CEC 2018-Section 62: Hot Water Tank Calculations

Поделиться
HTML-код
  • Опубликовано: 19 ноя 2024

Комментарии • 5

  • @mrsamba8151
    @mrsamba8151 Месяц назад

    Hi Deanna. Could you tell us how to do a service load calculation for an electric hot water boiler, please?

  • @abouzarfallah7012
    @abouzarfallah7012 7 месяцев назад +1

    For hot water tank many electrician follows section 8 and consider it as continuous load and derate both breaker and cable by 1.25.

  • @sbitschy
    @sbitschy Год назад

    Love your videos. Thank you.

  • @darnellbourassa1081
    @darnellbourassa1081 3 года назад +1

    Where do you get the 1.25 factor?

    • @asterelectric
      @asterelectric 2 года назад +1

      Rule 8-200(1)(a)(iii) takes you to section 62, because hot water tank is considered a fixed electric heating system. (See Rule 62-000 Scope and its Appendix B.)
      And the 1.25 factor is based on Rule 62-114(6)(b), which says:The load shall not exceed 80% of overcurrent protection device rating.