Common faults at visual & close EX inspection
HTML-код
- Опубликовано: 13 апр 2023
- يمكنك متابعتنا عبر منصة لينكد ان:
/ / mokhtarhosny
كما يسعدنى متابعتكم للموقع وشراء الكتب الالكترونية من خلال الموقع store.prin-ex.com/
Steps for visual inspection
1) Bring required document for inspection; Equipment layout, hazard area classification layout, conformity certificate of equipment to check special condition (X). etc.
2) Permit to work (if required).
3) Visual inspection by eye only.
4) Issue certificate of inspection (healthy) or with comments.
Visual Inspection Faults:
1) Wrong assembly cable gland.
2) Damage cable gland.
3) Missing screw for equip. cover
4) Missed blind plug
5) Protection concept of equip. is not matched with area classification i.e. EX nR lighting fixture installed at Zone 1.
Steps for close inspection
1) Bring required document for inspection; Equipment layout, hazard area classification layout, conformity certificate of equipment to check special condition (X). etc. Access to be used during inspection.
2) Permit to work (if required).
3) Close inspection; using tools to check tightness only (without opening equipment).
4) Issue certificate of inspection (healthy) or with comments.
Close Inspection Faults:
1) Loose screw for cover.
2) Loose equipment cover.
الله يسعدك اخوك من سلطنه عمان .. معلومات ممتازه ومفيده
جزاك الله خيرا اخي العزيز
الله ينور عليك ياهندسه
حبيبي يا م محمد .. ربنا يوفقك فى القادم
جزاكم الله خيرا 🙏. الله يحفظك ويبارك فيك
❤ عودا حميدا يا هندسة مختار الله ينور
جزاك الله خيرا يا م باسم
GOD BLESS YOU
aiwah tamam ya habib
الله ينور يا هندسه منتظرين من حضرتك المزيد ❤
بإذن الله تعالى
ربنا ينفع بيك ويوفقك 💪
عندي سوال لو سمحت، detail inspection اعملها في اي protection mode و هل في حالة "d" اقدر افتح the enveloppe و لا لا؟
الفحص التفصيلى يتم إجراؤه لكل انواع الحمايات وتبعا للمعايير standard ولابد فيه من عزل كهربي ثم نفتح المعدة envelope للنظر إلى ما بداخلها