Maximum Demand and Diversity Calculation Explained - BS 7671 On-Site Guide Appendix A

Поделиться
HTML-код
  • Опубликовано: 12 июн 2024
  • In this video we go through step by step the calculation for working out maximum demand and diversity for a single phase installation. For this version of the calculation we take 100% of the largest circuit fuse rating and 40% of the sun of all the other fuse ratings and add these numbers together to find the maximum demand for the installation.
    == 🕐 Time Stamps - Cut to the action 🕕 ==
    00:00 - Maximum demand and diversity
    00:18 - Easy calculation on-site
    00:38 - Old circuits
    00:47 - New heaters
    01:10 - Don't want to blow the 100 amps fuse
    01:33 - 100% of the largest circuit
    01:42 - 40% of the remainder
    02:04 - Circuit loads without diversity
    02:33 - Applying diversity to the old circuits
    03:23 - Applying diversity to the new circuits
    04:08 - Table in the On-Site Guide
    04:21 - Comparing calculations
    Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.
    You can follow me day by day on Facebook, Instagram, Twitter and TikTok lookout for "GSH Electrical.
    ▶️ FACEBOOK / gshelectrical
    ▶️ INSTAGRAM / brihzmraygdtmjmdb9lunq...
    ▶️ TWITTER / gsh_electrical
    ▶️ TikTok vm.tiktok.com/ZMRBLFdhe/
    #GSHElectrical #electricaltrainingvideos

Комментарии • 71

  • @protectiongeek
    @protectiongeek 2 года назад +26

    As a former DNO engineer, who spent about two years in distribution network design, most of it on LV networks, I never fail to be surprised at how high the After Diversity Maximum Demand (ADMD) for a domestic property turns out to be using the BS7671 criteria. 88A, single-phase assuming nominal supply voltage of 230V yields the ADMD as 20.2kW - this is well into three-phase supply territory!!! 20kW for a one-bed house is just nonsense. Don't misunderstand me, GSH Electrical appear to have correctly applied the criteria set out in the regs, but from a DNO perspective if the same criteria were used, the LV networks would be massively over-specified. And, yes, I know that a further degree of diversity applies for multiple properties, although they do tend to demonstrate remarkably similar load curves.
    As a matter of interest, I downloaded the latest version of my local DNOs spec' detailing ADMD calculations and - making some assumptions about the number/rating of the space and water heating appliances - the ADMD for this property falls out at 8.2kW (35.6A). I still think that's probably a bit high tbh but it's a lot closer to reality than BS7571 would have us accept.

    • @GSHElectrical
      @GSHElectrical  2 года назад +5

      Thanks for taking the time to give such a detailed comment it is very much appreciated. Gaz 👍🏻

    • @mathman0101
      @mathman0101 2 года назад +2

      @@GSHElectrical I agree Gaz in fact if you do a continuous actual load assessment and I have done that on my property at least here in the US it rarely gets over a third actual usage of the total cut-out size. And we have larger motors and load here in the US in residential settings that run large AC and forced air heating units.

    • @Adam-er2yi
      @Adam-er2yi Год назад +1

      Craig, I am a new electrical design engineer and tend to do a lot of load calculations. Could you walk me through or tell me where I can find the DNO ADMD calculations please? I can give you my email if it’s easier

  • @pauledwards5164
    @pauledwards5164 2 года назад +11

    At last, easily explained and also appreciated comments from former DNO engineer

    • @GSHElectrical
      @GSHElectrical  2 года назад +2

      Massive thanks for watching and commenting 👍🏻

  • @adrianupnorth
    @adrianupnorth 2 года назад +5

    I just love GSH training. A newbie learning for the first time to an old timer on CPD or just refreshing the memory you explain things in plain English. Keep up the good work 👍

    • @GSHElectrical
      @GSHElectrical  2 года назад +1

      Massive thanks for the kind words and watching 👍🏻

  • @terryleebarrett1080
    @terryleebarrett1080 8 месяцев назад

    You just explained this better in 5 min than my teacher in 30 minutes thanks for keeping it lemon🍋👈 appreciate it geez

  • @scarcxy
    @scarcxy Год назад +1

    Thank you so very much for taking time to explain to me how to calculate maximum demand and diversity. Great video and thumbs up.

    • @GSHElectrical
      @GSHElectrical  Год назад

      Thanks for watching and commenting 👍🏻

  • @Mike_5
    @Mike_5 2 года назад +6

    Very important subject explained expertly as no-one wants their Meter Tails glowing red hot

  • @POLEinTheUK
    @POLEinTheUK Год назад +2

    Great video, a very clear and concise explanation. Thank you

  • @James_scott86
    @James_scott86 3 месяца назад +1

    Fantastic video, simple and informal. Thanks guys!

  • @garythespark6295
    @garythespark6295 Год назад +2

    Nice easy to follow explanation. Ideal method for a quick tally up to put on an EIC. Cheers!

  • @BobBobOnYouTube
    @BobBobOnYouTube 2 года назад +3

    Excellent video, Marcus. Easy to understand. Thanks a lot 👍

  • @AndyK.1
    @AndyK.1 2 года назад +4

    Arh. A sensible and easy way of doing it.

  • @therealdojj
    @therealdojj 2 года назад +4

    that's a great help because i've just checked my numbers and the answer is 104.8!
    although that includes the 40a for the garage which i think is a little excessive so i'll drop that to a 32 and drop the 32's for the sockets down to 16 as that should make things within specs as it brings it down to 91.2 on our 100amp main
    ok, so that just means more stuff to do to fix this house of electrical horrors

  • @daverose4774
    @daverose4774 Год назад

    Another brilliant video from the best sparkies on you tube.
    Thanks so much for helping me get qualified.

  • @danielteyehuago1633
    @danielteyehuago1633 2 года назад +4

    Thanks for sharing it with us

  • @kingofthetrowel1725
    @kingofthetrowel1725 2 года назад +2

    Nice one Marcus 🙌🏻 well explained love it!!👌👌

  • @richardhayden4499
    @richardhayden4499 Год назад +1

    Good video, nice and clear.

  • @bryancarruthers1121
    @bryancarruthers1121 2 года назад +1

    Great video, cheers

  • @peleuwase7070
    @peleuwase7070 2 года назад +4

    Nice video, just to clarify, I have noticed that you have applied 40% to all the remaining circuits, according to the OSG, no diversity allowed on shower circuit?

  • @pah9844
    @pah9844 11 месяцев назад +1

    Thanks

    • @GSHElectrical
      @GSHElectrical  11 месяцев назад

      That’s very kind. Massive thanks Gaz

  • @avfczoff
    @avfczoff 2 года назад +1

    As always a great video and appreciated. Just a query though, diversity seems to have been applied to the two additional storage heaters? I thought no diversity allowed for storage heaters? There is a shower in the circuit as well as other panel heaters. Diversity seems to have been applied to these as well?
    Any help welcomed. Thanks guys

  • @johna8921
    @johna8921 Год назад

    Great video
    Any advice would be welcome I'm thinking of connecting an induction hob and oven to the same cooker outlet. Hob is 7.5 kw and. Oven is 3.5 kw so around 11kw. I'm using 6mm cable over around 6 meters to a 32 breaker no ring just direct.
    Thanks

  • @Edgariux111
    @Edgariux111 Год назад

    Great video . But what about working out three phase ? I imagine it would be the same process but devide the answer by three ?

  • @digitraxuk
    @digitraxuk 2 месяца назад

    Is this the same approach if you have a submain in an annex if it’s run from an mcb from the main board; or if it’s fed from a Henley block, would you perform this same calculation for each submain consumer unit and add them together?

  • @samrigden8013
    @samrigden8013 2 года назад +1

    Sorry, just a query.
    Isn’t current demand the current drawn by the connected equipment not the size of the protective device?
    Using the protective device size gives a high max demand.
    A 2kw heater would normally be installed on a 16 A radial but will only draw approx 8 A and is usually protected by a 13A fused spur. So you would be doubling the expected load by using the PD.

  • @myselfmusicworld5284
    @myselfmusicworld5284 10 месяцев назад

    After calculating the Final circuit diversity, can we install a circuit breaker with a lower power to the consumer unit? e.g. 40A CB change to 32A CB after diversity calculation.

  • @jasonbowe9767
    @jasonbowe9767 2 года назад

    What would be the scenario if the calculations worked out to be over the 100A main fuse (example 117A ) ?

  • @Adywebb123
    @Adywebb123 Год назад +1

    So how do you convert that figure to kva. What’s the recommendation solution if you go above the actual main fuse size. Thanks

  • @alanmarriott9216
    @alanmarriott9216 2 года назад +2

    Great video. What about for installations in schools or big office etc please?

    • @GSHElectrical
      @GSHElectrical  2 года назад +1

      We will produce more content on this in the future 👍🏻

  • @PhilipHudnott
    @PhilipHudnott Год назад

    I have a couple of queries for a board change I will be doing soon.
    The new board has an spd supplied via a 40a mcb.
    Am I correct in thinking that I can ignore that mcb for the calculation? My reasoning being that it is not drawing a load, it is just there to protect the spd.
    I have a second 40a rcbo which feeds a garage cu with a 16a and 6a mcb’s in it would you count that as 40a or 22a for the calculation?

  • @danielteyehuago1633
    @danielteyehuago1633 Год назад

    Please i want to ask you this question; what's the right order in which you should arrange your circuit breaker in your consumer unit. should it be from the lowest breaker to the highest or highest breaker to the lowest and why... Thanks

  • @simonupton-millard
    @simonupton-millard 2 года назад +4

    I am not an professional just started watching when my house was been rewired to make sure I knew enough to know if it was been done according to code and enjoyed the videos, one thing I was wondering is how do you know its a 100a fuse in there, My cutout said it was 100a but when the DNO removed it to allow the rewire to take place it was only an 80a fuse installed in the holder (had a complete rewire as house as my wiring was 2 core rubber stuff from the 50s with only 2 circuits for the whole 4 bedroom house)

    • @creativejamieplays7185
      @creativejamieplays7185 2 года назад

      You dont know. Unless you take the cover off (which should only be done by the DNO really) there could be a metal bolt in there for all you know.

    • @simonupton-millard
      @simonupton-millard 2 года назад

      @@creativejamieplays7185 so in the video example you could easly be drawing more A than an 80a fuse is rated for but you wouldn't know as you think its a 100a fuse, isnt that going to make the fuse blow? Or worse

    • @mra813
      @mra813 2 года назад

      in reality the max demand is unlikely to be anywhere near 88A. Sometimes I think the guidance has not kept up with some of energy savings now available e.g. for a 3-bed house, instead of using a 1000W for lighting it is now likely to be closer to 100W.
      The calculation is a very basic albeit quick for onsite use. It might give you idea if you need to do a more detailed design. In any event one of the regulations is to determine the supply characteristics. The rating of the over-current protective device is just one characteristics. The info should be provided by the distributors, in reality this is harder than you think. In your case when the DNO removed the fuse you/your electrician were able to determine rating of the over-current protective device.

  • @davidcase4041
    @davidcase4041 7 месяцев назад

    Just reading Craig’s comment, (1 year ago!) and I would agree that the 20+ kW seems excessive. The wording on the appendix A guidelines mentions maximum current demand, but the calculations shown are using the breaking ratings. If we know the attached loads, or at least their rating, I.e. storage heater, 3.5KW, oven 3.3kW etc. could these figures be used to calculate circuit maximum demand point loadS? The ring final circuit, I understand, we should consider worst case, and therefore likely to be the highest figure, but if we were to take the 40% of actual max demand loads, the overall figure is a more realistic load for a dwelling. Given that most “boiler” plate ratings for appliances are in excess of actual loads, there is already some float from the start.

  • @ef7480
    @ef7480 8 месяцев назад

    So a cooker circuit would have diversity applied before applying whole diversity?

  • @seandempsey7351
    @seandempsey7351 2 года назад +3

    Very well explained. But when you say 40% of the remaining, do you mean 40% off total remaining or 40% off each off the remaining? . Fantastic video Marcos as always 👍👍👍❤️

    • @crisislord00
      @crisislord00 2 года назад +3

      You will get the same value

    • @seandempsey7351
      @seandempsey7351 2 года назад

      @@crisislord00 still not clear.
      Sorry I have never been good at doing percentages. So I need it to be explained to me

    • @michaels8336
      @michaels8336 2 года назад +1

      @@seandempsey7351 add the full amounts together then 40% of that. It was explained in the video when they wrote it down, you can see they added and got the full amount and then 40% of that final value.

    • @seandempsey7351
      @seandempsey7351 2 года назад

      @@michaels8336 thank you if using the calculator on my phone am I right in thinking 40% would be 0.4

  • @wagabira
    @wagabira Год назад

    thanks for the video , one question! I have calculated the 40% out of 140 on your second calculation and it comes to 84 not 56 as you said. this means the amount taken has to be much more then 40% .
    am I missing something ?

    • @digitraxuk
      @digitraxuk 2 месяца назад

      Yes your maths is wrong. 0.4 x 140 = 56
      56+32 = 88Amps

  • @pah9844
    @pah9844 11 месяцев назад

    Hi. I worked out, thinking about fitting a new CU to be 85.6a, however my main DNO is an 80a. Would you apply any more diversity or put a 100a in.?
    Cheers

    • @GSHElectrical
      @GSHElectrical  11 месяцев назад

      The IET Guidance Notes has more details on MD 👍🏻

  • @M8d9R
    @M8d9R Год назад +1

    What about cooker circuits/lighting and all the other rows in Appendix A Table A2 in the OSG?
    Is this just for a quick calculation when doing an EICR?
    The 100% of largest then 40% of remaining circuits is shown in row 9 of that table, I absolutely accept that it's correct, but I don't understand when I'm supposed to apply the info shown in rows 1-8 of that table, based on this video.
    Great videos anyway thank you for making them.

  • @MD-um3nr
    @MD-um3nr Год назад

    Im confused i thought you had to do diffraction diversity factors for different circuits for example 66% of lighting circuits etc

    • @GSHElectrical
      @GSHElectrical  Год назад

      Standard circuit arrangement On-site Guide Appendix A table A2 indent 9. 100% of the largest circuit 40% of the remaining circuits as stated in the video 👍🏻. Thanks for commenting and watching

  • @gbelectricks
    @gbelectricks 2 года назад +1

    So after diversity applied you totalled 88amps. What if this had a 60amp cut out fuse, as the majority of older single phase installations have?
    The md calculation in osg is a bit… well … wrong really!! We’d be popping dno fuses all the time the md were anything near what most calculations total.
    God help the calculations (and dno fuses) when EV really takes off!!
    Great video chaps👍

    • @GSHElectrical
      @GSHElectrical  2 года назад +1

      Have a look at the pinned comment 👍🏻. There are other ways of carrying out the MD calculation but you have a great point about 60 amp cutout fuses and EV cars hence you have to tell the DSO (formally DNO) when you want to install an EV point.

  • @seandempsey7351
    @seandempsey7351 2 года назад +1

    eFixx you really need to sort your channel out your getting comments from idiots giving links to pornography websites . I don’t want to see this crap

    • @Martin-uf4ut
      @Martin-uf4ut 2 года назад +3

      report the comment like i have. it's all over youtube. we need to keep on reporting it.

    • @GSHElectrical
      @GSHElectrical  2 года назад +5

      This channel is NOT eFIXX 👀. All spam messages have been reported… THIS CHANNEL IS GSH ELECTRICAL 👍🏻

    • @simonupton-millard
      @simonupton-millard 2 года назад +2

      All channels get this now, youtube needs to stop the bots spamming

    • @seandempsey7351
      @seandempsey7351 2 года назад +1

      @@GSHElectrical yes it’s on your channel as well .

    • @SME_Ste
      @SME_Ste 2 года назад

      You mucky pup, stop clicking the links

  • @cestemshow
    @cestemshow 8 месяцев назад

    Correct.... But we all know it's still nonsense 😂