- PUMP Room
Indirect water supply is the most important part of the pump system in this
project which is a separate area for pump fixing which is called the pump room.
In this pump room we have installed 6 No Mono Block Pumps and 2 no’s
Submersible Pumps for various systems in this project. Find all the details
below.
Pump Capacity Details and what is models of the pump ?
Drinking water supply Pumps
(1nos working + 1nos stand by
2 no’s
Capacity 4Ips
Head 90 mts
Pump Description
Make Kirloskar
Model KDT 1388
Type Monoblock
Section & Delivery 65x 50 mm
Seal type Gland
packing
Material of Construction
Casting Cast Iron
Impeller Cast Iron
Shaft Carbon Steel
(C-40)
Class of Insulation NA
Degree of Protection IP 55
Power rating 9.3 K w/12.5
Hp
Speed 3000 RPM
Power Supply Voltage Range 300-400 V
(Three
Phase)50Hz
Balance 4 no Pump is same model and same Capacity .
Drainage pump
Dewatering Submersible Pumps
water supply Pumps
(1nos working + 1nos stand by
2 no’s
2 Capacity 1 to 6.2 Ips
3 Head 3 to 14 mts
4 Location C7 Jasmin
Tower
Pump Description
Make Kirloskar
Model Eternaa750CW
Type Submersible
Pumps
Section & Delivery 50 mm
Seal type
Material of Construction
Casting Cast Iron
Impeller Cast Iron
Shaft Carbon Steel
(C-40)
Class of Insulation NA
Degree of Protection IP 55
Power rating .75 kw
Speed 3000 RPM
Power Supply Voltage Range 300-400 V
(Three
Phase)50Hz
Mono block pumps are mainly recommended for freshwater as well as fluids
which are not chemically violent toward the components of the pump. These
pumps are mainly used for Big buildings Apartment’s, industrial, civil due to
their consistency and strength.
This precautionary measure must be followed before the mono
block pump startup:
• Do not run centrifugal pumps under low rated flow or with suction or
discharge valves off. This condition can quickly lead to mono block
pump failure and physical injury.
• Always disconnect and lock out power to the driver before you perform
any installation or maintenance tasks.
Mono block pump start-up in reverse rotation can result in the contact
of metal parts, heat generation, and breach of containment.
• Clean the system thoroughly to remove dirt or debris from the pipe
system to prevent failure at the initial pump startup.
• Bring variable-speed drivers (if installed) to the rated speed as quickly
as possible.
• Generally, if the temperatures of the pumped fluid will exceed 200°F
(93°C), then warm up the pump prior to pump start-up.
• Circulate a small amount of fluid through the pump until the casing
temperature is 100 °F above the fluid temperature before pump start-up
to avoid thermal shock to the liner and impeller and to prevent loss of
the mechanical seal.
Mono Block pump starts up procedure:
• Before pump start-up you must perform these tasks: -
• Open the suction valve.
• Fully close or partially open the discharge valve, depending on system
conditions.
• . Start the driver.
• Slowly open the discharge valve until the pump reaches the desired flow.
• Check the pressure gauge to ensure that the pump quickly reaches the
correct discharge pressure.
➢ Monitor the pump while it is operating.
➢ Check the pump for bearing temperature, vibration,
and noise.
➢ Clean all pumps 1-time weekly Filter must be
mandatory.
➢ Always ensure the flow of water to the pump room.
➢ If in any case there is water flow in the pump then run
the pump room drainage pump at that time, remove the
water from inside to outside.
➢ Check All U.G Tank Water Tube Levels Before
Running the Pump .
Please Like, Comment and Share our videos.. and Don't forget to Subscribe Our channel & press the 🔔 icon.
Copyright Disclaimer19- Copyright Disclaimer under section 107 of the Copyright Act 1976, allowance is made for "fair use" for purposes such as criticism, comment, news reporting, teaching, scholarship, education and research. Fair use is a use permitted by copyright statute that might otherwise be infringin. If any issues please contact me personally...🙏🙏🙏 Gmail - gaura90@gmail.com Thank you 🙏🙏🙏 .. II
👍👍👍👍