Hi, at 19:36, if 90% loading is allowed, means 0.9 x rating = 1200 kVA which gives rating as 1333.33 kVA. I didn't understand why you used 10% of 1200 to calculate that? To me my approach seems more straightforward. But then our results differ. Please clarify, thanks!
Excellant brother...
Good presentation brother
Hi, at 19:36, if 90% loading is allowed, means 0.9 x rating = 1200 kVA which gives rating as 1333.33 kVA. I didn't understand why you used 10% of 1200 to calculate that? To me my approach seems more straightforward. But then our results differ. Please clarify, thanks!
In primary side we are having 2voltages like 11kV and 33kV which one we have choose
Your power supply authority which voltage level provided that voltage has to be chosen
And how to deside steps like 7steps 5steps tap changing in trafo side pls let me know
I will make separate video on it. Thankyou for suggesting the topic
Hi engineer. May i know how to calculate the required incomer breaker size for main mdb as per dewa regulation. TIA
I am making G+ 4 building design and already publish 5 videos on that please follow all those video to know how to calculate MDB main breaker size