ACB Control Circuit Diagram | ACB Wiring Diagram | Electrical Panel Basics | Hindi

Поделиться
HTML-код
  • Опубликовано: 19 авг 2024
  • In this video we have explained how control circuit wiring of an Electrically operated ACB is done. Main difference between Electrical & Manual ACBs are as below;
    Electrical ACB has
    a) Spring charging motor
    b) Closing Coil
    c) Shunt release Coil
    Using above things we can operate an ACB remotely whereas we cannot do the same with Manual ACB as after every close command given to Manual ACB, we need to charge the spring manually for next close operation.
    If this video seems informative, please do like, share & subscribe!
    Chapters:
    0.00 Introduction
    0.20 Power Circuit
    1.40 Control Circuit
    8.06 Outro
    Drawing PDF Download Link: drive.google.c...
    #electrical #panel #electricalpanelbasics

Комментарии • 108

  • @nivaskadam
    @nivaskadam 8 месяцев назад

    खुप सोप्या पध्दतीने समजवले सर thanks

  • @amitsharma1957
    @amitsharma1957 3 года назад +1

    Sir ji app ka samjhane ka tarika bahut acha hai thanks sir .

  • @mahbubulislam8808
    @mahbubulislam8808 9 месяцев назад

    Thank you brother ❤❤❤❤❤

  • @mkyoutube9619
    @mkyoutube9619 2 месяца назад

    Bahut achha explained sir

  • @deeprajshanker2325
    @deeprajshanker2325 3 года назад +2

    Thank you .thank you.. many times for this informative VDO which I have been searching for long time to understand ACB control diagram..... Kindly guide us for actual wiring diagram in next vdo

  • @yashwantchouhan340
    @yashwantchouhan340 11 месяцев назад

    Thanks for this informative video🎉🎉

  • @sunilpatil1478
    @sunilpatil1478 11 месяцев назад

    Very nice explained thnks 🎉🎉

  • @vijaysharma3560
    @vijaysharma3560 Год назад

    Thanks sir good explain

  • @mogufranalisaifi8067
    @mogufranalisaifi8067 6 месяцев назад

    Bahut achche se samjhaya sir

  • @sujoyghosh7468
    @sujoyghosh7468 2 года назад

    খুব ভালো বুঝিয়েছেন ধন্যবাদ আপনাকে

  • @masumahmed7978
    @masumahmed7978 Год назад

    Best Video ever seen

  • @acelectricals3979
    @acelectricals3979 3 года назад

    Thank you Sir for your Valuable Video

  • @ashishvitekar3474
    @ashishvitekar3474 3 года назад

    Very nice explain and informative video's keep it up

  • @gamvirdangol2530
    @gamvirdangol2530 2 года назад +1

    Very informative and clear video. Further can you please explain the wiring of UVR (MN coil) and operation. I wish to use Closing coil , MN coil & MCH coil for remote operation.

  • @pradeepgiri3589
    @pradeepgiri3589 Год назад

    thankq dear sir 🙏

  • @DieselGeneratortraining
    @DieselGeneratortraining 2 года назад

    Very good explanation

  • @masumahmed7978
    @masumahmed7978 Год назад +1

    nice. please VCB control circuit upload karu

  • @anirbansasmal4942
    @anirbansasmal4942 3 года назад

    Ohh Dada fatia dia6o guru

  • @HEERASINGH-vl1mr
    @HEERASINGH-vl1mr 3 года назад

    Very Nice Information Sir....

  • @SabirHussain-oy6il
    @SabirHussain-oy6il 2 года назад

    Thanks sir

  • @SACHINSINGH-jj8gq
    @SACHINSINGH-jj8gq 2 года назад

    Please sir practically one video..

  • @ujjalchakma6538
    @ujjalchakma6538 2 года назад

    very informative video

  • @suryakantyadav128
    @suryakantyadav128 3 года назад

    Nice explation,

  • @mohdmasoom9324
    @mohdmasoom9324 3 года назад +2

    sir me ek company me kam karta hu to bha pr ACB ke breaker h sir jo sarkari line se karant kat gaya to jo bha main panal h bha se lineman kuch kiya tha to ye ACB hold ni kr pa rha line jane se phale sb kuch normal tha sb kuch acche se kam kr rha tha lakin lineman ne line kat kr diya or osne koi tar galat jod jiya tha to ACB hold ni kr rha reset kr diya push bhe kr diya lakin jb green button push kr rha to bo kam ni kr rha free ho gaya tha sir kiya bajah ho sakte h plz reply sir or ha sir aap video bhut acche banate h or daigram good

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  3 года назад +1

      First of all check karo ki control supply aa raha k nahi. Agar aa raha hai to ye dekho ki U/V coil me supply available hai ki nahi. Agar ye dono available hai to close push button tak supply check karo. then push button press karke closing coil ki terminal pe dekho line ja raha k nahi. Agar U/V coil me continuous supply nahi rahega and closing coil tak line nahi jayega to breaker on nahi hoga.

    • @mohdmasoom9324
      @mohdmasoom9324 3 года назад

      Sir supplay aa rhe in kr rhe h lakin jo puse yani charge karke jo green button ko puse karte bo button kam ni kr rha yani free ho gaya h fast sb kuch ok lakin line man ne line kuch time ke liye kat jo bahar ka maine line brekar h or bha se osne kuch wire idher odher kr diye to line to aa gai ACB tak lakin in kr rha or hamne hand charge kr diya lakin green button puse kr rhe to bo free ho gaya kia ACB ka maine line board se masla h aap jante ho

  • @harishankergupta7519
    @harishankergupta7519 Год назад

    Good

  • @rajeshsteelplant4453
    @rajeshsteelplant4453 2 года назад

    👌
    .. Sir interlock between two acb

  • @manoranjan4598
    @manoranjan4598 3 года назад

    Nice sir please aur banaiye video ACB drawing , repair ka

  • @masudranain2524
    @masudranain2524 3 года назад

    Thanks vroo

  • @hemantkanaujiya3561
    @hemantkanaujiya3561 3 года назад

    Very good 👍👍👍👍

  • @bablurana457
    @bablurana457 3 года назад

    Informative video

  • @oryxengineering4383
    @oryxengineering4383 2 месяца назад

    Please make more vedios panels

  • @agyaramkannojia1581
    @agyaramkannojia1581 3 года назад

    Very nice vidio sir ji

  • @AAgrwal
    @AAgrwal 4 месяца назад

    Ye to thik hai lekin mujhe ek question hai jo 3 month se clear nhi ho paya ACB ko only insulater ke jaise kaise kar sakta hai mera matlab hai usko bypass kaise kare bar bar. Trip Ho to shirf bypass kar ne ka ek full video details me banaiye thanks 👍

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  2 месяца назад

      Apka question clear nahi hai. May be you are asking about Isolator. Agar ACB me protection release laga hai to fault jab tak clear nahi hoga tab tak trip unit ko reset nahi kar sakte. This is as per safety guidelines. You can't close any circuit breaker until unless the fault is cleared for which the breaker has tripped.

  • @sarjansharma390
    @sarjansharma390 2 года назад

    Sir anding puming pr video banao please

  • @kidseducation3808
    @kidseducation3808 3 месяца назад

    Sir UV coil ka video banaiye please sir ❤❤❤

  • @ashishpatil6899
    @ashishpatil6899 3 года назад

    Nice

  • @rajukumarthakur8491
    @rajukumarthakur8491 3 года назад

    Sir ht breker anty pumpking ka vedio banaey

  • @johnbryntponesto8514
    @johnbryntponesto8514 4 месяца назад

    sir when does ACB normally open contact become close contact? is it when na closing coil have a voltage ?

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  4 месяца назад

      ACB contacts are potential free contact. It is latched with a rod which moves with ACB make-break contacts. Auxiliary contact blocks only change their state(NO to NC or NC to NO) when ACB is turned on and get back to the previous state when turned off.

  • @excellentelectricalknowled6672

    When motor spring charges complete Motor automatic off auxiliary contact drawing me nahi hai kya sir...

  • @DeepakSharma-dv9lt
    @DeepakSharma-dv9lt 3 года назад

    Please tell me how to spring charge in auto mode

  • @acelectricals3979
    @acelectricals3979 3 года назад

    Dear
    Sir I have required Control wiring Circuit diagram for 4 INCOMER and 1 BusCoupler 2EB (2000A 4P ACB EDO ) + 2 DG (1000A 4P ACB) EDO ) B/C also 2000A 4P both DG Synchronisation by Synchronization Woodward EASYGEN 2300 , for and 1 PLC for auto operation. Sir if anyone who can prepare the schematic drawing.

  • @rahullifetime1001
    @rahullifetime1001 3 года назад

    Two acb inter loking with tnc switch control wiring diagram

  • @sunilsunil1962
    @sunilsunil1962 2 года назад

    Hi sir can you explain this operation with ilpb

  • @chetbahadurmajhi1250
    @chetbahadurmajhi1250 5 месяцев назад

    Dear sar Iam frm nepal 400 KW hydropowar me use hey larsen /SR18g / 800in ka acb hey on hojayega but 15minetka bat triip hoga plz teach me🙏

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  5 месяцев назад

      Reason bahat kuch ho sakta hai. Agar fault create ho raha hai to release main indication ayega. Agar fault nahi hai for v kuch time k interval main trip ho raha hai to UV coil check karna hoga. Ho sakta hai UV coil de-energise ho raha hai. Agar heating issues hai to arc chute ko clean karna hoga. ACB k contacts ka tightness check karna hoga

  • @SabirHussain-oy6il
    @SabirHussain-oy6il 2 года назад

    Sir I want know that acb again to again. Try but acb not on I mean hold what s region
    Please explain

  • @shantusaikia8490
    @shantusaikia8490 Год назад

    Why does an acb stop button use NO contact?

  • @nikhildalui8563
    @nikhildalui8563 2 года назад

    Sir spring charge bond kaye see hoja. Continue chalte rahega kaya????

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  2 года назад +1

      Spring full charge hone k baad charging motor cut off ho jaata hai..

  • @mahiprakash862
    @mahiprakash862 Год назад

    D G Beaker tnc se hold ni ho ra.menual bhi on ni ho raha he waring kese chack karun

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  Год назад

      Agar U/V coil hai circuit me to check kariye usme supply ja raha k nahi. Agar U/V nahi hai to kisi tarha shunt release coil me supply jaa raha hai aur ACB trip ho raha hai. Ye do check karne k baad v problem hai to mechanical issue hai

  • @changeurlife89
    @changeurlife89 2 года назад

    How motor stops when spring charge completed

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  2 года назад +1

      Charging motor consists a limit switch which cuts the power when spring is fully charged.

  • @SelvaKumar-uh3ss
    @SelvaKumar-uh3ss 3 года назад

    Very clear, but one doubt the spring charging motor have auxiliary contact? There's only 3terminals. How we have to connect please reply

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  3 года назад

      Spring charging motor has two terminals(Black sleeves cable).

    • @SelvaKumar-uh3ss
      @SelvaKumar-uh3ss 3 года назад

      @@ElectricalPanelBasics yes sir, 2black and 1 red is there, if 4 wire is there we can use 2for motor coil and 2 for contact, that's y i am confusing, please explain me, thanks

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  3 года назад

      In L&T C Power ACB, C & D terminal is used for charging motor power supply. Other terminals(if any) are used for internal purpose. For control wiring, we only need to provide control supply to charging motor.

  • @vasanthkumar-zy4yg
    @vasanthkumar-zy4yg 3 года назад

    Under voltage conection

  • @suryakantyadav128
    @suryakantyadav128 3 года назад

    Sir ye trip micro switch ka possition knha pe hai ,dikha sakte hai kya live aisa possible hai ,ya phir drawing ki mathed say hi samjha djye

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  3 года назад +1

      Trip Alarm Contact (TAC) micro switch breaker k trip bar(rod) k sath attach raheta hai. Jab v kise fault k karan breaker trip hota hai to TAC ka limit switch actuate hota hai momentarily. Then ek Aux. Contactor k holding logic k through trip indication ko supply milta hai. As well as closing prevention v valid raheta hai until unless fault is cleared and reset push button is pressed.

    • @suryakantyadav128
      @suryakantyadav128 3 года назад

      @@ElectricalPanelBasics theak hai sir Mai practically spare breaker me find out krne ki kosis krta hu ,thanks

  • @arvindparashar8134
    @arvindparashar8134 Год назад

    ABB

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  10 месяцев назад

      The working principle of all breakers are more or less same. If we understand the logic, only the terminal numbers will be different

  • @manuyadav8272
    @manuyadav8272 Год назад

    Isme kitne coil laga sakte hain

  • @VipulKumar-sk3eu
    @VipulKumar-sk3eu 6 месяцев назад

    UV connection??

  • @sushantcollection1135
    @sushantcollection1135 Год назад

    Street light control diagram milegaa

  • @shabujctg6871
    @shabujctg6871 3 года назад

    Please give us the control wiring pdf

  • @ashishvitekar3474
    @ashishvitekar3474 3 года назад

    Sir,
    But how breaker trip when fault occurred

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  3 года назад +1

      ACB has microprocessor or thermal based protection release with inbuilt CT. CT sense the fault current and sends off/open command to protection release. Protection release is connected with the trip bar of ACB. In any fault condition trip bar gets mechanical input from the release and the ACB immediately turns off.

    • @ashishvitekar3474
      @ashishvitekar3474 3 года назад

      Sir,
      Please One more query, if breaker trip directly through lever of release processor then what is the use of shunt coil only for manually breaker off

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  3 года назад

      Shunt release is used to turn off the breaker through TNC or any additional protection relay. For example if we use IDMT relay, then IDMT will send trip command to shunt coil in case of any fault detection.

    • @ashishvitekar3474
      @ashishvitekar3474 3 года назад

      OK Thank you for your very fast and early reply with cleared dount

    • @ashishvitekar3474
      @ashishvitekar3474 3 года назад

      Sir,
      Please clear query in ACB, what is the difference between Aux. Contacts & secondary isolating contacts, where it's used for what purpose etc.
      Also if possible make videos on the same, full details of wiring diagram of interconnected etc.
      Thank you

  • @himanshu8623
    @himanshu8623 Год назад

    UV coil kha gyi isme se.... 🥲.. Bina uske toh acb chalega hi niii

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  Год назад

      Really? But at the time of testing it was perfectly working. By the way can you please explain "ACB U/V coil k bina kaise nahi chalega!!"

    • @himanshu8623
      @himanshu8623 Год назад

      @@ElectricalPanelBasicsChalega nii se wo mtlv nii h..i mean.. agar m uv coil na lgau toh mera breaker trip niii marega..
      If i interlock 2 acb... Toh chiye na mrko uv coil for safety

    • @ElectricalPanelBasics
      @ElectricalPanelBasics  Год назад

      That's the point. We generally use U/V coil for interlocking purpose.
      You may watch below video where we have used U/V coil to interlock two ACBs.
      ruclips.net/video/1Bw-xZvSts0/видео.html

  • @furkanmulla3992
    @furkanmulla3992 11 месяцев назад

    Apka number

  • @pradeepgiri3589
    @pradeepgiri3589 Год назад

    thankq dear sir 🙏

  • @SACHINSINGH-jj8gq
    @SACHINSINGH-jj8gq 2 года назад

    Thanks sir

  • @SACHINSINGH-jj8gq
    @SACHINSINGH-jj8gq 2 года назад

    Thanks sir