DG are normally limited in capacity, hence as a power source with a leading pf, are not advisable to have a directly connected capacitor bank…. A directly connected capacitor bank will immediately bring an over unity power factor to the DG which will trigger it to self-destruct by losing the voltage specially in unloaded conditions.. It is more preferred for a DG to have a lagging pf for a more reliable operation…typically around 0.8 pf for a more reliable operation… A DG being a limited capacity power source, any planned power factor corrections is switch on and off together with the load.... DG set output is often distorted and full of harmonics. These can cause harm to capacitors.DG set cannot take even light capacitive load, if this happens by chance.Load on DG can vary quite frequently, and capacitor bank cannot control it on continuous basis.Usually DG sers themselves are quite small in capacity, and capacitor bank is of not much use.
दोस्त आपकी सभी विडियो बड़ी💥 आसानी से समझ मे आता है इसके लिए आपके धन्यवाद मै प्रतिदिन आपका विडियो💥 देख रहा हूँ आपका गूगल साईट💥 भी विजिट करता हूँ लेकिन बहुत दिनो से आपसे रिक्वेस्ट कर रहा हूँ कि आप इलेक्ट्रिक्ल HV, LV पैनल, कन्ट्रोल पैनल, और इनके टेस्टिंग के ऊपर विडीयो अगर संभव हो तो बनाईये💥💥💥🙏🙏🙏
Very nice and soo motivation for learning .this channel is very very amazing, enjoyable,and very very useful for learning.and bro your voice and teach strategy is also good and nice.well done bro.good job bro.
With lesser power factor say 60% Load Power factor = 0.6
DG rating in kVA = 1000 Load in kW = 500 Load kVA is required = 500/0.6 = 833.33
% of DG utilization = 83.33 With improved power factor using APFC say 85% Load Power factor = 0.9 DG rating in kVA = 1000 Load in kW = 500 Load kVA is = 500/0.9 = 555.56 % of DG utilization = 55.55 From the above it is clear that when power factor is improved the DG utilization for defined load say 500 kW is less and the burden on DG is reduced compared to the unimproved power factor. So isn't that good to connect APFC and maintain PF close to 90 to 95%? Can you pls explain what would be case if we connect a load of 750 kW with 0.6 PF, will the DG supply load current? Also one small suggestion instead of using 'KVA' pls use 'kVA'.
Following are my Questions Regarding Capacitors on DG. We connect individual Capacitors near the Inductive Load only & we turn it on when the load is on. And when the load stops, the capacitor also shuts off. In this case following scene creat... 1) Capacitors leading current will cancelled the Inductive load current, & capacitors leading current doesn't move to DG Alternator. 2) We can save the Fuel consumption 4-5%. 3) Voltage regulation also good.
1. Ye batao capacitor ko add karne par load 800kw se 1000 kw kaise ho jayega 2. And ham 800 kw load fix hai to capacitor laga ke power factor improve kar rahe hai to kya nuksan hoga kyonki hamare equipment se bhi to power factor kam hota hai kewal alternator me hi loss to nhi hai na.?
Sir mai ek stadium me mentanance ka job karta but os me jo tower light hai os me 2000watt ka single phase balb laga hai osko ham dg se opret kaise karenge keny k oska chock ignetar hai os k sath capiceter v laga hua hai espe thora bataye sir
Sir yaha kaam karne ke jagah transmission ka power bandh hote he hamari DG chalu hota hai magar hamara capacitor bank band nahi hota hai is se hamara DG ko kuch effect hota hai pls sir toda bataye
Double fed induction generator working explain plz....WIND TURBINE me use hota hai... Aisa....pls.... nhi smj aata... Ye topic pe 30mim ka video bana do detail mai
Sir mera sawal ye h ki normal dg gharo me upyog ki jane wali dg1000 1500kva ki ho sakti h aur agar ye 1000 Kva hoke 800 Pe Chalta h to hmare gao me laga tarsformar mat63 ya 100 kva ki ho ke itna lod kyse leti h
In DG sets, role of AVR is to maintain voltage of tha alternator. Now how it maintains Voltage of Alternator??... By varying DC Excitation Voltage and current of the Excitation windings of an alternator.....But, by varying the voltage of excitation field windings, Power factor also changes...This means role of AVR is not only to maintain Voltage, but Power factor also.. Now, what will happen if we Connect power factor improvement devices??.. There will be ambiguity between AVR and APFC..
दोस्तो हमारे इस नए चैनल को भी एक बार आप जरूर चेक करे। कुछ दिनों के अंदर मैं रोजाना यहाँ पर भी इलेक्ट्रिकल से जुड़ी वीडियो अपलोड करूँगा।
ruclips.net/channel/UCF9cJahy23HDhxiB2Lf6KRg
bhai mene camment kari he dheko or us par video banao
Thanks Bhai😊
जरूर भाई
जरूर भाई 💥🙏
Ok
Sir aap best ho...i wish collge mai bhi ase teacher ho to job milne ki tnsn na rhe👏😊😊
Job 😂😂😂 small minds
Thanks sir aapke video dekh k maine bahut sikha aur mera salection ho gya interview me pas ho gya
Bahi am Form Pakistan you're great & good instructor
Behtar jankari lagi aur aise video banaen
Very very nice sir jee bahut achha samjhane ka tarika hai sir jee
Bahut hi achha knowledge bhai
sahi jankari dete ho bhai thanks
Thank you Boss ☺️
Itna easy koan smjata h bhai awesome bhai
Very Useful Information.... superb sir
वीडियों बहुत ही अच्छा था
DG are normally limited in capacity, hence as a power source with a leading pf, are not advisable to have a directly connected capacitor bank…. A directly connected capacitor bank will immediately bring an over unity power factor to the DG which will trigger it to self-destruct by losing the voltage specially in unloaded conditions..
It is more preferred for a DG to have a lagging pf for a more reliable operation…typically around 0.8 pf for a more reliable operation…
A DG being a limited capacity power source, any planned power factor corrections is switch on and off together with the load....
DG set output is often distorted and full of harmonics. These can cause harm to capacitors.DG set cannot take even light capacitive load, if this happens by chance.Load on DG can vary quite frequently, and capacitor bank cannot control it on continuous basis.Usually DG sers themselves are quite small in capacity, and capacitor bank is of not much use.
Do we have any rules and regulations in place for this situation?
Great Great Great ATTITUDE Great superb superb.
Bahot acchi bat batai Bhai
Ek video relay settings par bhi Bana dijiye
Dost aapki video bahut achi hoti hai thanks dg ki neutral ko earth kyo kya jata hai please answer
दोस्त आपकी सभी विडियो बड़ी💥 आसानी से समझ मे आता है इसके लिए आपके धन्यवाद मै प्रतिदिन आपका विडियो💥 देख रहा हूँ आपका गूगल साईट💥 भी विजिट करता हूँ लेकिन बहुत दिनो से आपसे रिक्वेस्ट कर रहा हूँ कि आप इलेक्ट्रिक्ल HV, LV पैनल, कन्ट्रोल पैनल, और इनके टेस्टिंग के ऊपर विडीयो अगर संभव हो तो बनाईये💥💥💥🙏🙏🙏
You are the best sir
Very nice and soo motivation for learning .this channel is very very amazing, enjoyable,and very very useful for learning.and bro your voice and teach strategy is also good and nice.well done bro.good job bro.
Solid information mila....
All doubt clear ..thank u sir
Bahut acha lgaa
Supar work sir.
Very useful video sir
Excellent video👌
Thanks sir 👍👍 have a great day
Useful for electrical student
Good knowledge
Achha concept h
Thank you
Good job Dost
Nice video sir jee
AVR BOX mai kya lagate hai aur vo kaise work karts hai
DJ ki information very helf full
SUPERB VIDEO
Nice Dear great
Very good sir
Good sirjee .thank you
Good explain 👌👍
Nice explanation sir.!!
Thank you Karan Ji ☺️🙏
Mast video
Agr 1000kva main 800kw load daal sakte hain. To with capacitor bank agr usme 800kw hi load dalu toh ?
Good post
sir ek din pahle yeh vdo dekhta to interview pas hota
Very very nice
Always super...Sir aapne mere massage pr video nhi banayii.?
Very very thanks sir
Bilkul sahi hai
Nice info
Good sir...
V good vedio, Thank u
Good one
Thank you sir🙏
Shukriya NiTika Ji ☺️🙏
@@electricaldost sir you are awesome 👌
I had made notes of your all videos and I revise it each day.
Thank you for sharing your knowledge with us.🙏🙏🙏🙏
U r great bro
Formule pr video ek bana dijiye
Jisme saare kw kvr kva convert karma ho
With lesser power factor say 60%
Load Power factor = 0.6
DG rating in kVA = 1000
Load in kW = 500
Load kVA is required = 500/0.6 = 833.33
% of DG utilization = 83.33
With improved power factor using APFC say 85%
Load Power factor = 0.9
DG rating in kVA = 1000
Load in kW = 500
Load kVA is = 500/0.9 = 555.56
% of DG utilization = 55.55
From the above it is clear that when power factor is improved the DG utilization for defined load say 500 kW is less and the burden on DG is reduced compared to the unimproved power factor. So isn't that good to connect APFC and maintain PF close to 90 to 95%?
Can you pls explain what would be case if we connect a load of 750 kW with 0.6 PF, will the DG supply load current?
Also one small suggestion instead of using 'KVA' pls use 'kVA'.
Very good
Following are my Questions Regarding Capacitors on DG.
We connect individual Capacitors near the Inductive Load only & we turn it on when the load is on. And when the load stops, the capacitor also shuts off. In this case following scene creat...
1) Capacitors leading current will cancelled the Inductive load current, & capacitors leading current doesn't move to DG Alternator.
2) We can save the Fuel consumption 4-5%.
3) Voltage regulation also good.
I feel same too but we can't increase much load by seeing ampere coming down bcz of capacitors
Good sir DG se sambandh it puri knowledge pr video banao please
Best answer
Really helpful
Nice video
Please make video about ac generator
Capacitor se Reverse power generate hoti hay.
So excitation loss hoti hay.
Reverse Power relays operation se DG trip hota he.
This is real Reason.
🙏🙏🙏
Sir aap KVA ko current aur kW kis formula se nikalte hai.
Jay Jagannath sir 🙏 sir alternator and avr ka working principles vedio banaie please
Apfc used krte par iska load , total load me iskha load calculate krta h ya nhi
Thanks sir🙏🙏🙏🙏
Avr sort hone ka karan pe video bnae
Dg me kon sa lube oil dalte hai, or dg ka kitna load connect kr skte hai (1250 kva ka dg hai)
1. Ye batao capacitor ko add karne par load 800kw se 1000 kw kaise ho jayega
2. And ham 800 kw load fix hai to capacitor laga ke power factor improve kar rahe hai to kya nuksan hoga
kyonki hamare equipment se bhi to power factor kam hota hai kewal alternator me hi loss to nhi hai na.?
Good
Ac ( EB )power k time ager capacitor panel ko band kr de to kya nukshan h or kya capacitor panel ki vje se humari main acb trip ho sakti h
Good.rsh
Agar Hmare DG pe PF 0.8 se kum chal rha ho .....0.68 ya 0.75 tab kya kre bhai ...iska solution capacitor hi hai na
भाइ अगर मै capacitor लगा के सिर्फ़ 700 kw use कर रहा हु तो क्या नुकसान है
Thank you so much
Sir kW se Current kis formula se nikalte hai.
Bhai node and branch ke bare me video banai aur samjao
Dg power factor 0.6 de tab kya capacitor use karna chahiye?
Please one video on basics of DG & APFC panel function
Sir imcc ka video banavo smart mcc kaise work krti he vo
Sir please make video about chemical earthing
Sir mera inverter genretor se charge nahi ho raha hai. Samarsebal chalne se inverter charge hota. Eska koi solution bataey.
sir, i have some confused..if capacitor use then increase voltage and current and power equal to product of vi then why power is not increasing..
Bhai aap bollard gate barriers ka control diagram bnao
DG ko chalu krke output me PF kaise check kr skte h btaiye sir
Avr trip nai krta sir , generator control module trip krwaata hai generator ko during overloading
👍👍👍👍
amada terret punch press pega 357 ki jankari do
Sir helecaptor me Kon sa motor use hota hai Bata a gea please sir
Lekin agar 800kw ki capacity wale par 400kw ka load jode to kya capacitor bank chalu kar sakte hain
Bhai muze bato Jo small genretor ate he like petrol wale honda ke unka wavefrom to Nahi hota na mstlb uspe computer chalne par kharab Nahi Hoga na🤔🤔
No,but better use through ups.
Can you please explain on why we designed AC voltage as 230v,440v & DC as 12v 24v 48v 72v?
Sir mai ek stadium me mentanance ka job karta but os me jo tower light hai os me 2000watt ka single phase balb laga hai osko ham dg se opret kaise karenge keny k oska chock ignetar hai os k sath capiceter v laga hua hai espe thora bataye sir
Sir yaha kaam karne ke jagah transmission ka power bandh hote he hamari DG chalu hota hai magar hamara capacitor bank band nahi hota hai is se hamara DG ko kuch effect hota hai pls sir toda bataye
servo moter ki drive ki jankari do drive ke card ki jankari do cnc ke servo alarm ki jankari do
Sir type of submersible ka vedio banao na sir please
Double fed induction generator working explain plz....WIND TURBINE me use hota hai... Aisa....pls.... nhi smj aata... Ye topic pe 30mim ka video bana do detail mai
Sir mera sawal ye h ki normal dg gharo me upyog ki jane wali dg1000 1500kva ki ho sakti h aur agar ye 1000 Kva hoke 800 Pe Chalta h to hmare gao me laga tarsformar mat63 ya 100 kva ki ho ke itna lod kyse leti h
Max 63 kva lod lag bhag 50,000ke aas pas ho jata h
Bhai Kiske ghar mai lga hai 1000 KVA ka Dg......Normal ghar mai Chote hi DG ki need hoti hai 3 KVA se 30 KVA....Depending on your load
1000 KVA to Kai Village ki Bijli Chala dega bhai ...Ye Maximum Industry mai lage hote hain
In DG sets, role of AVR is to maintain voltage of tha alternator. Now how it maintains Voltage of Alternator??... By varying DC Excitation Voltage and current of the Excitation windings of an alternator.....But, by varying the voltage of excitation field windings, Power factor also changes...This means role of AVR is not only to maintain Voltage, but Power factor also..
Now, what will happen if we Connect power factor improvement devices??.. There will be ambiguity between AVR and APFC..