Sir mere 3 phase industrial condition hai. Automatic PF controller laga hai. 3 phase lord per ok chal raha hai. Per factory ki sari lights on karne par PF 0.75 dikhta hai. kaya karen sir ?
Sir ji Namaste🙏. mere yha par 800 kw load chal rha h. Aur P. F= 0.996 chal rha h. Isme 575kvar capacitor bank laga h. Muje apna p.f 1 karna h. Aur kitna kvar add karna padega.
Sir mere karkhane me 2kw load ka 3 phase capacitor bank laga hai jiska ampere 2.78 hona chahiye lekin ab check karne per 1.4 aa raha hai isase kya fark padega Kya isase fuse kat sakta hai
Industries me 3phase load kliye calculate kiya hu. 160Kw 3ph motor kliye formula ke hisab se 97kvar ayega. Iskliye 97KVar ka lagana hai ya 97/√3 = 56 kvar capacitor lagana hai?
Sir ji 🙏 m Panipat Haryana se hu maine 10hp ki three phase motor (7.5kw) ki motor h jiska (pf 0.85) h or mujhe ye nhi pta k (pf.0.99 ) kaise ho sakta hai h sir btaye kitne kvar Ka capacitor lagana pdega 🙏 sir reply fastley
Three phase 7.5hp 960 rpm Connection 6kw Power factor 0.788 aur 4kvar ka capicitor lagane ke bad bhi power factor 0.788 Sir kitne kvar ka capicitor lagaye ki pf 0.99 ho jaye
Sir substation mei three phase connection kaise kare. And mathematical kaise calculate kare kitne cap. Lgane honge 3 phases mei. Sab phases mei same rehte hai but kitne kre connect. kWh se nikale kya ?
Sharma ji थ्री फेज कनेक्शन ह लेकिन बिल्डिंग में सिंगल फेज उपकरण अलग-अलग लोड दिया जा रहा है तीनों फिजो में सामान लोड कभी कभी नहीं रहता है, ट्रांसफार्मर में 30 एंपियर की एमसीबी लगी हुई वह कभी कभी गिर जाती है , कृपया यह बताएं कि पावर फैक्टर सिंगल फेज में अलग-अलग लगेगा ,या थ्री फेस में? Total load=30 AMP ह तो पावर फैक्टर कितने का लगेगा?🙏🙏 मार्गदर्शन जरुर देवें 🙏
single phase upkaran ke liye power factor ki jarurat ni padti kyonki aajkal single phase upkaran rasistive ya capacitive ha. yadi tum alag alag lagana chahte ho to single phase lagega.
Hi Sir, I watch all your videos it's really interesting and informative. Could you please clarify that the load value 4850kw is included all types of load (resistive+cap+inductive) or only inductive load we need to consider?
Hi Sir, Thank you for your reply. But still I didn't get clarity. In general capacitor bank is making newly against only considering inductive and capacitor load or including resistive load? Please clarify sir..
@@premvigneshappiya9583 Dear thanks for watching my videos, Connected load of a building is always any type of electricity load ,doesn't matter it is resistivity, capacitive or inductive.
Very detailed information, Thanks for such good video.
Gajab sir main pura clear ho gaya thank!
Tup clear ho gaye ya tumhara funda?
Ok just joking thanks for watching my videos.
Helpfull video
Glad you found it helpful.
बहुत खूब 🥰🥰🥰🥰🥰🥰
Excellent 👍 HAT'S OFF 🙏SIR
Shandar 😊
Sir mere 3 phase industrial condition hai. Automatic PF controller laga hai. 3 phase lord per ok chal raha hai. Per factory ki sari lights on karne par PF 0.75 dikhta hai. kaya karen sir ?
light LED ha kya? Doosra 0.75 minus me dikhatahoga please check and reply.
Sir ji Namaste🙏.
mere yha par 800 kw load chal rha h. Aur P. F= 0.996 chal rha h. Isme 575kvar capacitor bank laga h. Muje apna p.f 1 karna h. Aur kitna kvar add karna padega.
No need to add KVAR only set your APFCR. And .996 is treated like 01.
How to determine of substation. kWh se nikaale kya ? I mean jitna kWh hoga utna kw multiplication kre.
Dear isme kwh ka jikar kahan ha ?
Sir mere karkhane me 2kw load ka 3 phase capacitor bank laga hai jiska ampere 2.78 hona chahiye lekin ab check karne per 1.4 aa raha hai isase kya fark padega
Kya isase fuse kat sakta hai
Pf weak hoga, bill zyada ayega.fuse nhi katega
Nice explanation sir ji.kindly make video on cable calculations.
Okay sure
Super, thanks
Thank you
Sir meri motar 15hp ki. Hai capistar kitana lagega
Single phase or 3 phase.
@@BuildingSanchalansingle phase me bhi capacitor bank laga sakte hai
سر پاور ہاؤس سے جو سپلائی میرے مین بریکر پر آتی ہے وہاں ولٹیج کا ڈفرنس ہے لیکن پاور ہاؤس کے آؤٹ پر وولٹیج برابر ہیں اس کو کسے برابر کرو
Industries me 3phase load kliye calculate kiya hu.
160Kw 3ph motor kliye formula ke hisab se 97kvar ayega.
Iskliye 97KVar ka lagana hai ya 97/√3 = 56 kvar capacitor lagana hai?
56 kvar in each phase.
1125kw ki sleepring motor ko kitna kvar lgega
Power capacitor ke liye motor ke type ki jarurat ni hoti. tum 1125 kw per calculate karo.
Sir mera 10hp moter 1400 rpm three phase hai to muje kitne kvar ka capacitor lagana hoga
Try to calculate
Sir ji meri 15 HP 960 rpm cg company ki moter h .iski name plate me pf .79 ,efic 90% aur 11kw likha h.Isme kitne kvar ka capeciter lagana padega
Sir Transfarmer 1500kw kahai aur load 1600kw ka hai to capicitar kitneka lagega
Dear Please calculate accordingly as video.
Pranaam karta hu sir jis junoon k saath aap teaching karte hain
Pranayam sir, I m not a teacher , I m engineer
Good sir 👍
Single phase capacitor hai to neutral and R, Y, B ke sath connection hoga , phase to phase nhi
yes
7.5 hp 1440 RPM motar me kitana kvar lagana parega
3 phase capacitor= 4.3 KVAR, if u select 1 phase then = 4.3/3=1.4 kvar each phase.
Sir ji 🙏 m Panipat Haryana se hu maine 10hp ki three phase motor (7.5kw) ki motor h jiska (pf 0.85) h or mujhe ye nhi pta k (pf.0.99 ) kaise ho sakta hai h sir btaye kitne kvar Ka capacitor lagana pdega 🙏 sir reply fastley
Sir very nice
Please tell that how much energy store a capaciter
According to capacitor capacity.
Three phase 7.5hp 960 rpm
Connection 6kw
Power factor 0.788 aur 4kvar ka capicitor lagane ke bad bhi power factor 0.788
Sir kitne kvar ka capicitor lagaye ki pf 0.99 ho jaye
4 KVAR ka 3 phase capacitor is OK not single phase please check.
if you ask the shopkeeper then ask 7.1 KVA or 4 KVAR
Thanks 🙏 sir
Sir ji DB and SDB me kiya Antar Hai
DB= distribution board
SDB= sub distribution board
@@BuildingSanchalan Kaun Sa Kaha pr use HOTA hai
@@hengineeringmind1647 according to use, jese three phase k liye DB aur single phase distribution k liye SDB
3 face 52 h.p. par kitna lagega
calculate accordingly
@@BuildingSanchalan hum kisan h itne pade like nhi h app nikal ke batao
50HP hai 52 nhi
17.5kvar 3ph 415v
Sir capacitor Bank ka connection digram bato kese connect hota hai load me please sir
will try
@@BuildingSanchalan thank sir g
Sir substation mei three phase connection kaise kare. And mathematical kaise calculate kare kitne cap. Lgane honge 3 phases mei. Sab phases mei same rehte hai but kitne kre connect. kWh se nikale kya ?
Sir 50 Questions M.S.T. Interview ke liye banaiye na
Dear sir HT Dg hota he kiya, agr hota he to sir please make video
11 केवी के डीजी होते हैं
Sharma ji थ्री फेज कनेक्शन ह लेकिन बिल्डिंग में सिंगल फेज उपकरण अलग-अलग लोड दिया जा रहा है तीनों फिजो में सामान लोड कभी कभी नहीं रहता है, ट्रांसफार्मर में 30 एंपियर की एमसीबी लगी हुई वह कभी कभी गिर जाती है , कृपया यह बताएं कि पावर फैक्टर सिंगल फेज में अलग-अलग लगेगा ,या थ्री फेस में? Total load=30 AMP ह तो पावर फैक्टर कितने का लगेगा?🙏🙏 मार्गदर्शन जरुर देवें 🙏
single phase upkaran ke liye power factor ki jarurat ni padti kyonki aajkal single phase upkaran rasistive ya capacitive ha. yadi tum alag alag lagana chahte ho to single phase lagega.
Thank you sir
Welcome
CT PT meter related ,MF,HT conection related, videos plz exam in meter testar Pgvcl
Hi Sir, I watch all your videos it's really interesting and informative. Could you please clarify that the load value 4850kw is included all types of load (resistive+cap+inductive) or only inductive load we need to consider?
Connected load
Hi Sir, Thank you for your reply. But still I didn't get clarity. In general capacitor bank is making newly against only considering inductive and capacitor load or including resistive load? Please clarify sir..
@@premvigneshappiya9583 Dear thanks for watching my videos,
Connected load of a building is always any type of electricity load ,doesn't matter it is resistivity, capacitive or inductive.
@@BuildingSanchalan OK sir.. Understood.. Thank you..
@@premvigneshappiya9583 मोस्टली यह लोड उतना ही होता है जितना बिजली का कनेक्शन लेते हैं
सर इसका कोई थंब रूल भी होता है
nahi
Sir ji apko PTA nhi hai ki dg me power bank ka use nhi kia jata hai.
Dost, HT generator per kiya jaata h jab bulk generation hota h.
Thanks for commenting me.
Please clear your concept don't misguide by providing such stuff,
Taki Jo M.S.T.hai wah Supervisor Bansake
Yes, thanks for watching