Thank you so much sir i under stood can u please tell me fuel water sens warning 428 ECM004!hi what to do this warning how reset normal condition In our same 780kva dg fuel soilened coil is not working. We replaced now working normal
Water sensor warning is for coolant and there are 2 types of warning one is coolant level low and 2nd is coolant sensor hi....if it shows coolant sensor hi try to change coolant sensor harness...if still warning exists try to open sensor with 33 no. Spanner only to some extent when coolant starts leaking then tight it again then press reset button and if it still shows that then your coolant sensor is not working change the sensor. Shivam Mahajan Testing enginner incharge Sudhir power ltd
Hi, How to check charging alternator . When battery not charging. I replace the carbon brush but not charging, Winding all are ok. What is the fault . Please reply sir.
Engine speed position sensor not detected 1 ) may be position sensor faculty. 2 ) faulty engine harness. Please check 5 voltage dc in position sensor pin. Please check previous our video sender voltage
HMI 320 (1010 kva ) showing ESTABLISHING COMMUNICATION FIRMWARE VERSION with some number's... What to do??? Cummins guy saying calibration is no use because the light in base board is not blinking ..so... I need to change baseboard of 3300 which is 1.3 lakh ...
I am in sudhir power limited as testing engineer incharge....you are wrong bro...this pcc only comes on demand for greater then 750 kva.....this pcc belongs to only 250 to 380 kva gensets
Thnx sir apke video se kafi help mil jati h.. 🙏🏻
Bahut accha vidio
Paheli bar Aesa janretor par vidio dekha👍
Nice video sir bahut jankari mili
thank you soooo much sir..
1st time itna acha video mila hai.
keep it up 👍👍
Sir , 500 kva ka Genset controller ka display off nahi ho raha hai, please site pe settings bataiye, sir aap ke video bahot helpful bhai.🙏🙏🙏
Which cantroller??
Good massage sir
Very good information Sir.
Good work 🎉
Nice vdo thanks
Thanks🙏 sir necily prepomes and alternator
Hello SIR deep sea 8610 coumins GENSET PAR Kaise lgate hain
Engine Crank dose not starting , replaced MPU... what' smore action
Sir pcc3.3 mein kiya sabhi sensor by pass ket sakte hain.
Please all details given here
Sir voltage Puri hi but self nai uthaa rha.1500 kva dght
superb.
.sir
Sir aap Aux 101 ka posetive Wire ka number bta do TB koun sa hai.dono dg synchronize hai .
Aux 101 me 5 wair hote hai usme se red wair disconnect kardijiye
Very nice thank you sir
Thank you so much sir i under stood can u please tell me fuel water sens warning 428 ECM004!hi what to do this warning how reset normal condition
In our same 780kva dg fuel soilened coil is not working. We replaced now working normal
Water sensor warning is for coolant and there are 2 types of warning one is coolant level low and 2nd is coolant sensor hi....if it shows coolant sensor hi try to change coolant sensor harness...if still warning exists try to open sensor with 33 no. Spanner only to some extent when coolant starts leaking then tight it again then press reset button and if it still shows that then your coolant sensor is not working change the sensor.
Shivam Mahajan
Testing enginner incharge
Sudhir power ltd
Can you share video for DSE7310
Sir, governer card ko supply kaise ja Rahi, please explain karna.
No display and no supply on pcc 3.3 controler. Checked starter fuse. Negative voltage -2 volt found on. J20_21 connector. How to solve.
Sir 1500 kva ke Dg me auto wali button blink ker rahi hai mhi disple per not in auto likh ker aa raha hai kya Kare.
Send your no
This display having issues after some time running . So kindly start by auto and replace display after proper checkup. Thanks
Windig fhild me hiter kaha laga hota o kaisa kam karta windig ko nami se bachne ke liye
Hitting elements are fitted back side of alternator in air suction point. Also send me alternator and engine details
@@technicalmanish9032 1010 kva DG Cummins
Establishing comm kay hai sir
Display mai establishing comm aa rha hai ..uske baad kuch bhi nhi ho rha hai ..reset bhi nhi ho rha hai ..
Check card supply first one small light bleanking or not
demo mode kaise remove hoga
Hi,
How to check charging alternator .
When battery not charging.
I replace the carbon brush but not charging,
Winding all are ok.
What is the fault .
Please reply sir.
If charging alternater is in good condition but battery not charging there some leakage in wiring checke wiring
Battery charger konsa hain?
Remote Start vha lait jal raha es lai D G nahi start nahi horha hai Romote laet kaise khatam hoga
Which cantroller
Agar display on hi na ho to kya reason h
First check supply voltage
Sir 2250 kva ke bare me bistar se batar please
Dear sir please help
Display battan ok and aro battal not warking
Dear,
In this cantroller some issue after some time runing button not working.
Please confirm which button are not working.
DG HMI me running hours show nahi kr rha hai
Manish Bhai please all details falt and remove DG 1010 kva
how to fix the 236 ecm problem in pcc3300
Engine speed position sensor not detected
1 ) may be position sensor faculty.
2 ) faulty engine harness.
Please check 5 voltage dc in position sensor pin.
Please check previous our video sender voltage
Demo mode fault ka batao sir
Not repairable
solved the problem with the demo mode?
Sir remote system use kaise kiya jata hai
Sir demo foult kaise thik kare
KINDLY circuit diagram bna kar upload kar dain
Aap 2250 kva DG set ke saath batae please
Sir now 2250 KVA not available with me as soon as possible I try
Sir how to solve 2335 excitation fault in 1010kva cummins DG set.
How to solve fault code 7697 in Cummins engine.
Manishje total power com chori ho gya h ,please provide
Power com chahiye ya another cantroller what's aap no+919839787404 . Please send engine model
Aur video chaiye plzzz...
Which type of video
@@technicalmanish9032 Cummins controller troubleshooting video
🙏🙏
If HMI 320 in Demo mode, what we will do?
Please calibrate
solved the problem with the demo mode?
How to synchronize this pcc please make a video
Synchronisation video will be come in next month. Thanks
Sir I am waiting for synchronize pcc3300
Hi
HMI 320 (1010 kva ) showing ESTABLISHING COMMUNICATION FIRMWARE VERSION with some number's... What to do???
Cummins guy saying calibration is no use because the light in base board is not blinking ..so... I need to change baseboard of 3300 which is 1.3 lakh ...
he is telling true ......I am cummins engineer baseboard is failed ...
How calibration hmi 320 in pcc 3300
After one week
Video coming
Ok sir
Aadal me karna hai
Electrical wiring and use and fuel cycle full
Manish Ji aap kaha pr based ho, apna mobile no. denge to kuchh kam ki bat karni hai, 750 KVA ieset mai 3100 PCC ke bare mai.
I am in sudhir power limited as testing engineer incharge....you are wrong bro...this pcc only comes on demand for greater then 750 kva.....this pcc belongs to only 250 to 380 kva gensets
Thanks for watching my videos.
This cantroller for all DG
Shivam ji. What we have to check to clear the pcc net device failed 2895 error?
Sir is possible means future videos please explain in english
Ok
Sir how to solve error code 2898
I need the drawings for controllers
Which cantroller???
Power command 3.3
PCC3300
And how to installation between two generator cummins synchronization the all controllers power command 3.3
What's app number please and DG ke tank me bhi koi pump hota hai kya please explain
750 kva cummins ka dg hai
Aux 101 ka posetive wair disconnect kardo aap
English??
What is the default password of this controller?
1209 and 574
How calibration hmi 320 in pcc 3300