Water Load Accident ❌ Big Generator Load Trial 1010KVA | 4K

Поделиться
HTML-код
  • Опубликовано: 24 ноя 2024

Комментарии • 50

  • @eduardosanchez7827
    @eduardosanchez7827 4 месяца назад +3

    I appreciate greatly this kind of video showing the dangers of such maneuver. I’m not criticizing at all, actually this shows that the whole operation must be carried with more precautions. Thank you so much for posting this 👍🏻. Most people only show how to do it but it’s important to also address the possible problems. Thanks again from Mexico! 🇲🇽

    • @surajdieselgenerator
      @surajdieselgenerator  4 месяца назад

      @@eduardosanchez7827 Thank you for understanding our motive to upload the video. 😊

  • @PortableGeneratorServices
    @PortableGeneratorServices 10 месяцев назад +9

    That blue tank is maybe large enough for a 15kw unit for a short time.
    You do not want the water boiling like that. With the water boiling like shown the plates can not stay 100% in contact with the water. The water is being blown away from the plates due to the boiling. Boiling allows air pockets Resulting in the fluctuating amperage.
    Salt is not necessary if the tank is large enough. I did 2 such load bank jobs in a fresh water river.
    Never remove the plates until the breaker is opened.
    The separation of the plates needs to be much greater - we separated our plates about 16”.
    Whoever was in charge should be fired - very dangerous setup.

    • @surajdieselgenerator
      @surajdieselgenerator  10 месяцев назад +2

      I appreciate your review. But the salt here is used to Check the load on instant. The mistake here happened was. While we were not available our 1 engineer put salt on the Backalite. And that salt didn’t dissolved. You might hai seen dropping salt many times. That’s because we have changed water and added fresh water again. My motive here of uploading video was. In india this technique is used since 1990s. I want to teach our brothers that these kind of accidents can take place.
      Thank you 😊

    • @JPcostarica27
      @JPcostarica27 9 месяцев назад +1

      Is ok that plates are in line? I mean, should they be placed forming a triangle to guarantee a load balanced?

    • @PortableGeneratorServices
      @PortableGeneratorServices 9 месяцев назад

      @@JPcostarica27 for a resistive load not needed

    • @galponeroserial
      @galponeroserial 4 месяца назад

      There is no risk of electrolysis products to be released creating a near explosive atmosphere?

  • @billmoran3812
    @billmoran3812 10 месяцев назад +8

    That drum is way too small for the kind of power being dissipated. Way too much salt too.
    Boiling that hard will further concentrate the salt causing a runaway condition. Essentially that’s what happened when they pulled the electrodes out. Very salty water dripping off close spaced electrodes caused the arcing. Extremely dangerous.
    They need a tank of water about 10 times larger for a generator that size. And much bigger electrodes spaced at least 2-3 feet apart.

    • @surajdieselgenerator
      @surajdieselgenerator  10 месяцев назад

      Actually the problem occur was due to our engineer put salt on the backalite. It should have been properly dissolved in the water. That salt did the spark

  • @zs6vl
    @zs6vl 8 месяцев назад +11

    Those guys are a walking accident.

    • @surajdieselgenerator
      @surajdieselgenerator  8 месяцев назад +3

      Dude. Get a life. We are doing much better than you. Go and work.

    • @ghostcrusher5169
      @ghostcrusher5169 8 месяцев назад

      @@surajdieselgenerator I agree with you

    • @ghostcrusher5169
      @ghostcrusher5169 8 месяцев назад

      Look at urself before commenting

  • @teresashinkansen9402
    @teresashinkansen9402 7 месяцев назад +2

    480VX421A=202kW If that water barrel holds 190L at 20C° that means it will reach 100C° in about 5 minutes or about 1 minute at full power. That water resistor is way undersized. Also do not take out the electrodes with power on! that's why such thing happened.

    • @surajdieselgenerator
      @surajdieselgenerator  7 месяцев назад +1

      Basically the load varies.
      But the calculations you gave is top notch.
      We will consider it.

    • @tjc-gaby9687
      @tjc-gaby9687 6 месяцев назад

      480v ou 400v ?

  • @sree6127
    @sree6127 7 месяцев назад +5

    No safety

  • @alisaad4913
    @alisaad4913 11 месяцев назад +13

    Hello bhai generator safe hai na

  • @argosy440
    @argosy440 7 месяцев назад +1

    What happens when it arcs like that? Does the generator automatically switch off?

    • @surajdieselgenerator
      @surajdieselgenerator  7 месяцев назад +1

      If the ACB breaker contains Earth Fault Relay.
      The Breaker will shut down.
      But Generator won’t stop you have to stop it.

  • @unknowncoder2037
    @unknowncoder2037 9 месяцев назад +1

    Sir kya bliss ka jo engine ata tha kirloskar electric dg set me bo engine achha hei long lasting hoga plz help kijiye mujhe me kharidna chata hun ek admi se isiliye ouch raha hunn engine kesa hei alternotr kesa hei 62 kva ka dg set hei plz reply

    • @surajdieselgenerator
      @surajdieselgenerator  9 месяцев назад

      Aap whatsapp kijiye photos. Ham bata denge uski condition
      +919033353459

  • @ghostcrusher5169
    @ghostcrusher5169 10 месяцев назад +2

    Is this Cummins Genset?

  • @sahilrathod1684
    @sahilrathod1684 3 месяца назад

    125 kv price ?
    Adressss

  • @sahilshaikh6290
    @sahilshaikh6290 9 месяцев назад +4

    Mccb trip huva ki nahi

  • @bigmuller1
    @bigmuller1 11 месяцев назад +5

    That is not a good way to do a load test

    • @surajdieselgenerator
      @surajdieselgenerator  11 месяцев назад +1

      Yes we know. But the load banks are way too costlier to purchase and to maintain. So we have this alternative. Which is risky. But the footage you saw is rare of rare incidents happened.

    • @urboydexter
      @urboydexter 10 месяцев назад +1

      ​@@surajdieselgenerator so do you guys plan to get the one which is safe

    • @surajdieselgenerator
      @surajdieselgenerator  10 месяцев назад

      @@urboydexter Yes we are planning to make one instead of buying.

  • @nothing12299
    @nothing12299 6 месяцев назад

    V16 turbocharged?

    • @surajdieselgenerator
      @surajdieselgenerator  6 месяцев назад +1

      Yes. V16 Turbocharged
      3067 Litres of displacement.

    • @nothing12299
      @nothing12299 6 месяцев назад

      @@surajdieselgenerator ok thanks for the information

  • @vikrammalviya7917
    @vikrammalviya7917 Год назад +4

    Sir esa ku hogya.

    • @surajdieselgenerator
      @surajdieselgenerator  Год назад +4

      Excessive Salt Use ho gaya. Salt dalne wale ne Salt ko paani me nhi milaya. Usse BAKALITE me blast ho gaya. Or Load Bank Pighal gaya

    • @vikrammalviya7917
      @vikrammalviya7917 Год назад +3

      @@surajdieselgenerator sir i really appreciate your work and your response 👍👍

    • @surajdieselgenerator
      @surajdieselgenerator  Год назад +3

      @@vikrammalviya7917 thank you 😊

  • @patel6228
    @patel6228 Год назад +2

    😱

  • @scua2646
    @scua2646 3 месяца назад

    👍

  • @wiltonsurya4600
    @wiltonsurya4600 6 месяцев назад +2

    too much salt