  • PUMP Room
    Indirect water supply is the most important part of the pump system in this
    project which is a separate area for pump fixing which is called the pump room.
    In this pump room we have installed 6 No Mono Block Pumps and 2 no’s
    Submersible Pumps for various systems in this project. Find all the details
    below.
    Pump Capacity Details and what is models of the pump ?
    Drinking water supply Pumps
    (1nos working + 1nos stand by
    2 no’s
    Capacity 4Ips
    Head 90 mts
    Pump Description
    Make Kirloskar
    Model KDT 1388
    Type Monoblock
    Section & Delivery 65x 50 mm
    Seal type Gland
    packing
    Material of Construction
    Casting Cast Iron
    Impeller Cast Iron
    Shaft Carbon Steel
    (C-40)
    Class of Insulation NA
    Degree of Protection IP 55
    Power rating 9.3 K w/12.5
    Hp
    Speed 3000 RPM
    Power Supply Voltage Range 300-400 V
    (Three
    Phase)50Hz
    Balance 4 no Pump is same model and same Capacity .
    Drainage pump
    Dewatering Submersible Pumps
    water supply Pumps
    (1nos working + 1nos stand by
    2 no’s
    2 Capacity 1 to 6.2 Ips
    3 Head 3 to 14 mts
    4 Location C7 Jasmin
    Tower
    Pump Description
    Make Kirloskar
    Model Eternaa750CW
    Type Submersible
    Pumps
    Section & Delivery 50 mm
    Seal type
    Material of Construction
    Casting Cast Iron
    Impeller Cast Iron
    Shaft Carbon Steel
    (C-40)
    Class of Insulation NA
    Degree of Protection IP 55
    Power rating .75 kw
    Speed 3000 RPM
    Power Supply Voltage Range 300-400 V
    (Three
    Phase)50Hz
    Mono block pumps are mainly recommended for freshwater as well as fluids
    which are not chemically violent toward the components of the pump. These
    pumps are mainly used for Big buildings Apartment’s, industrial, civil due to
    their consistency and strength.
    This precautionary measure must be followed before the mono
    block pump startup:
    • Do not run centrifugal pumps under low rated flow or with suction or
    discharge valves off. This condition can quickly lead to mono block
    pump failure and physical injury.
    • Always disconnect and lock out power to the driver before you perform
    any installation or maintenance tasks.
    Mono block pump start-up in reverse rotation can result in the contact
    of metal parts, heat generation, and breach of containment.
    • Clean the system thoroughly to remove dirt or debris from the pipe
    system to prevent failure at the initial pump startup.
    • Bring variable-speed drivers (if installed) to the rated speed as quickly
    as possible.
    • Generally, if the temperatures of the pumped fluid will exceed 200°F
    (93°C), then warm up the pump prior to pump start-up.
    • Circulate a small amount of fluid through the pump until the casing
    temperature is 100 °F above the fluid temperature before pump start-up
    to avoid thermal shock to the liner and impeller and to prevent loss of
    the mechanical seal.
    Mono Block pump starts up procedure:
    • Before pump start-up you must perform these tasks: -
    • Open the suction valve.
    • Fully close or partially open the discharge valve, depending on system
    conditions.
    • . Start the driver.
    • Slowly open the discharge valve until the pump reaches the desired flow.
    • Check the pressure gauge to ensure that the pump quickly reaches the
    correct discharge pressure.
    ➢ Monitor the pump while it is operating.
    ➢ Check the pump for bearing temperature, vibration,
    and noise.
    ➢ Clean all pumps 1-time weekly Filter must be
    mandatory.
    ➢ Always ensure the flow of water to the pump room.
    ➢ If in any case there is water flow in the pump then run
    the pump room drainage pump at that time, remove the
    water from inside to outside.
    ➢ Check All U.G Tank Water Tube Levels Before
    Running the Pump .
    Please Like, Comment and Share our videos.. and Don't forget to Subscribe Our channel & press the 🔔 icon.
    Copyright Disclaimer19- Copyright Disclaimer under section 107 of the Copyright Act 1976, allowance is made for "fair use" for purposes such as criticism, comment, news reporting, teaching, scholarship, education and research. Fair use is a use permitted by copyright statute that might otherwise be infringin. If any issues please contact me personally...🙏🙏🙏 Gmail - gaura90@gmail.com Thank you 🙏🙏🙏 .. II