    Ocom-over compensation alaram will came how to solve. This video don't told OCOM alaram.

    • @itzelectrical
      @itzelectrical  4 месяца назад

      1st check how many apfc panels are there like, is there any local apfc panel connected near to load? If yes the set the target power factor in local apfc is less than main apfc panel.

    • @itzelectrical
      @itzelectrical  4 месяца назад

      2nd if there are no apfc panels in load end then check target power factor in this apfc controller. If the power factor is not set to 0.999 then set it.

    • @itzelectrical
      @itzelectrical  4 месяца назад

      3rd case if your load is very low, in that case the apfc controller also shows ovcom ( not continuously but rapidly). To solve this problem you have to either increase the load or install 1 kvar, 2 kvar and 5 kvar capacitor bank.

    • @itzelectrical
      @itzelectrical  4 месяца назад

      And sorry that was part 6 video not part 7 in which you can completely understand about different alarms in the apfc controller. And also there are no. videos on etasmart apfc control if you watch then you will definitely get a brief idea