How to Calculate Size of Cable Tray and How to Install Cables Inside Cable Tray (Part 2)

Поделиться
HTML-код
  • Опубликовано: 23 дек 2024

Комментарии • 16

  • @GPI-JoannDosal
    @GPI-JoannDosal Месяц назад

    Sobrang helpful po neto, thank you po! Sana po next na maitackle is yung sizing of duct bank sa PEC. di ko po kasi talaga maintindihan. :(

  • @ninjaniunlimovie2679
    @ninjaniunlimovie2679 4 года назад +1

    Ang ganda ng channel na toh para sa tulad namin walang alam sa electrical more power po

  • @valmurs
    @valmurs 4 года назад +1

    Maganda to lods sa mga electrical students or yong mha nakapagtapos ng tesdA na hindi pa malawak ang kaalaman sa electrical wire

  • @CharlesMotovlog
    @CharlesMotovlog 4 года назад +1

    Nice vlog sir..consistent lang sa pag upload sir.. Baka naman.

  • @remediosb.tongol9231
    @remediosb.tongol9231 4 года назад +1

    Imformative vlogs, do more, keep vloging.

  • @ElmerSportRock
    @ElmerSportRock 4 года назад +1

    nice learning sir, thanks

  • @merfess
    @merfess 4 года назад +1

    Informative po

  • @emilyvlog6185
    @emilyvlog6185 4 года назад +1

    Nice content sir

  • @GANDANGLALAKI
    @GANDANGLALAKI 4 года назад +2

    New supportters from fb pre jeanjoe flores

  • @humbeym9069
    @humbeym9069 2 года назад

    sir ang pag derate po ba ng conductors na nakalagay sa cable tray eh ganun din sa nakalagay sa PEC na table ung example eh pag 4-6 daw eh 80% na lang? what if ang space ng conductors sa cable tray eh mga isang dangkal need pa ba iderate?

    • @RandyAmorchannel
      @RandyAmorchannel  2 года назад

      Sir ayon sa PEC Section 3.10.2.6, yung mga derating factors ay not applicable sa conductors installed in cable trays. Susundan naten yung derating factors na nakasulat sa Section 3.92
      "Where conductors are installed in cable trays,
      the provisions of3.92.2.71 shall apply."

  • @leogrande9977
    @leogrande9977 2 года назад +1

    Medyo malabo ang gamit ng single conductor cables on cable tray. Dapat maging specific ang code kung 3-phase para pwedeng i-bundle as trefoil for smaller tray width.

    • @RandyAmorchannel
      @RandyAmorchannel  2 года назад

      Sakop pa din ng PEC yan general provisions yan sir. Thank you sir sa comment

    • @leogrande9977
      @leogrande9977 2 года назад

      Mostly kc sa ganyang kalalaking size, they must be 3-phase feeders, so i-apply dapat ang 3-phase cable formation.

    • @RandyAmorchannel
      @RandyAmorchannel  2 года назад

      @@leogrande9977 tama sir, either trefoil formation para makatipid sa cable width or pwede din namang flat formation with distance, depende sa diskarte ng design engineer. Good point sir. Applicable pa din ang provision ng PEC di lang nila ginawang specific para siguro magkaroon ng flexibility yung designers. Kaya kung mapapansin mo sir sa dulo ng video ay pinakita ko yung mga accessories sa installation ng cable mapa horizontal formation or trefoil formation.