    @MaxEpsom 3 года назад +1

    What is the maximum ze we should not exceed

    • @proactivetechnicaltraining4431
      @proactivetechnicaltraining4431 3 года назад

      Depending on the earthing arrangement then for TN-C-S Ze must not exceed 0.35 ohms, for TN-S Ze must not exceed 0.8 ohms. For TT it can be as much as 200 ohms.

  • @mustaphaabdulai6763
    @mustaphaabdulai6763 4 года назад

    Can two separate electric meters use one protective earth

  • @jaydenplaysguitar3896
    @jaydenplaysguitar3896 3 года назад

    Further explanation on how parallel paths lower impedance and raises the PFC would be great thanks

    • @proactivetechnicaltraining4431
      @proactivetechnicaltraining4431 3 года назад

      Hi Jayden thanks for the comments we discuss parallel paths during the associated classroom training courses