Assalamualaikum apki ye video boht achi hai , brother 1 request hai plz kisi bhi packeg unit ko le k video bna dien k bnda wiring diagram sath mn rekh k kesy tracing kry 1 ,1 cheez but control wiring diagram k sath to so that wiring diagram perhna seekh skien video ko dekh k
Bhai need to be checked something Like Loose connection check karo control ka wire fully tight or not V belt bhi check karo tight ok Or not Standing pressure and actual pressure compressor Blower rated amps and actual amps Duct bhi kya Naya hain? Dusra duct main damper laga Hai kya? Agar laga hai tou damper check Karo fully open ho raha hain ki nhi
Bhai agar error code FL dikha raha tou Uske reason ye hain wo ya tou LP YA HP Switch se trip kiya hai agar PCBs board light slowly blinking kare tou wo lp switch se tripping huwa Aur fast blinking kare hp switch se trip huwa Aur lp mein agar trip huwa ho tou Check karo Freon pressure Lp switch Air filter Cooling coil V belt loose or damage And dumper Anti ice switch Hp switch Condenser motor Condenser coil dirt Loose wiring Condenser motor contactor Stuck Motor jammed
Bhai Agar compressor on nhi ho rha hai Tou kuch sahi ho sakta hai lekin Sab kuch sahi nhi ho sakta hai Agar sab sahi hoga to compressor On ho jyega, agar on nhi ho rha hai to Reason jarur hai, Sabse pehle c & g C & y1 C & Y2 mein voltage check Karo, 24 dikhana Chahiye aur abhi ketna dikha rha hai? Gas standing pressure ketna hain?
Bro Agar transformer ke 🔴 red wire mein 220 nhi dikha raha hai tou sabse phle Sab Phases voltage karo ⚡️aur phase Neutral mein bhi voltage⚡️ check kro Agar UVM ko bhi check karo,
Bhai zamil ke kuch unit mein solenoid valve hota hai aur kuch unit mein nhi hota hai lekin agar solenoid valve ho tou pcb board main solenoid valve ka ek wire pcb main P1 main lagao system one ke liye lagao aur solenoid valve system 2 ke liye Pcb main P2 main ek wire lagao Aur dono systems solenoid valve ka dusra wire unit ATB terminal 2 main laga do, laikin solenoid valve 220 voltage coil hona chahiye
Bhai sabse phale C aur G main voltage⚡️ check karo 24 dhik Hana chahiye agar dhika raha phir nhi blower nhi on ho rha hai tou blower contactor ka over load reset karo aur check karo aur ampere bhi check karo kyu over load se trip, Aur agar 24 voltage nhi dikha rha tou C aur G main phir ek single wire jumper Karo R aur G main sirf testing ke liye agar on ho gya tou phir thermostat main ya thermostat wire ka ya thermostat setting ka problem hoga Main
@@MahtabAlam-mp8xn Dear Bro , blower contactor ke auxiliary main wires number 48 aur 49 blower run for BMS indication ke liye used hota aur compressor contactor ke auxiliary main wires number 55 aur 56 compressor number 1 run for BMS indication ke liye used hota
@@MahtabAlam-mp8xn Bhai zamil unit ka jo wiring 4 se 5 tarika hota hain same same model hoga likha hoga laikin wiring thora bahut fark hoga Kyu kuch unit mein SSPS hota hain kuch mai nhi kuch mai FCS used hota hain kuch mai nhi kuch mai anti ice used hote hai kuch mai nhi aur kisi bhi unit agar koi terminal mein wire double laga ho tou phale bhai check karna hoga ki wo wire kyu aur kis liye lagaya hai,,, Aur is ac mein jo double wire laga hai neutral terminal in the pcb board main agar wo hata de PCBs se tou koi unit ko problem nhi hoga unit theek se run karenga
Bhai Zamil's package and all these models have no such switch yet to control both compressors But if there are two compressors in the system and not much cooling is required, then temperature from thermostat increase it & second compressor number two If the compressor is not to be run, the wire terminal of Y2 exit
@@HVACAMJADTROUBLESHOOT 4 compressor wala package unit ha 3 compressor on hota ha ik nhi ho rha sub kuch check kiya cammand bhi a rhi ha conctor push krne se on ho rha ha compressor
@@tahirgujjar7476 Bhai sabse phale pura wiring ko loose connection check karo aur tight karo phir on karke check karo agar same problem hain tou phir LP aur HP ko direct karo sirf testing ke liye phir check karo phir bhi same ho tou compressor contactor ka over load direct karo sirf testing ke liye Then on the unit and check the performance
Brother i have one doubt last 3 three same model skm package unit same pcb board after cutoff again not start unit what problem can you explain brother please can you send whats app number
Bro Even if there is a problem in the package unit zamil or SKM and like this then some things must be checked like loose connection, LP HP switch, gas pressure, air filter clean or not, V Belt tight or loose and air return duct dumper fully open or not brother if you have any question you will get answer i getting too many messages by what's aap and phone calls and it is difficult to answer them all at once? And I have too much work load pressure right now
Jaise aap video me samjate h bahut hi kaamal ka video lagta bahut kuch sekhne ko milta h
Alhumdolilah & thanks for the liking my video bro
Bahut hi achhi jankari di hai apne, shukriya
Thank you too bro
@@HVACAMJADTROUBLESHOOT welcome sir
bhai ap video me bhot accha samjhte hai
Alhamdulillah rabb al alamin 🤲🤲
& shukran for liking my video bro 👍
my Bangladesh se ho🇧🇩 very clear explanation
thank you so much sir ❤
You are most welcome and shukran
Compressor contrecter over load ki wairing ki vedeo banaw
ruclips.net/user/shortsPrWSO_MXedw?si=g04IgY1jrRZhexjl
ruclips.net/video/NlLcFT5iphc/видео.htmlsi=jOjOeq6eC4PLB4K2
Aap jab tak ye video dekho
Main insa allah video banayege
Thank you vary helpful & informatic video
Thank you too brother
Best of luck bhai
Great sir ji 👍❤❤
Thank
Good explanation
Thanks for liking
Good explain bhai
Thank bro
Sukriya sir jes❤
Ek number bhaijaan love u
Ok and thanks bro
Nice
Very nice
Thanks
Very nice explained..
Nice video ❤
Thanks 🤗
Masha Allah bhaijaan ❤❤❤❤
Great job Sir ji 👍
Dear you too
Nice Brother
thank bro
Thank you so much very clear explain ❤
thank you too bro
اسلام علیکم ۔مھربانی
Walaikum salam jnab
Assalamualaikum apki ye video boht achi hai , brother 1 request hai plz kisi bhi packeg unit ko le k video bna dien k bnda wiring diagram sath mn rekh k kesy tracing kry 1 ,1 cheez but control wiring diagram k sath to so that wiring diagram perhna seekh skien video ko dekh k
Walaikum Salam wr wb bhai
OK jnab 👍 & thanks for liking my video bro
face book group name
for HVAC knowledge 📚
AC TECHNICIAN GULF
facebook.com/groups/134091166017387/?ref=share
Thanks brother 👍
You're welcome bro
Hii make one video zamil slave board how is chang setting
❤❤❤
👍👍❤️❤️💯👍❤️❤️
HVAC
Hl lowvol bor wre loose no selft ee wire cilp putther ok goodsheringallhigh low voltwire cilp very power passinv loose all cmpnet dsmges card fully
Iove you ustad g....
Dear you too
Bahi mujhe AC ka Kam Aata Hai overtime Karna Hai 9am se 5pm tak Kam hai HVAC ka full waring Aata hai
Good job Dada
Thank you very much
Sir ac panel terminal ka video banaiye
Ok dear and thanks for your suggestions
Sir NO and NC per ek video please
Ok bro
Skm ka package unit ha low pressure ma trip hota ha gas ok solnit vole ok drier filter ok exp vole ok .new ac ha
Bhai need to be checked something
Like
Loose connection check karo control ka wire fully tight or not
V belt bhi check karo tight ok
Or not
Standing pressure and actual pressure compressor
Blower rated amps and actual amps
Duct bhi kya Naya hain?
Dusra duct main damper laga
Hai kya?
Agar laga hai tou damper check
Karo fully open ho raha hain ki nhi
Bhai aap ne uvm ki wiring nahi bataya plz bataye
Bhai Please watch this video,
ruclips.net/video/fTGBnWTFd0o/видео.htmlsi=lqEVD-Lz2RiaUIji
ruclips.net/video/UBvluHxU8Gk/видео.htmlsi=LInCzCmrdr7IalKw
Aur baad main saprate video banayege
Zamil Chiller ka code bataye
Sir zamil package AC Mai FL error arah hay iska opuar AK video banaiye sir
Bhai agar error code FL dikha raha tou
Uske reason ye hain wo ya tou LP YA HP
Switch se trip kiya hai
agar PCBs board light slowly blinking kare tou wo lp switch se tripping huwa
Aur fast blinking kare hp switch se trip huwa
Aur lp mein agar trip huwa ho tou
Check karo
Freon pressure
Lp switch
Air filter
Cooling coil
V belt loose or damage
And dumper
Anti ice switch
Hp switch
Condenser motor
Condenser coil dirt
Loose wiring
Condenser motor contactor
Stuck
Motor jammed
@@HVACAMJADTROUBLESHOOT Thank you sir ❤❤❤
AC compressor Nahin chal raha hai sab Kuchh sahi hai
Bhai
Agar compressor on nhi ho rha hai
Tou kuch sahi ho sakta hai lekin
Sab kuch sahi nhi ho sakta hai
Agar sab sahi hoga to compressor
On ho jyega, agar on nhi ho rha hai to
Reason jarur hai,
Sabse pehle
c & g
C & y1
C & Y2
mein voltage check Karo, 24 dikhana
Chahiye aur abhi ketna dikha rha hai?
Gas standing pressure ketna hain?
Vai jan tharmostat ka connection kahun se o tho nahi bataya
Bro aapka sawal ka
Main kuch baat samjha aur kuch nhi
Vmc ke cnecsion nahi bataye sir
Ok 👌 bro is par video banayenge
Solo night ko pawar kaha se jata h
Please bro watch this video
ruclips.net/video/Got8DfUGzoQ/видео.htmlsi=IuI52lBos2ug70HV
X1 aur x2 kis liye hota hai pcb me
Jab system Tripping hone par
BMS trip indication ke liye
Org light bilar kri he kya problam he sir
Bhai iske ye sab waja hone se
Light 💡blinking hota hai
1, loose wiring
2,less freon or low freon
3, belt loose
4, filter dirt
5,pcb board
@@HVACAMJADTROUBLESHOOT thanks
@@AbrarAhmad-sx7iq
welcome bhai
Sir transformed me 220v in nahi horay, yani cercit me 220v nahi arayh.,thermostat me current nahi aray,kya muskin ho saktahe
Bro
Agar transformer ke 🔴 red wire mein 220 nhi dikha raha hai tou sabse phle
Sab Phases voltage karo ⚡️aur phase
Neutral mein bhi voltage⚡️ check kro
Agar UVM ko bhi check karo,
Bhai lock code bhi batiyega
Ok 👌bro
Zamil cassat a/c ka remote mobile may Kay say download karn plz batayn
Sir is me solinoid valve Ka connection nhi hai
Bhai zamil ke kuch unit mein solenoid valve hota hai aur kuch unit mein nhi hota hai lekin
agar solenoid valve ho tou pcb board main solenoid valve ka ek wire pcb main P1 main lagao system one ke liye lagao aur solenoid valve system 2 ke liye
Pcb main P2 main ek wire lagao
Aur dono systems solenoid valve ka dusra wire unit ATB terminal 2 main laga do, laikin solenoid valve 220 voltage coil hona chahiye
Lp or hp kharab ho Gaya ho to bypass kaise kare zamil AC m
Video banayenge bhai laikin
Lp aur hp ko sirf testing karne ke liye
Hi bypass karen,
Sir zamil ka package unit hai uska blower motor nhi chal rha jab contector push krta hu tab chalta
Bhai sabse phale C aur G main voltage⚡️ check karo 24 dhik Hana chahiye agar dhika raha phir nhi blower nhi on ho rha hai tou blower contactor ka over load reset karo aur check karo aur ampere
bhi check karo kyu over load se trip,
Aur agar 24 voltage nhi dikha rha tou
C aur G main phir ek single wire jumper
Karo R aur G main sirf testing ke liye agar on ho gya tou phir thermostat main ya thermostat wire ka ya thermostat setting ka problem hoga
Main
No / nc ka btao bhai
ruclips.net/video/sn0_N7phkgM/видео.htmlsi=0BkU38sCOPqdU7lx
ruclips.net/video/NlLcFT5iphc/видео.htmlsi=yqwMc77dm2-SsUyC
Aap ye video dekho
Compressors Contector coil / control 24v L N wire ke alawa baju me 3rd ek wire dikh raha hai wo kaisa wire hai ?
Wire cod 48 hai jo blower contector par laga hai wase hi compressors contector par bhi laga hai please us wire ke bare me batayen
bhai pch Neutral point mein two wires used kiya hain
@@MahtabAlam-mp8xn
Dear Bro ,
blower contactor ke auxiliary main
wires number 48 aur 49 blower run for BMS indication ke liye used hota
aur compressor contactor ke auxiliary main wires number 55 aur 56 compressor number 1 run for BMS indication ke liye used hota
Kya us wire ke na hone par contector chalu ho sakta hai ya wo wire pcb/transformer se series me hai ?
@@MahtabAlam-mp8xn
Bhai zamil unit ka jo wiring 4 se 5 tarika hota hain same same model hoga likha hoga laikin wiring thora bahut fark hoga
Kyu kuch unit mein SSPS hota hain kuch mai nhi kuch mai FCS used hota hain kuch mai nhi kuch mai anti ice used hote hai kuch mai nhi aur kisi bhi unit agar koi terminal mein wire double laga ho tou phale bhai check karna hoga ki wo wire kyu aur kis liye lagaya hai,,,
Aur is ac mein jo double wire laga hai neutral terminal in the pcb board main agar wo hata de PCBs se tou koi unit ko problem nhi hoga unit theek se run karenga
W1 ky h
W1 yani
Jaise Y1 hota hain cooling ke liye
Waise he W1 heater ke liye
Thermostat se demand ataa hai
Heater contactor ko on karne ke liye
Bhaya
P1 & P2 kis liye hai
P1, Solenoid Valve for
System One
P2, solenoid valve for
system 2
In Dx unit there's not any system switch, one unit is running and second one on the rest why?
CMY 300 FDAA
Bhai
Zamil's package and all these models have no such switch yet to control both compressors But if there are two compressors in the system and not much cooling is required, then
temperature from thermostat
increase it & second compressor
number two If the compressor is not
to be run, the wire terminal of Y2 exit
@@HVACAMJADTROUBLESHOOT
I exited Y1 but Y2 isn't switch on in after 5 minutes ?
@@MuhammadNadeem-vc7zy
take out Y2
Kindly tell me about dip switch position.
CMY 300 system are lead or lag automatically?
Assalamualaikum bhai jaan aapna no dege please
Walaikum Salam wr wb bhai
ruclips.net/video/GFpMfWUeTZ4/видео.htmlsi=V7ZQOSNqS9-chuWU
Mere under big zamil units ha us ki bhi ik video bna do.
Ok 👌
Aapke site main kuan sa model ka unit hain please batao
@@HVACAMJADTROUBLESHOOT 4 compressor wla
@@HVACAMJADTROUBLESHOOT 4 compressor wala package unit ha 3 compressor on hota ha ik nhi ho rha sub kuch check kiya cammand bhi a rhi ha conctor push krne se on ho rha ha compressor
@@tahirgujjar7476
Bhai sabse phale pura wiring ko loose connection check karo aur tight karo phir on karke check karo agar same problem hain tou phir LP aur HP ko direct karo sirf testing ke liye phir check karo phir bhi same ho tou compressor contactor ka over load direct karo sirf testing ke liye
Then on the unit and check the performance
@@tahirgujjar7476
Ok 👌
Brother i have one doubt last 3 three same model skm package unit same pcb board after cutoff again not start unit what problem can you explain brother please can you send whats app number
Bro
Even if there is a problem in the package unit zamil or SKM and like this then some things must be checked
like loose connection, LP HP switch, gas pressure, air filter
clean or not, V Belt tight or loose and air return duct dumper fully open or not
brother if you have any question you will get answer
i getting too many messages by what's aap and phone calls and it is difficult to answer them all at once?
And I have too much work load pressure right now