this is right setting please reply
Assalam o alaikum, I hope you are doing well. First, thank you for creating such a detailed video. Second, I have a question regarding the settings you mentioned. When I keep my electric breaker on, even after the solar is on, the electricity lines going to the home remain active. When I turn off the breaker, those lines get cut off. Third, for a 585-watt panel, what is the minimum and maximum wattage and amperage it provides, and how much does it generate during rainy weather? Or normal weather
Mere pas old model infinisolar inverter solar V lll 3KVA ke sath 125A 15 plates ki 4 batteries jo ke 48V installed hai 585watt ke 8 solar install hai please ek video inverter settings ki bana de
Masha Allah ur vidios is awesome Bhi mujy ap se ye pochna h m konci setting kro k n sirf solar hi use kro or sham ko wapda use ho bs or battery tb use ho jb loadsheding ho
@@TechnicalAsif747 m ne apki sari vidio dekh li h or oso setting ki ab meri battery wapda se charge ni hoti h bs 1 ab 1 sawal ap se pochna h jb m koi heavy load on krta ho to inverter battery use kr k heavy laod on kr deta h wapda per shift ni krta load ye setting kesy ho m ne bypass b enables kiya h
السلام علیکم Dear Asif sb 2nd setting k barey me Bata dey. merey pass 4 tubler batteries he jo k 185AHM ki he to me to me 2nd setting me Kiya figure rakkhu plz???
Sahi Connection par ek detail video banay hai ma nay us may series/parallel ma laganay ky baray ma , channel par dekh saktay hain ap, 2.5kw DB box kay naam say hai
Many new soler inverter liya he Usy wapda sy connect bhi nahi kia Issue ya arha he jasy hi battery us sy connect kerty hen to jo soler ki input he wha tester full current show kerny lagta he soler conect bhi nahi kia phir bhi Ac out put to sahi arha he Bus soler input py kio current arha he ya bta den.
A.O.A Bhai main nay inverter only solar charging per set kia hay to jub take sunlight ho ti hay wo battery full dikhata ta hay but jaisay he sun off ho ta hay wo battery around 60% dikhata hay jubkay battery use bhi nahi ho ti hay please guiide jazak Allah
Sir ap sy ak question ha k 2.5 inverter wapda say kitny wat aur imp leta ha mtlb rat k tim jb koi lod na chl ra ho. 1 hour ma wapda k kitny unit use hon gy Plzz
Assalam walekum bhaijaan hamen sirf yah samjha de ki Ham hamari inverter ke sath hamari metre ki light bhi jalti hai to Ham to charging per humne battery Nahin lagai hai to hamari metre ki light jal rahi hai sirf yah maloom karna hai ki hamara metre bhi chal raha hai iske sath
ups mood par rahka tha laken jab light gaye to fareg chal raha tha battry par plzz is ka kuch batan k kon c sating karan to frezar battry say on na hoo
Bhai SOL mode pr yeto h k 100amp ki 2 battery save rehti h bs ye 1 msla h k kuch na kuch ampere ya watt wapda sharing pr inverter lyra rehta h bhly load kam bhi ho hamara..jissy hamara bill zada ata h Iska koe solution btady?w8 kroga apky jawab ka ap buhat acha smjhaty h..❤
Assalam walaikum agr hum magrib k bad isse apne ghar ki light yani k.e istimal krte hen to wese hi apko ye costly par jaye ga q k iske apne watt hi 200 k kareeb he bhai please asif bhai is pr b video bana den rehnumaye ho jaye take sabki lazmi jwb di jiye ga
Jee bilkul theek kah rahe hain main bhi Yahi recommend Karunga ki aap Raat Ko inverter ko bypass Karke off kar de Taki 200w ki bachat kar sakian. Inshallah is per aur Wapas sharing per video Aane Wali Hai
Assalamualikum Bhai Bhai Mery is 2.5kw inverter Per 02 150mp Wali Battery install hain Phoenix ke Onka Backup Bhut Kam ha 02 Chaat Waly Fan Sirf 04 Ghanty Timeing Ha Battery B New hain
Mere pas jinko n type 585 watt 6 plats lage hen 2.5 veyron 2 pe jo din me agar dhop sai ho to 1500 watt 1600 watt tak jate hen new setup lgaya hai bhai btaen aesa q hai koi masla to nh hai ye plats ka jbke 585 watt ki 6 plats hen 3000 watt se upar bnte hen plz axhe se btadyn
Full dhup mein bhi 1600 watt de raha hai to yakinan Koi masala hai yah Kuchh points hai jo aap check kar sakte hain First Sare panel series Mein connect Karen Takay voltage zyada bane, iske elawa 6 panel 3000 watt Se zyada bante Hain Inko 5 panel Karke Dekhe series mein, rating Se zyada panel Lagane se bhi output kam ho jaati hai iskay baray Ma mianay inverter ki fault wali video hai kiya tha. Inverter All Faults: ruclips.net/video/GhOeuqpsjwU/видео.html
Bhai battray charging ka jo ap bta rahe ha us pe ma ap se itefaaq nhe krta jab inverter battray ko charge krta ha for example 10 ampre se to wo sab battries ko 10,10 ampare deta ha matlb agr 100 wali 4 battray lagi ha to hr battray ko 10 .10 ampare melengy total 40 ampare se charge hongy ap jo formula bta rhe ha us me battray kharab hu jati ha jaldi .
Bhai Apne 12 aur 13 Num ko ghalt define kia hai. Aur Apne bulk voltage aur floating voltage bhi ziada rakhe huwe hen. Eske elawa equalization fast charge nhi krti bal'ke over charge krti hai ta'ke sulfation khatam ki ja sake. Equalization hamesha battery full hone ke baad On krni chahiey.
As Salam o aleykum Sir new battery hain per Karachi may baadal honey ki wajha se batteries sahi charge nhi horhi hain or gravity down hojati hay or humarey ha load shedding nhi hay koi setting btaey k back up acha miley.
Walekum Assalam YES, clouds ki wajah se PV Puri Nahin arahi hoti Jis per ghar ka load hi chal Jaaye to bahut hai charging to bilkul Bhi Nahin Hoti. Agar aapki light Nahin jaati to Koi masala Nahin Hai Lekin Agar jaati hai to aap SNU per kar den charging ki setting usse aapka solar aur utility se sath mein charge Hoga lekin usse aapka Bil hi Badhana Hai, To Rahane den Kyunki aapko loadshedding ki wajah se backup ki zarurat Nahin.
Assalamualikum Bhai mere pas veyron 2 2.5 premium model he. Mene battery connect nae ki. Inverter 1.5amp grid se hr waqt leta he chahe solar a he raha ho. Ye approx 350watts bnte he. Iska koi solution btaen
Yes, yah masala Hai ismein Jab wapda available Hoti Hai To yeh Apna self consumption wapda per Dal Deta Hai Chahe solar Ho Ya Na Ho, HAL sirf yahi hai ki aap wapda ka breaker band kar den lekin uske liye second source Mein batteries Lagani padegi warna inverter Thode Se Bhi clouds ki wajah se trip kar Jaega aur Low PV ki warning ajayegi Kyunki second source Nahin Hogi.
Setting 2 samaj nhi ai sahi se mere pass Veyron II 6KW ka inverter he or Exide ki battery 12V - 120 AH ki total 4 batteries he jo k series me connected he. Total 48V and 120AH hogae. Then Charging Current would be 12A hoge na ?? q k 120 ka 10% is 12 A, please guide me. Thank you
Asif bhai bulk charging 29.3 ya 6 par foran return nahi hute he janab gradually down hute he float tak aur ahat grid se charge karge bulk tu aur time lete he ise batttry backup better bhuta he some time tura risk but its save not over charge mene khud practicle kia he
Bahi apko confusion hy battery 100amp ki hi rahy gi cz charging b to 29 volt aur 10amp se gi dono batteries 14 volt se nahi hgi agr 14 volt se batteries charge hti phir 20amp current hum rakh skthy thy ye series me amp same reh gae volt ziada hgae
میرا 6.2 solar hyd inverAnern ہے. UPS والے آپشن AC کا icon بلینک کرنا شروع کرتا ہے اور input بھی نہیں دیتا ۔ جبکہ apl والے آپشن پر beep کرتا ہے ۔ واپڈا کے وولٹیج 170 وولٹ ہوتے ہیں ۔
سر میرے پاس invverex کا aerox 3.2 kw ماڈل ہے اور اس right side پر 3 بٹن ہیں مجھے اس کی سیٹنگ نہیں آتی۔ براہ کرم انتہائ آسان سیٹنگ بھیج دیں۔انتہائ ممنون ہوں گا۔میرے پاس 210 کی 2 ایسڈ والی بیٹریاں ہیں۔شکریہ
Brother mera 6kw ka invertor hai or battery charge Only Solar select hai 4 batteries lagi hui hai 70AH ki.. Sham ko batteries fully charged hoti hain or pori raat use nhi hoti, light bhi nhi jaati but raat me battery 1ampere waqtan fawaqtan drain hoti rehti hai or subha tk battery 50 ya 60% tk reh jati hai.. Ye kia masla hai please ye bhi bata dein...
@@TechnicalAsif747 Sir iska solution kia hai please ye bhi guide kr dein. Ap sab behad achy se guide krty Hain I really like your videos. Allah apko kamyaab kre or dher sari khushiyaa ata farmae. Ameen
السلام علیکم Dear Asif sb 2nd setting k barey me Bata dey. merey pass 4 tubler batteries he jo k 185AH ki he to me to me 2nd setting me Kiya figure rakkhu plz???
Masha ALLAH Buhat details say app nay video banai, well done 👍👍
ماشاءاللہ, بہت ہی تفصیل اور اچھے طریقے سے سمجھایا
شکریہ
Well done! Your efforts are impressive and appreciated.
weldone very well explained.
اللہ جزاے خیر دے بہت اچھی طرح سمجھایا ہے آپ کے قیمتی وقت کا شکریہ
جزاک اللہ
For Example 12v100Amp two batteries are used... If connected in series then 24v100Amp , setting 02 is 100/10=10Amp
if connected in parallel then 12v200Amp, setting 02 is 200/10=20Amp
زبردست بھائ جواب نہیں آپ کی تحقیق کا,
بھائ آپ لیتیھم بیٹری پر بھی مکمل معلومات کی ویڈیو بنائیں, اور یہ بھی بتائیں اگر اتنی مہنگی بیٹری لگائ جائے تو اس کا کوئ فائدہ بھی ہے ,
shukriya sir
yes, sasti or reliable lithium battery kay baray ma bhi jald share karonga.
Thanks brother, this video was super helpful.
Salam boss aap ne bohat ache tareke se inverter ki setting samjhai hain bohat bohat shukariya aap ka.
Sir mere inverter utility se battery charge nhi kar rha please mjhe guide kare.
Excellent
Good Shehzady ❤️
اللّٰه آپ کو خوش رکھے میرے پاس 70 ایمپئیر کی اے جی ایس کی دو بیٹریاں لگی ہیں
Well Explained🎉
Bhai bohtt ache se samjha ya apne
Mashallah bohht alaa
Bhai mere yahi inverter inverex veron 2
Uss me raat ko reverse ki light on ho jati he meter pr
Kindly ye masla kese hal kro
بہت ہی خاص اور بہترین
Zabardast Asif Bhai ❤
Shukriya sir
@TechnicalAsif747 isolar app ka ni btaya ap ny us py video bnaein kinndky
Very good information
Asif Bhai good video I have two tall tubular batteries TX 2500 and 4KVA inverter. I have set the battery charging at 20 ampere....this is right setting please reply
Masha Allah
Very nice
Thank you
Assalam o alaikum, I hope you are doing well.
First, thank you for creating such a detailed video. Second, I have a question regarding the settings you mentioned. When I keep my electric breaker on, even after the solar is on, the electricity lines going to the home remain active. When I turn off the breaker, those lines get cut off.
Third, for a 585-watt panel, what is the minimum and maximum wattage and amperage it provides, and how much does it generate during rainy weather? Or normal weather
Mere pas old model infinisolar inverter solar V lll 3KVA ke sath 125A 15 plates ki 4 batteries jo ke 48V installed hai 585watt ke 8 solar install hai please ek video inverter settings ki bana de
Masha Allah ur vidios is awesome
Bhi mujy ap se ye pochna h m konci setting kro k n sirf solar hi use kro or sham ko wapda use ho bs or battery tb use ho jb loadsheding ho
Yah video is hi bare mein hai,
is setting ko karne ke bad aapki battery sirf aur sirf load shedding Mein Hi use Hogi
@@TechnicalAsif747 m ne apki sari vidio dekh li h or oso setting ki ab meri battery wapda se charge ni hoti h bs 1 ab 1 sawal ap se pochna h jb m koi heavy load on krta ho to inverter battery use kr k heavy laod on kr deta h wapda per shift ni krta load ye setting kesy ho m ne bypass b enables kiya h
Brother yr phele backup nai de Rahi battery new ha hafta hi hua ha batterys liya hu
1 battery hawk taltubler 180ah mei battery setting half kerni pade gi?
Bhi m ne ups ki wiring krni h to wo kesy inverter k sath lagani h ups ki wire inverter ki kis jaga per lagani h kindli bta dena bhi
Sir phli Video ma apne sbu ki seting select ki thi...kindly btaen gay..Sol karna hai yeah sbu
Sir .ager string parallel main hoin gay to 2 plat 585se kitnay ampere aur kitnay volt Milani. Gain .
Assalamualaikum bhai mara 1.5 ton Dc inverter Ac hai orient k mary installer bol rahy hai wo nh chal skta is par
السلام علیکم
Dear Asif sb 2nd setting k barey me Bata dey. merey pass 4 tubler batteries he jo k 185AHM ki he to me to me 2nd setting me Kiya figure rakkhu plz???
Bhai SBU mood pe b battary use nhe hoti agr ap 12 and 13 number ki setting sahi kr do
Kindly let me know the setting of dual load setting (smart load and heavy load)
Bhai meray pass 230 AH ki ( TX 2500) 2 batteries hain es may say 1 battery solar say charge ho Rahi hai, please need solution.
Bhai m me inverter inverex 2.5 kw lagaya hai 5 jinko sollar plates (580 watt) lagai hai panels ke connection pearl main kaye hai kia sahi hai
Sahi Connection par ek detail video banay hai ma nay us may series/parallel ma laganay ky baray ma , channel par dekh saktay hain ap, 2.5kw DB box kay naam say hai
Which inverter is best Inverex veyron 11 4kw or knox crypton 4k ?
12 number setting ko 24 volt per krsaktay hay ? aur 2 batteries hay 135amp ki to 20A per charge karay ya 30 ?
Karsakte he
AoA
Meray pass inverex veyron II 1.2 hain sol first pay hain liken per wapda by pass line show hoti hain
Many new soler inverter liya he
Usy wapda sy connect bhi nahi kia
Issue ya arha he jasy hi battery us sy connect kerty hen to jo soler ki input he wha tester full current show kerny lagta he soler conect bhi nahi kia phir bhi
Ac out put to sahi arha he
Bus soler input py kio current arha he ya bta den.
بھائ مینے اپنے 2.5kw varion2 پر longi 585 کی 5 پلیٹیں لگائ ہیں, کیا مزید 1 اور پلیٹ کا اضافہ کرسکتا ہوں؟
Yes
Inverter ka roz khudse bnd hojana kya setting me msla he
Same yehi masla aa raha battery khatum ho jati hai jaldi. Lekin inverter ziewnic ka hai hamara. Kindly us ki bhi video bna dein.
A.O.A Bhai main nay inverter only solar charging per set kia hay to jub take sunlight ho ti hay wo battery full dikhata ta hay but jaisay he sun off ho ta hay wo battery around 60% dikhata hay jubkay battery use bhi nahi ho ti hay please guiide jazak Allah
Ye bhi Bata dey k is video me or is se pahley jo video me amney settings bataee he Kiya Ye tubler batteries ki he????
Jee tubular ki hai
Boss ye 13 number ki Setting battery full ki hain kia please batye app
Sir ap sy ak question ha k 2.5 inverter wapda say kitny wat aur imp leta ha mtlb rat k tim jb koi lod na chl ra ho. 1 hour ma wapda k kitny unit use hon gy Plzz
Takreeban 100w say 200w leta hai bina kisi load kay bhi
pv 6000 novatec ki mukamal sitting ki video bna dene
Inshallah
Sir inverex veyron 6kw ke mukamal sitting ke video bnaye plzz
W number setting pehnix tx 1800 k leye kitna rakna chaheye
2 number
Sar hamray light nahi jati
Baatary ka bacap kasa baray
Suba hota he sollar active ho jay
Assalam walekum bhaijaan hamen sirf yah samjha de ki Ham hamari inverter ke sath hamari metre ki light bhi jalti hai to Ham to charging per humne battery Nahin lagai hai to hamari metre ki light jal rahi hai sirf yah maloom karna hai ki hamara metre bhi chal raha hai iske sath
12 Volt Inverter 1.2 Kay bary main video Bana dain
Please
Done Inshallah
ups mood par rahka tha laken jab light gaye to fareg chal raha tha battry par plzz is ka kuch batan k kon c sating karan to frezar battry say on na hoo
Video coming soon
Bhai es main wifi ki settings bhi samjha do please
jee channel par inverter wifi setup video moojud hai ap wo dekh saktay hain
Apkaha sy hy mojhko seeing karwanihy.new new betray kharab hojati hy please help
Bhai SOL mode pr yeto h k 100amp ki 2 battery save rehti h bs ye 1 msla h k kuch na kuch ampere ya watt wapda sharing pr inverter lyra rehta h bhly load kam bhi ho hamara..jissy hamara bill zada ata h
Iska koe solution btady?w8 kroga apky jawab ka ap buhat acha smjhaty h..❤
Shukriya sir
Jee yah wapda say power lagta rhata hai is kay baray ma video par kaam jari hai
@@TechnicalAsif747 is video ka intzar rahe ga
@@TechnicalAsif747 میں منتظر ہوں جواب کا....
@@TechnicalAsif747thankx sir w8ing
Asif bhai CSO per hone ke bawjood battery wapda se charge nai hoti rat ke wakat
Solar maujud hoga to wapda se nahin Hogi cso per bhi
Solar Jab khatm hoga tab charging Hogi wapda se.
CSO only works in standby mode, matlab yay ky aap inverter ka switch off kerain tu phir ya utility say charge hoga
Assalamu alaikum sir with out battery kasa chala
1.2 KW veryron 2 premium me yahi settings k options hen ......?
Setting sequence same hai,
values different hongi Kyunki wo 12volt system hai aur yah 24volts
12 volts ki Kia values hon gi
Assalam walaikum agr hum magrib k bad isse apne ghar ki light yani k.e istimal krte hen to wese hi apko ye costly par jaye ga q k iske apne watt hi 200 k kareeb he bhai please asif bhai is pr b video bana den rehnumaye ho jaye take sabki lazmi jwb di jiye ga
Jee bilkul theek kah rahe hain main bhi Yahi recommend Karunga ki aap Raat Ko inverter ko bypass Karke off kar de Taki 200w ki bachat kar sakian.
Inshallah is per aur Wapas sharing per video Aane Wali Hai
@@TechnicalAsif747 sir 1.2 veyrone me hum din me solar or wapda se sharing kese kr sakte hen is pr b video banaye
Sir invrix 1.2 or TX 1800 or185 ampere battery key setting bata de
Asif sab mujy sating chak karwane ha 6 kw
Assalamualikum Bhai
Bhai Mery is 2.5kw inverter Per 02 150mp Wali Battery install hain Phoenix ke Onka Backup Bhut Kam ha 02 Chaat Waly Fan Sirf 04 Ghanty Timeing Ha Battery B New hain
Mere pas jinko n type 585 watt 6 plats lage hen 2.5 veyron 2 pe jo din me agar dhop sai ho to 1500 watt 1600 watt tak jate hen new setup lgaya hai bhai btaen aesa q hai koi masla to nh hai ye plats ka jbke 585 watt ki 6 plats hen 3000 watt se upar bnte hen plz axhe se btadyn
Iska reason pata chalay to share karna plz
Full dhup mein bhi 1600 watt de raha hai to yakinan Koi masala hai yah Kuchh points hai jo aap check kar sakte hain
First Sare panel series Mein connect Karen Takay voltage zyada bane,
iske elawa 6 panel 3000 watt Se zyada bante Hain Inko 5 panel Karke Dekhe series mein,
rating Se zyada panel Lagane se bhi output kam ho jaati hai iskay baray Ma mianay inverter ki fault wali video hai kiya tha.
Inverter All Faults: ruclips.net/video/GhOeuqpsjwU/видео.html
Bhai battray charging ka jo ap bta rahe ha us pe ma ap se itefaaq nhe krta jab inverter battray ko charge krta ha for example 10 ampre se to wo sab battries ko 10,10 ampare deta ha matlb agr 100 wali 4 battray lagi ha to hr battray ko 10 .10 ampare melengy total 40 ampare se charge hongy ap jo formula bta rhe ha us me battray kharab hu jati ha jaldi .
Bhai Apne 12 aur 13 Num ko ghalt define kia hai.
Aur Apne bulk voltage aur floating voltage bhi ziada rakhe huwe hen.
Eske elawa equalization fast charge nhi krti bal'ke over charge krti hai ta'ke sulfation khatam ki ja sake.
Equalization hamesha battery full hone ke baad On krni chahiey.
As Salam o aleykum
Sir new battery hain per Karachi may baadal honey ki wajha se batteries sahi charge nhi horhi hain or gravity down hojati hay or humarey ha load shedding nhi hay koi setting btaey k back up acha miley.
Walekum Assalam
YES, clouds ki wajah se PV Puri Nahin arahi hoti Jis per ghar ka load hi chal Jaaye to bahut hai charging to bilkul Bhi Nahin Hoti.
Agar aapki light Nahin jaati to Koi masala Nahin Hai Lekin Agar jaati hai to aap SNU per kar den charging ki setting usse aapka solar aur utility se sath mein charge Hoga lekin usse aapka Bil hi Badhana Hai,
To Rahane den Kyunki aapko loadshedding ki wajah se backup ki zarurat Nahin.
@@TechnicalAsif747 sir how to maintain battery gravity?
Isme grid disabled krne ka ni btaya
M kb grid m enter krta disable k liye tu wo agye counting show krwata h 00 esy
Bhai mere pas 330 wat k 4 panel hen inverter daily din men 3 bje bnd hojata he us k bare me bataen kuch
330w ka panel bohat kaam hai 3 bje ki dooph ma bhi kuch nhi banayga
Assalamualikum
Bhai mere pas veyron 2 2.5 premium model he. Mene battery connect nae ki. Inverter 1.5amp grid se hr waqt leta he chahe solar a he raha ho. Ye approx 350watts bnte he. Iska koi solution btaen
Yes, yah masala Hai ismein Jab wapda available Hoti Hai To yeh Apna self consumption wapda per Dal Deta Hai Chahe solar Ho Ya Na Ho,
HAL sirf yahi hai ki aap wapda ka breaker band kar den lekin uske liye second source Mein batteries Lagani padegi warna inverter Thode Se Bhi clouds ki wajah se trip kar Jaega aur Low PV ki warning ajayegi Kyunki second source Nahin Hogi.
@@TechnicalAsif747 ap ny expo m kaha tha isolar app py video bnaein gay..video ni ai abi tk apki asif bahi?
What's the price of this invertor?
Setting 2 samaj nhi ai sahi se
mere pass Veyron II 6KW ka inverter he
or Exide ki battery 12V - 120 AH ki total 4 batteries he jo k series me connected he.
Total 48V and 120AH hogae.
Then Charging Current would be 12A hoge na ?? q k 120 ka 10% is 12 A, please guide me.
Thank you
Make them 10A as it is close to 12A
Bhai plzz help me
Meri lithium battery 1 din sahi backup deti he 1 din nh deti
Frunas ka revars sitting
Bhai 13 No setting me, agr mery pass 2 12v ki battery hon gi TU UN ko kitny volt tak charge krna ho ga
Minimum 23 as per load
Asif bhai bulk charging 29.3 ya 6 par foran return nahi hute he janab gradually down hute he float tak aur ahat grid se charge karge bulk tu aur time lete he ise batttry backup better bhuta he some time tura risk but its save not over charge mene khud practicle kia he
Yes try to keep it lower as possible
Bahi apko confusion hy battery 100amp ki hi rahy gi cz charging b to 29 volt aur 10amp se gi dono batteries 14 volt se nahi hgi agr 14 volt se batteries charge hti phir 20amp current hum rakh skthy thy ye series me amp same reh gae volt ziada hgae
Osaka 1800 Lage ha 160 Am+160Am #320 ban gae Hume Kitne par set kane
If you use good with damage battery then good must be over charged and ultimatly damage too...
True
Sir crown ki sating
Isolar app ka ni btaya ap ny ??
will upload that as soon as possible
Thanku @@TechnicalAsif747
آصف ایک سوال ہے
Fornus pv 3200 h, solar pure din sahe chalta h, rat m light Jane k bad battery pr 30 minutes k fluctuate krta rehta h
میرا 6.2 solar hyd inverAnern ہے. UPS والے آپشن AC کا icon بلینک کرنا شروع کرتا ہے اور input بھی نہیں دیتا ۔ جبکہ apl والے آپشن پر beep کرتا ہے ۔ واپڈا کے وولٹیج 170 وولٹ ہوتے ہیں ۔
سر میرے پاس invverex کا aerox 3.2 kw ماڈل ہے اور اس right side پر 3 بٹن ہیں مجھے اس کی سیٹنگ نہیں آتی۔ براہ کرم انتہائ آسان سیٹنگ بھیج دیں۔انتہائ ممنون ہوں گا۔میرے پاس 210 کی 2 ایسڈ والی بیٹریاں ہیں۔شکریہ
Brother mera 6kw ka invertor hai or battery charge Only Solar select hai 4 batteries lagi hui hai 70AH ki.. Sham ko batteries fully charged hoti hain or pori raat use nhi hoti, light bhi nhi jaati but raat me battery 1ampere waqtan fawaqtan drain hoti rehti hai or subha tk battery 50 ya 60% tk reh jati hai..
Ye kia masla hai please ye bhi bata dein...
Inverter apna load data hai battery par 150w 200w
@@TechnicalAsif747 Sir iska solution kia hai please ye bhi guide kr dein. Ap sab behad achy se guide krty Hain I really like your videos. Allah apko kamyaab kre or dher sari khushiyaa ata farmae. Ameen
@@TechnicalAsif747
Battery setting of my invertor is as follow:
Battery Settings Default:
-Battery Type: FLD
-Battery Cutt off Voltage: 40.8
-Battery Bulk Voltage: 56.4
-Battery Float Voltage: 54.0
-Max Charging Current: 30
-Max AC Charging Current: 10
-Charger Source Priority: Solar only
-Back to Grid Voltage: 46
-Back to Discharge Voltage: 54
Assalam o alaikum
Mene 2 num setting SBU
Aur 16 num setting CSO pr kr rakhi hy lekin display mein phir Wapda input output bata raha hy,
Yes wo show karta rhata hai bypass but 100w 200w let hai sirf ,
Yahi inverter apna load data hai sirf
Never use two batteries of different Amphere...
Yes
اگر آپ ممکن ہو تو سسٹم چیک کرسکتے ہیں میرا؟ میں خداداد کالونی کراچی نزد نمائش چورنگی ہوں
جواب دیجیے گا ضرور میں نے بمشکل سسٹم لگایا ہے چھت بھی میری ٹین کی ہے جس پر سسٹم لگایا ہے آپ اگر سسٹم دیکھ لیں کہ کیا اشو ہے
13 number ki setting aapny ghalat btai hai
Mtlb explain
Mene check kiya he ye takreeban 1 Amper leta he ap experiment kr k bata den video me take sab bachat kr saken
Yes iss ki selfconsumption 1amp yahi 200w hai takreeban.
دو میں سے ایک بیٹری خراب ہوگئی ہے مجھے لگتا ہے کیونکہ ایک بیٹری انڈیکیشن میجک آئی بلو ہوتی ہے دوسری نہیں ہوتی
Bai ye he setting ke hai magar 500w pe just 2 gantey backup de rahi hai 2 bettries tx1800
Load kitna hai apka
@@TechnicalAsif747bata to raha 500 watt
AoA, plz provide me your no to contact, I have little different situation so I can get your help
السلام علیکم
Dear Asif sb 2nd setting k barey me Bata dey. merey pass 4 tubler batteries he jo k 185AH ki he to me to me 2nd setting me Kiya figure rakkhu plz???