Hi, do you know how can I make test plans for 21 relay. I want to test impedance boundary and impedance - time, with selection by the user of the type of test methodology, constant voltage, constant current and constant source impedance?
can I have help I want to know that what is the difference between delay time of a relay and operation time and also the relationship between pick up current and delay time
Actually I have been able to do this. As long as you can physically get your hands on the CT (ie: not on a bushing). Apply Voltage on the CT secondary X1-X5. So if you have a 1200/5 (240/1) CT, Apply say 120V from X1-X5. You should read 0.5 Volts on the CT Primary. This verifies your CT Turns Ratio without stressing the F6150.
with regards to relay manufacturer it is okay if it just generic differential relay, what I was after is that the test plan with regards to delta wye transformer, I am not sure how to make the settings in the compensation page, I am not sure with the idea. The manual did not provide much info. Can you discuss that part?
can you make a video about differential test using F6150? thanks..
Thank you for the tutorial it was very helpful!
Hi, do you know how can I make test plans for 21 relay. I want to test impedance boundary and impedance - time, with selection by the user of the type of test methodology, constant voltage, constant current and constant source impedance?
can I have help I want to know that what is the difference between delay time of a relay and operation time and also the relationship between pick up current and delay time
Can we use this F6150 Power System simulators for Ratio testing of the Current transformer?
lok chand no,, the burden of CT is high and the test set will not be able to inject the required current
You will damage the test set
Actually I have been able to do this. As long as you can physically get your hands on the CT (ie: not on a bushing). Apply Voltage on the CT secondary X1-X5. So if you have a 1200/5 (240/1) CT, Apply say 120V from X1-X5. You should read 0.5 Volts on the CT Primary. This verifies your CT Turns Ratio without stressing the F6150.
Sure, do you want it for any specific make ?
Thanks sir 👍
with regards to relay manufacturer it is okay if it just generic differential relay, what I was after is that the test plan with regards to delta wye transformer, I am not sure how to make the settings in the compensation page, I am not sure with the idea. The manual did not provide much info. Can you discuss that part?
TheSurgeArrester check the Rio file converter
any updates with regards to the video?
Hi. Thank you for this video. Do you can share your database with all test plans with me? I don't have a database.
The database is large
It would go thru whatsapp
How to make ramp test
Ramp for voltage or current ?
Any one have doble
sent a PM
off late i got too busy ,,, i will make the the video sometime in this month.. regards