Connect The Ground & Neutral Wires

Поделиться
HTML-код
  • Опубликовано: 28 авг 2024
  • The Only time Electricians connect the Neutral Wire and the Grounding Conductor is at the Service Entrance! Call George now @770.596.1437 ‪@Argoelectrical‬ #ArcFaultCircuitBreakers

Комментарии • 174

  • @phillystrangler7337
    @phillystrangler7337 3 месяца назад +100

    Hack , I pray you don’t have any apprentices under you

  • @barryjohnson7183
    @barryjohnson7183 6 месяцев назад +50

    You see that fraid wire on the ground at the bus bar😮

    • @michaelbourassa2379
      @michaelbourassa2379 21 день назад +1

      Good catch but it really isn't going to hurt anything

    • @rustyshackelford1230
      @rustyshackelford1230 13 дней назад +6

      No way I would leave that wire like that and make a video.😂

  • @GailUrge-vq6qn
    @GailUrge-vq6qn Месяц назад +9

    Wow, I'm graced again at being fortunate enough to see another "RUclips lectrician".

  • @williamlowther7051
    @williamlowther7051 2 месяца назад +11

    Another classic example of a little bit of knowledge is not always a good thing, love the ground ding terminology

  • @gary01826
    @gary01826 3 месяца назад +36

    What’s the melted cable used for?

    • @djpcinema
      @djpcinema Месяц назад +1

      😆

    • @eyeswideshut7732
      @eyeswideshut7732 Месяц назад +4

      Welding 😂

    • @greenbudkelly2820
      @greenbudkelly2820 Месяц назад +3

      It’s rated at 125% so it’s fine

    • @gregbaldwin1900
      @gregbaldwin1900 Месяц назад +2

      It's not melted, they didn't lube the feeder wires up good enough and outer sheathing got caught at the first connector..or on a coupling at one of their 4 pre-fabbed 90°'s haha

  • @gatsbylight4766
    @gatsbylight4766 11 месяцев назад +48

    And to point out before someone asks: 'Yes', some inspectors would ding you if any of your conductors were connected to a neutral/ground bar but not all of the strands were under the set screw [ 0:33 ].

  • @snowman6686
    @snowman6686 3 месяца назад +17

    You can use copper on any electrical installation, it doesn't have to be a commercial job. Smaller conductor size, easier to bend and you don't lose the neutral like you do in Aluminum SEC.

    • @pico3tinez
      @pico3tinez 3 месяца назад

      I think he means they are not using aluminum because it is a commercial job… maybe, probably

    • @JustHazardous
      @JustHazardous 2 месяца назад +3

      Copper is definitely not "easier to bend" than aluminum.

    • @snowman6686
      @snowman6686 2 месяца назад

      @@JustHazardous You have your opinion. I have mine.

    • @walsakaluk1584
      @walsakaluk1584 2 месяца назад +1

      ​@@pico3tinezexactly. Cu is smaller for the same loading. Big Al conductors on a tight site, this looks tight, is a pain. Then there's corrosive environments...not stated.

    • @pico3tinez
      @pico3tinez 2 месяца назад

      @@walsakaluk1584 thanks

  • @GypsyMoFoJoe
    @GypsyMoFoJoe 5 месяцев назад +20

    You didn’t wait for your helper to get back with the plastic bushing for the load side pvc conduit. Also, I’d like to see the chart you used to size up your groun”ding” conductor

    • @stanleywilliam
      @stanleywilliam 2 месяца назад +2

      Haha. #4 CU for 200A all day long. I guess he thought that needed to be 125% also 😂

  • @cletuss57
    @cletuss57 6 месяцев назад +7

    advantage of a 4-wire system: if faults develop in the line, you have a safety conductor (the EGC) that functions without parallel paths through random neutrals and grounds. Such a separate EGC will completely clear a case fault (e.g. a hot wire breaking loose and contacting a chassis) via the breaker if it’s working properly. With a three-wire system it was common to be accidentally carrying neutral current on EGCs which at times of uneven loads (across L1 & L2) can be significant. And it has been deadly on numerous occasions for example when maintenance workers are well earthed, and happen to separate a conduit or EGC and their body becomes the circuit bridge for the accidental neutral currents or when the EGC wasn’t good enough allll the way back to the panel to clear an intermittent or poor-connection case fault via the overcurrent protective device. Disadvantage of 4-wire: one more wire required. Nowadays it’s code requirement in the US to have a 4-wire system and to NEVER BOND EGC and neutral anywhere but the first point of disconnect. Usually the meter base or the Service Entrance. Not an electrician, YMMV, do your own research, not liable for any opinions given here. See Mike Holt’s grounding website.

  • @waterlec8718
    @waterlec8718 9 месяцев назад +52

    L👀K at ripped insulation on the load side of the meter... Holy shit ⚡‼️

    • @LenstskyYT
      @LenstskyYT 8 месяцев назад +1

      Right 😂😂

    • @Hathorr1067
      @Hathorr1067 2 месяца назад +3

      That's just the plastic jacket. It protects the insulation.

  • @drycreek3204
    @drycreek3204 7 дней назад

    It's a feed thru panel, so you need 2 hots, 1 neutral & ground to feed the sub panel. That is common practice for someone who is licensed...

  • @UpWheel.
    @UpWheel. 3 месяца назад +5

    Nice fiber bushing on load side

  • @walsakaluk1584
    @walsakaluk1584 2 месяца назад

    Thanks for the clear explanation for the non Americans out here on the interstring.
    Very concise.

  • @zhumusic-ng9tr
    @zhumusic-ng9tr 8 месяцев назад +8

    Jus call it neutral you know yuh want tooooo

  • @linehandibew6205
    @linehandibew6205 3 месяца назад +13

    No plastic bushing again!!!!

    • @jeremytate3664
      @jeremytate3664 2 месяца назад

      Not required with pcv fittings but I still go with them... however code does not require a bushing when using pvc fitting.

    • @jeremytate3664
      @jeremytate3664 2 месяца назад

      Also thank God he didn't have any red phase tape since that is usually ONLY used in 3 phase settings. Plus red is the indicator for wild legs on 120/240 3 phase

    • @Hathorr1067
      @Hathorr1067 2 месяца назад +1

      @@jeremytate3664 Nope. Red is used on single phase as well.
      Single is black-red.
      3 phase is black-red-blue.
      I have no idea what you are calling a 'wild leg'.

    • @jeremytate3664
      @jeremytate3664 2 месяца назад

      @@Hathorr1067 look it up before you make an idiot out of yourself. I live in Louisiana and have been an electrician since 2004... BLACK RED BLUE denotes 3 phase of course... I never argued that. Here in Louisiana wild legs are common on houses that have both single phase service as well as a 3 phase service to feed air conditioners. I just used this Google thing and found this. en.m.wikipedia.org/wiki/High-leg_delta Hope its informative... I learned that in other areas its denoted by orange tape.

    • @stanleywilliam
      @stanleywilliam 2 месяца назад +1

      Where in the world did you learn electrical? Blue should only be used to mark the C-phase on 3-phase 208V. If it was a wild leg 208V/240V, you would mark it with orange phasing tape.

  • @Cosigner22
    @Cosigner22 8 месяцев назад +31

    Congratulations, you bonded neutral and ground at your first means of disconnect like you're supposed to 🤷🏻‍♂️

  • @michaelbourassa2379
    @michaelbourassa2379 21 день назад

    I'm actually glad to see this. First connection which is usually the meter cam. What's the only place you bonded the neutral.. good job

    • @KevinCoop1
      @KevinCoop1 19 дней назад

      It was bonded in the electrical panel that had a 200 amp MCB, not the meter “cam”. Auto spell didn’t help.

  • @joemarchinski914
    @joemarchinski914 Месяц назад +2

    Wtf happened to having separate bus bars for neutral and ground and where do i buy the tool to both strip wire and shred the insulation prior to install

    • @johndavies2949
      @johndavies2949 22 дня назад

      You can put equipment grounds and neutrals under the same buss bar in a meter base main box. From that point on like at the distribution panel they have to be separate of one another and the neutral buss bar has to be isolated from the metal box. It usually has plastic stand offs and is factory installed.

  • @DrHarryT
    @DrHarryT 2 месяца назад +2

    ONLY in the main panel are the neutral and ground tied.

    • @JustHazardous
      @JustHazardous 2 месяца назад

      He's got a combo meter/disconnect there - it is the service disconnecting means and this is where the Grounding and Grounded conductors are bonded together. The only thing that Argoelectrical seems to have gotten right is that it is the ONE time you bond those conductors.

    • @LilMuffinTop
      @LilMuffinTop 2 месяца назад

      Your main panel is always the first point of disconnect from the meter base. This dude did a crummy job with some of his connections but that part is right.

    • @KevinCoop1
      @KevinCoop1 19 дней назад

      @@JustHazardous. You can say 100% sure without any doubt that in the NEC there is one and only location in an electrical system that neutral and ground are bonded?

  • @skootrcootr4073
    @skootrcootr4073 8 дней назад

    Ground at the meter, load side, bottom end,not the distribution panel where it can be easily moved by someone that doesn't know what they are doing.

  • @thetexan6969
    @thetexan6969 2 дня назад

    Damn man I can’t believe you posted this and thought you did a good job 😂😂

  • @RussZolotov
    @RussZolotov Месяц назад

    Bushings exist and are required to be installed before you pull the conductors specifically because of installations like this.

  • @glennbosworth1423
    @glennbosworth1423 Месяц назад +1

    You referred to the Neuteal feed as a ground.

  • @MEGAONE302
    @MEGAONE302 Месяц назад +2

    Ground has to be all green or bare to the rod.

    • @YaksAttack
      @YaksAttack Месяц назад

      Cite the code article that states that.

    • @MEGAONE302
      @MEGAONE302 Месяц назад +1

      ​@@YaksAttack Do you own work! Where does it say the insulation can be black?

  • @markhottman2652
    @markhottman2652 Месяц назад +1

    When “Red” is blue and GROUND GREEN IS white : Confusion 😮 INBOUND! 💥. What year did your… house burn 🔥 down?

  • @acalifornian6588
    @acalifornian6588 2 месяца назад

    Are you sure the neutral is the same as the ground? The neutral is the return path. The ground is the connection for leakage and emergency discharge.

  • @np5548
    @np5548 Год назад +1

    2nd year apprentice - why’d you use Noalox on copper? I was taught it was short for No Aluminum Oxidation, Al being the elemental symbol for Aluminum

    • @austinjones6964
      @austinjones6964 Год назад +3

      It might sound crazy but some inspectors want it no matter what really just depends on the jurisdiction

    • @Argoelectrical
      @Argoelectrical  Год назад +1

      I alwqays thought that to @np5548. Actually, the Lubricant says it is ok for Copper as well as Aluminum.

    • @panemon187
      @panemon187 11 месяцев назад +2

      ​@@Argoelectrical You should use Antiox for CU just as you do for AL. Especially outdoors.
      Keeping oxygen, moisture away from your conductors is very important, especially if you're using AL wire.
      Any area where there is moisture, you should use antiox coatings for bathroom, laundry room, kitchen, anywhere there is steam/moisture and an abundance of oxygen.
      People don't worry much about oxidation of copper, since it allegedly retains is conductivity in an oxidized state, but AL actually loses its conductivity in exposed areas.
      Losing that conductivity causes heat, AL wire under high load likes to expand due to heat and that expansion can loosen receptacle connections leading to arcing and fires.

    • @Argoelectrical
      @Argoelectrical  7 месяцев назад

      I actually always thought no Nolox on copper, however, it is an appropriate anti oxidant for copper wire..Read the bottle

    • @thomasmarable6818
      @thomasmarable6818 3 месяца назад

      Quit think and open a nook or read manufacturer instructions. Don't assume anything in electrical work. Don't take anybody word on what's code. Get a code book and read for yourself.

  • @rashellyohn5128
    @rashellyohn5128 24 дня назад

    Sub panel
    Thank you for your time and video.
    I have a separate panel that is not connected to the house. Its just in the yard and it powers my garage, my barn and a pump. There are 3 double pole, 60 amps each pole , breakers in this panel. For the breaker that powers the creek pump, 12 gauge wires that read 220V go down to power a creek pump. The pump was just on the ground. I have since built a pump house around it. Could i power a sm panel box with these wires and run a 220 pump and an outlet each with there own breaker? I need to plug in a heater to keep the pump from freezing in the winter.
    Thank you 🙏

    • @KevinCoop1
      @KevinCoop1 19 дней назад

      Really? #12 on a 60 amp breaker? Hmmm. Just might be a code violation. Especially since NEC very specifically states #12 is for 20 amp branch circuit, or less.

  • @lrayvick
    @lrayvick 4 месяца назад

    And in a subpanel where there is a ground bar and there is no ground i the main panel.

  • @jimmycreamer7905
    @jimmycreamer7905 5 дней назад

    I’m sure that piece of number four solid ground could have gone in plastic, actually I think it is supposed to. Jill hole in the corner of the panel come on, dude.

  • @ssaraccoii
    @ssaraccoii 18 дней назад

    He’d get dinged for the ground from the get-go. It should be in flex or conduit, with a listed fitting, not a bare wire poked through a hole drilled in the box. Jeez!

  • @Manuel-kd3zb
    @Manuel-kd3zb Год назад +3

    I have a question, does that grounding conductors could've been a smaller gauge ?

    • @Argoelectrical
      @Argoelectrical  Год назад +5

      Yes For #150 Amp Panel the Grounding Electrode could use a #8 Bare Ground Wire, A 200 Amp Panel needs a Minimum of #6. I usually go one size larger.

    • @gatsbylight4766
      @gatsbylight4766 11 месяцев назад

      @@Argoelectrical - I'm thinking that @Manuel-kd3zb was referring to the feeder ground conductor, not the grounding electrode conductor. I'm thinking he asked this because at a glance all 4 feeders do look to be the same size (though, if you look closely it appears that the feeder ground conductor 'might', 'might' be one gauge smaller). I think the ungrounded conductors are 3/0 (copper) [which means this is most likely a 200 amp rated service].

    • @gatsbylight4766
      @gatsbylight4766 11 месяцев назад

      @Manuel-kd3zb - Yes, the feeder grounding conductor (EGC) can be a smaller gauge than the ungrounded conductors [NEC 250.122].

    • @Argoelectrical
      @Argoelectrical  7 месяцев назад

      Yes This is the common practice in Residential wiring (Manufacturer set) Personally The Grounded or Neutral should be the same size as the 120volt lines@@gatsbylight4766

    • @gatsbylight4766
      @gatsbylight4766 7 месяцев назад +1

      @@Argoelectrical - I didn't mention anything about the *grounded* conductor - I was clarifying the question about the *grounding* conductor.

  • @chriskreiser87
    @chriskreiser87 19 дней назад

    Nice, didn’t want to get that last strand of your grounding conductor under the lug? Nolox on copper, who stripped those? Yikes.

  • @jameswood9764
    @jameswood9764 2 дня назад

    Need to redo

  • @KinginChrist1
    @KinginChrist1 8 месяцев назад +6

    didnt have any RED!!! kidding me? i have at LEAST 3 rolls of Red, green, white and Brown. come on at least have happily included one roll of red in the materials

  • @stepanvinnikov6024
    @stepanvinnikov6024 7 месяцев назад +16

    If I was the inspector it’s failed inspection. One strand on sbj is not inside the ground lug. Looking closely I see nicked wires from meter to panel are damaged. You pretty much created weak point. This guy is a hack. Has balls to post this online.

  • @richardyates1033
    @richardyates1033 2 месяца назад

    All strands should be under the screw.

  • @user-nn5ph4js1n
    @user-nn5ph4js1n Месяц назад

    There's a loose strand on the ground wire

  • @spicetaz
    @spicetaz Месяц назад

    Where is the main breaker?

    • @KevinCoop1
      @KevinCoop1 19 дней назад

      In the first few frames of the video, clearly shows 200 amp MCB.

    • @spicetaz
      @spicetaz 19 дней назад

      @@KevinCoop1 I do not see any 200 amp MCB.

    • @KevinCoop1
      @KevinCoop1 19 дней назад

      @@spicetaz Stop the video and set it at the beginning stopped. It is just above the text on the screen.

  • @electricalron
    @electricalron 8 месяцев назад +1

    Where’s the main disconnect?😊

    • @Argoelectrical
      @Argoelectrical  7 месяцев назад +1

      at the Top of the Buss

    • @sterlingferguson7234
      @sterlingferguson7234 3 месяца назад

      ​@Argoelectrical ... naw... the only way to shut it down is to pull the meter...

    • @KevinCoop1
      @KevinCoop1 19 дней назад

      @@sterlingferguson7234. Start the video, stop it, and slide it back to the beginning. It clearly shows a 200A MCB. Mistakes cost money!

  • @greenbudkelly2820
    @greenbudkelly2820 Месяц назад

    Home Depot was out of the big ground busses

  • @MEGAONE302
    @MEGAONE302 Месяц назад +1

    The ground wire is FFFFFFFFFFFFFFFFed....

  • @Superman-ed9rs
    @Superman-ed9rs Месяц назад

    Is the installation safe ???-

    • @whitesnxw
      @whitesnxw Месяц назад

      no it would fail inspection

  • @user-wc8lu7qd2m
    @user-wc8lu7qd2m 3 месяца назад +2

    Looks like a future lawsuit

  • @Firestarter635
    @Firestarter635 2 месяца назад

    Bonding screw?

    • @LilMuffinTop
      @LilMuffinTop 2 месяца назад

      Is it needed if there is nothing to insulate it from the can? Its an honest question because i thought the same thing but now thinking about it there is nothing separating it from the can ya know?

  • @caring-assoul_
    @caring-assoul_ Месяц назад

    I’m willing to bet those Lugnuts aren’t torqued to specification.

  • @user-im9ov9ud7m
    @user-im9ov9ud7m 2 месяца назад

    Rough pull on the load side.?!

  • @BrandonWidows
    @BrandonWidows 22 дня назад

    The second leg is gonna start a fire..

  • @coreyayers7933
    @coreyayers7933 Месяц назад

    Grounds can't be re identified, and the ground bar seems not to be a proper ground loop.

  • @montyharder3663
    @montyharder3663 Месяц назад

    It's a commercial setting with split-phase instead of 3-phase? Wow.

    • @KevinCoop1
      @KevinCoop1 19 дней назад

      Commercial Never required to be 3 phase. The size of the structure and the equipment are what determine the electrical system.

  • @caring-assoul_
    @caring-assoul_ Месяц назад

    Those conductor to lug terminations are horrible😳🤯.

  • @MichaelBrown-xb6pp
    @MichaelBrown-xb6pp 2 месяца назад

    Putting all strands in the lug is for suckers!!!

  • @Chach555
    @Chach555 Месяц назад

    The ground isn’t all under lug

  • @hunterthelord
    @hunterthelord Месяц назад

    GROUND DING! TRAILER PARK SPECIALIST NO DOUBT...

  • @tylercappadonia6973
    @tylercappadonia6973 4 месяца назад

    What is that red piece called

    • @SnareX
      @SnareX 2 месяца назад

      Blue

  • @Dallasfwguy
    @Dallasfwguy 9 месяцев назад +1

    The fact that you wouldn’t even say neutral, ground ground, ground ground ground

    • @JeffPenaify
      @JeffPenaify 8 месяцев назад +3

      in official language the “neutral” is “grounded conductor” where green is “groundING conductor”

    • @danieljuneau229
      @danieljuneau229 6 месяцев назад

      A corner grounded delta system doesn’t have a neutral wire but it has a grounded conductor. So a grounded conductor isn’t always a neutral. Also a neutral isn’t always grounded. Complete ungrounded systems exist. He could of said what the system was first and then used easier nomenclature such as “hot”, neutral, “ground”.

  • @FJBVoteTRUMP24
    @FJBVoteTRUMP24 2 месяца назад

    Wonder when his last project caught fire? 😂😂😂😂😂

  • @claytonpridgen2324
    @claytonpridgen2324 4 месяца назад

    Your copper to the ground rods needs to go to the meter base

    • @edisont.picard4112
      @edisont.picard4112 4 месяца назад

      That is up to the utility provider. Some will not allow it in their meter. But it is irrelevant because the neutral bar is continuous between the two spaces.

    • @thomasmarable6818
      @thomasmarable6818 3 месяца назад

      Per NEC in can be in the meter or the service disconnect

    • @KevinCoop1
      @KevinCoop1 19 дней назад

      @@thomasmarable6818. Utility company rules Trump NEC. Their way or “Nope, not connecting”

  • @user-nz5op6rd4u
    @user-nz5op6rd4u Месяц назад

    Man he sounds confused as he’s pointing to the burned wires

  • @michaelrowan3851
    @michaelrowan3851 17 дней назад

    Top effort for making a video. Wank work though. I’d delete it if I were you. 😂

  • @JuanLopez-zx6bc
    @JuanLopez-zx6bc Месяц назад

    Missing a Ground business

    • @KevinCoop1
      @KevinCoop1 19 дней назад

      You mean buss? Not required to have separated ones in the Main panel.

  • @alexturner893
    @alexturner893 23 дня назад

    I feel more confused then when I started the video

  • @markusallport1276
    @markusallport1276 3 месяца назад

    Why is he calling the split phase neutral a ground?

    • @thomasmarable6818
      @thomasmarable6818 3 месяца назад

      He call it the grounded conductor because that what it is. Looking up in article 100

  • @estv9598
    @estv9598 8 месяцев назад

    Separate the neutral wire with the ground wire

    • @Argoelectrical
      @Argoelectrical  7 месяцев назад +1

      incorrect

    • @estv9598
      @estv9598 7 месяцев назад +1

      @@Argoelectrical explain what is the advantage and disadvantage by separating.

    • @cletuss57
      @cletuss57 6 месяцев назад

      @@estv9598advantage of a 4-wire system: if faults develop in the line, you have a safety conductor (the EGC) that functions without parallel paths through random neutrals and grounds. Such a separate EGC will completely clear a case fault (e.g. a hot wire breaking loose and contacting a chassis) via the breaker if it’s working properly. With a three-wire system it was common to be accidentally carrying neutral current on EGCs which at times of uneven loads (across L1 & L2) can be significant. And it has been deadly on numerous occasions for example when maintenance workers are well earthed, and happen to separate a conduit or EGC and their body becomes the circuit bridge for the accidental neutral currents or when the EGC wasn’t good enough allll the way back to the panel to clear an intermittent or poor-connection case fault via the overcurrent protective device. Disadvantage of 4-wire: one more wire required. Nowadays it’s code requirement in the US to have a 4-wire system and to NEVER BOND EGC and neutral anywhere but the first point of disconnect. Usually the meter base or the Service Entrance. Not an electrician, YMMV, do your own research, not liable for any opinions given here. See Mike Holt’s grounding website.

    • @jerimymccray
      @jerimymccray 5 месяцев назад +2

      According to NEC, this is the only place where neutral and ground should be bonded.

    • @markusallport1276
      @markusallport1276 3 месяца назад

      It is a split feed neutral, and it does tie to the ground in a panel.

  • @seanforder8824
    @seanforder8824 Месяц назад

    Tell he’s a plumber

  • @polareclipse6309
    @polareclipse6309 2 месяца назад

    Nice job, but why waste time phasing the legs on a single phase service?😂

  • @kylechristie5792
    @kylechristie5792 Месяц назад

    This won't pass code in china

  • @electvolt67
    @electvolt67 7 месяцев назад

    Shoowee!

  • @joseascencio70
    @joseascencio70 Месяц назад

    Omg how many years of experience do you have you don’t do that with the ground solid 🤦🏽 going inside the panel

    • @KevinCoop1
      @KevinCoop1 19 дней назад

      Please explain your comment? Confusing!

  • @FJBVoteTRUMP24
    @FJBVoteTRUMP24 2 месяца назад +5

    Calling this guy an electrician is like calling Biden President both doing a horrible job

    • @j_m_b_1914
      @j_m_b_1914 Месяц назад

      Some asshole (always a Trump supporter) has to make everything political.

    • @KevinCoop1
      @KevinCoop1 19 дней назад

      Way better than Trumpty Dumbty who is a Convict!

  • @dblackjr52
    @dblackjr52 Месяц назад

    This guy is a perfect example of someone who shouldnt be in charge of the situation, he may have a place in the company standing in line to buy materials and leave the work to a qualified craftsman. The amount of issues on such a brand new install is astounding, even an untrained eye should be worried. What a joke.

  • @thegreenerthemeaner
    @thegreenerthemeaner 18 дней назад

    Take this down or re-label this as poor examples and terminology. In our locality, the Neutral and Ground are Bonded inside the Meter Base, not the Panel. You won't get away with not marking ALL conductors as well.

  • @user-dv7hq2nt9m
    @user-dv7hq2nt9m Месяц назад

    Bruh

  • @user-fz2lq5rx3h
    @user-fz2lq5rx3h Месяц назад

    😂😂😂😂 this is a joke, right? Right?? 😮

  • @SteeledJester
    @SteeledJester 2 месяца назад

    😳😳😳

  • @masonbeveridge
    @masonbeveridge 2 месяца назад

    Un safe won't pass inspection

  • @ginjaninja6963
    @ginjaninja6963 2 месяца назад

    I hope he doesn't have an apprentice

  • @creativecurbing
    @creativecurbing Месяц назад

    I don't know what is scarier. The job I just saw, or the fact that he is stupid enough to think it's a good job.

  • @andrewm1704
    @andrewm1704 9 дней назад

    This video should be taken down. Shows upcoming electricians what not to do

  • @jamesharrison7261
    @jamesharrison7261 Месяц назад

    So much wrong here

  • @vladimirvladimir2606
    @vladimirvladimir2606 Месяц назад

    Нихуя не понял

  • @CTLRadio
    @CTLRadio 2 месяца назад

    You sir are a butcher lol

  • @frankdiaz7571
    @frankdiaz7571 7 месяцев назад +2

    Really why is ground and neutral together to all DIY watching don’t do this hill billy crap

    • @Argoelectrical
      @Argoelectrical  7 месяцев назад +1

      1st Point of disconnect is where the Grounded and Grounding conductors are attached. Check out Service Entrance

    • @bend4236
      @bend4236 5 месяцев назад +2

      Calling it " hillbilly " while not understanding what you are talking about is hilarious. Grounding and grounded conductors are required to be bonded together at the service in the first world. What third world country are you in?

    • @John34.
      @John34. 4 месяца назад

      You are definitely not the sharpest tool in the shed. Neutrals and grounds are bonded at the first means of disconnect.

  • @Ginajenns
    @Ginajenns Месяц назад

    Please delete this

  • @robertwasson9295
    @robertwasson9295 3 месяца назад

    🤮

  • @kevinmaldonado982
    @kevinmaldonado982 День назад

    Terrible phasing looks like halfass work and its called x o bonding genius