How to Change Out a Capacitor Bank

Поделиться
HTML-код
  • Опубликовано: 24 янв 2025

Комментарии • 34

  • @bubblehead78
    @bubblehead78 4 года назад +6

    I'm a retired submarine electronics technician. I've watched a number of T&D World videos recently. The care and professionalism shown by the crews are exceptional and a model for other dangerous fields of work.

  • @edge1289
    @edge1289 5 лет назад +16

    Not one word about hazards involved during the pre job briefing. Work performed in the primary area in leather gloves without 100% cover up. I don’t care if you read no load on that bank, you never open a cap without a load buster. Geez guys, bad shit happens in a heartbeat and can change lives forever. When complacency sets in, its time for a boot in the ass.

    • @markmcvey7686
      @markmcvey7686 3 года назад

      These are switched capacitors. You probably didn’t see the oil switches under the link break cut outs. The were measuring current confirm the switches were open. The capacitors have less than 50 volts after 5 mins from deenergization anyway. If the meter showed current and the switch was defective you would pull the lever on the cut out to deenegize the phase. Load break tool does not work well on a type C link break cutout. It’s not impossible but breaking the link is easier and a little safer. I total agree about prejob brief. No talk of dangers and what could go wrong.This was not gloving work and at this voltage minimum approach distance was never close so cover up with hoses would require gloves a different approach.

    • @pumkinface1
      @pumkinface1 2 года назад

      @@markmcvey7686 always use your loadbreak. better safe than sorry

  • @metersocket00
    @metersocket00 7 лет назад +5

    I once got a nice 7,200V shock from an undischarged 200kVAR correction capacitor, was completely disconnected from the power source for a while, had one hand on the ground and grabbed the "hot" wire with the other. Threw me back 5 FT and burned my fingers pretty good. No serious injuries of course, almost crapped my pants through. Now I will not touch one until I, myself short out the terminals to make absolute certainty there is no charge.

    • @lumberwhack6294
      @lumberwhack6294 6 лет назад

      Luckily the shock from the capacitor is like a static discharge and very short in duration, otherwise you would have been fried lol

    • @seanmccarthy7582
      @seanmccarthy7582 5 лет назад +2

      It's not dead if it's not grounded. ABC, 123... Mary had a little lamb. Capacitors have the capacity to kill you.
      Glad you got the chance to learn from it yourself.... instead of being learned from.
      I really am glad your ok.

    • @edge1289
      @edge1289 5 лет назад +1

      metersocket00 shunt the can for Christ sakes.

    • @hassanalkhair5235
      @hassanalkhair5235 5 лет назад

      Nothing about Safety procedure to discharge the Capacitors??

    • @markmcvey7686
      @markmcvey7686 3 года назад

      A cautionary tale. Always assume a capacitors is energized unless it is shunted. Single bushing to case and two bushing is bushing to bushing. Even though a capacitor has a discharge resistor installed you can never see if it is undamaged unless tested. My company requires all capacitors not in use to be shunted. Our specification from the manufacture requires the cans even for banks to be shunted for shipping.

  • @danielgroves1597
    @danielgroves1597 8 лет назад +7

    No gloves and sleeves, love it.

    • @AchillesWrath1
      @AchillesWrath1 8 лет назад

      +Daniel Groves But them gloves...theyre so hot and uncomfortable, sarcasm. If you did that where i work you'd get sent home for at least a week if not fired.

    • @danielgroves1597
      @danielgroves1597 8 лет назад

      +AchillesWrath1 oh you would where I work too lol.

    • @swang6782
      @swang6782 7 лет назад +6

      Daniel Groves the dish gloves are for rookies, once you learn your way around the poles and cans all you need is a union hat with stickers and a pension to bankrupt the state.

  • @EphemeralProductions
    @EphemeralProductions 2 года назад

    i don't have any electrical training. So these cap banks are basically used for voltage regulation?

  • @acescape88
    @acescape88 4 года назад +2

    It didnt show the most important part which is grounding the bank before bringing it to the ground

  • @BenjaminEsposti
    @BenjaminEsposti 7 лет назад +5

    Hey T&DTV ... I have a question. Why did you go near the capacitors without discharging them or at least shunting across their terminals? Do they have internal bleeder resistors, or did you not show this in the video? ...

    • @PostureGrounds
      @PostureGrounds 3 года назад

      Because they grounded them and let em bleed off

  • @denniscurless904
    @denniscurless904 7 лет назад +1

    If APS is a sticking company as shown in other videos of them working, I would like to see the blankets and line hose being applied.

    • @bungahole2033
      @bungahole2033 5 лет назад

      Dennis C they claim to be a hotstick company, but apply rubber with gloves.

  • @juancasillas3751
    @juancasillas3751 3 года назад

    Hi Sir do you know what meter was used? Thanks

  • @jaykuckuck9986
    @jaykuckuck9986 Год назад

    did I miss the step of grounding the old capacitors for safety

  • @Backyardmech1
    @Backyardmech1 6 лет назад

    Of course they’re showing they’re having a pre job safety meeting.
    I’m sure most do, but from where I come from (we have to show things like that to show we are doing it for clients, even though we know what the hell we are doing) we know what to do, and communicate as we progress with our work. I’m not a lineman, but the work progresses the same, and safety is top priority. Just my line of work is considered “low risk” in most cases.

    • @Engineer9736
      @Engineer9736 6 лет назад +2

      Backyardmech1 It’s physical labour, repetitive work. After doing it 50 times right you might make a slip on the 51th time. Such safety breefings are meant to keep your mind active on what you are doing and thus staying safe.

  • @николайл-ц1е
    @николайл-ц1е 3 года назад

    Заметил на 3:39 в машине в кузове тиски. Оригинально)))

    • @ElectroTree01
      @ElectroTree01 2 года назад +1

      Yes. I was somewhere and somebody had backed the vise handle into the wood and it bent the handle.

  • @colinmoore9511
    @colinmoore9511 5 лет назад +4

    Never seen anything about discharging the capacitors, ground it out ensure the capacitor is completely discharged.

    • @movax20h
      @movax20h 4 года назад

      Surely they did it tho :) There is discharge resistors in the housing, but it will take few minutes for it to discharge caps, especially the high voltage ones to safe level.

  • @jrconner9115
    @jrconner9115 8 лет назад +5

    no gloves, no sleeves, no loadbuster on the cutout opening at the beginning!! nice. Looks like a non union job

    • @antroballen
      @antroballen 8 лет назад +7

      JR Conner you would use a loadbuster even after you amp checked it?

    • @keepers0215
      @keepers0215 7 лет назад +10

      Arizona Public Service is a sticking company, IS union, doesn't require gloves or sleeves (not OSHA mandated) and don't have to conform to the same rules your company uses. Why would you need a loadbuster on a cap rack if your vac switches were confirmed open with an amp check?

    • @lukerooks947
      @lukerooks947 6 лет назад +5

      Another dumb ass union guy. Too stupid to realize amps = load. No amps = no load buster.
      Sincerely a dirty ole scab.

  • @robertkovalesky8343
    @robertkovalesky8343 Год назад

    Y’all don’t shunt out the cells?

  • @orisonsquirrell
    @orisonsquirrell 6 лет назад +2

    when u can do this work anymore... / u know squirrels.. :(