It was better if you show what you change the function on the meter to? Thank you
What is the maximum ze we should not exceed
Depending on the earthing arrangement then for TN-C-S Ze must not exceed 0.35 ohms, for TN-S Ze must not exceed 0.8 ohms. For TT it can be as much as 200 ohms.
Can two separate electric meters use one protective earth
Further explanation on how parallel paths lower impedance and raises the PFC would be great thanks
Hi Jayden thanks for the comments we discuss parallel paths during the associated classroom training courses
It was better if you show what you change the function on the meter to? Thank you
What is the maximum ze we should not exceed
Depending on the earthing arrangement then for TN-C-S Ze must not exceed 0.35 ohms, for TN-S Ze must not exceed 0.8 ohms. For TT it can be as much as 200 ohms.
Can two separate electric meters use one protective earth
Further explanation on how parallel paths lower impedance and raises the PFC would be great thanks
Hi Jayden thanks for the comments we discuss parallel paths during the associated classroom training courses