Tanveer bro.. Ur post is very useful for Mep engineer and Fire fighting engineer.. As a Mep Engineer, i wish u thanks it will very useful for people in our field.. 😍😍😍👍👍
First of all, i appreciate eng.Tanveer Ahmed, his way of explaining is excellent. 2ndly he prepared slides perfectly. my request to mr.tanveer is please always attached NFPA reference below link, we can read many things from google but where its written in NFPA, its difficult to find. moreover, if you can attached some drawings also below link.
@@TanweerAhmedI want to know that the Installation height of Fire fighting GI pipes from ceiling the threded rod is for how much length for hanging pipes & also from side wall what should be the distance wall to pipes ..please send the link if available
I here that as per NFPA-13, if height of false ceiling is 80cm ,than we have to use upright sprinkler above false ceiling. Up & down . Anyhow sir your vedios are very good & proffesional helping us very much
Thank you very much. I requested this information some days ago. Pipe schedule method explained clearly. Please explain hydralic calculations in elite. I hope u covered all the topics in firefighting. Thank u for your information 🙏
Sir valuable knowledge. Thank you so much , I request you to please full design course regarding HVAC & Firefighting in collaboration with some institute .It will very beneficial for new graduate like us. Unfortunately after many effort I didn't find any institute or training center which transfer this knowledge to young professional you are first who transfer this knowledge.I appreciated and hope sir you will think my suggestion and keep doing good work .Allah bless you... Regards, Engr Asif Karachi....
Assalamualaikum sir. What will be the minimum residual pressure for ordinary Hazard 1, ordinary Hazard 2 ,Extra hazard -1, Extra Hazard -2 and High piled storage occupancies
Wow. I make a good living by ripping out pipe scheduled systems. This is old school method, if you're not hydraulically calculating the system, you have zero clue on what head is getting desired pressure to operate. Only reason to use pipe schedule is in a room requiring more than 2 sprinkler heads on the same branch line.
Agreed. My RUclips Channel is for beginners and junior Engineers for learning. I try to learn and teach from basic to advance. However, I have uploaded some videos on hydraulic calculation also.
Assalamualaikum Engr.Tanveert Ahmed You are really a great job. Can you please guide me. I have a query for design and quote sprinkler system of Diagnostic Block that has ground + 4 floor having area of single floor is 200*300=60,000 sqft. So we can calculate it on pipe schedule method as you guide us as per NFPA. Kindly suggest me or guide me pipe size for riser that will used for main riser. As per Nfpa 13 guide for light hazard occupancy table shows pipe sizes till 4" and sustainable 100 sprinkler according to my knowledge. Please sent me more sizes that sustain 500+ sprinkler. Thanks in advance
Assalamualykum, bhai Above & below sprinkles how to differ , I mean when we have to use above sprinkle ,what should be the maximum height for ceiling to provide the above sprinkler.
W.salam, it depend on condition where these sprinklers are required for above & below sprinklers. Commonly under used sprinklers but in above ceiling rarely used sprinklers where many services are used above ceiling and you want to protect them.
7:13, what's the purpose of having U piping pendent sprinker? we install piping for pendent sprinker this way and I don't know the reason behind this, could you explain it? thanks.
U-bends are used primarily to prevent sediment accumulation in the drop to the sprinkler. Prevent mineral deposit, pipe scale, and sediment accumulation (NFPA 13 2002 8.14.18.2, 2007/2010 8.15.18.2, 2013/2016 8.15.19.2)
Yes you can get. Join my Telegram group "HVAC|MEP Engineering" and link is given in each my RUclips video's description and also my community tab for joining
Light Hazard: Light hazard refers to places where there is a low risk of fires, like offices or homes, so they don't need a lot of fire protection. Ordinary Hazard: Ordinary hazard refers to places with a medium risk of fires, like warehouses or factories, so they need some standard fire protection measures to keep people and property safe.
Great Khan saheb.... 👍👍👍👍
Knowledgeable video.
Thanks
Tanveer bro.. Ur post is very useful for Mep engineer and Fire fighting engineer.. As a Mep Engineer, i wish u thanks it will very useful for people in our field.. 😍😍😍👍👍
Welcome
Thanks bro..
Pls kindly post full details about hydraulic calculation for fire protection..
Woowoo VERY useful information for student
Thank you
First of all, i appreciate eng.Tanveer Ahmed, his way of explaining is excellent. 2ndly he prepared slides perfectly. my request to mr.tanveer is please always attached NFPA reference below link, we can read many things from google but where its written in NFPA, its difficult to find. moreover, if you can attached some drawings also below link.
References to be added in next videos insha'Allah. Thanks for apriciation
@@TanweerAhmedI want to know that the Installation height of Fire fighting GI pipes from ceiling the threded rod is for how much length for hanging pipes & also from side wall what should be the distance wall to pipes ..please send the link if available
Watch my video "fire sprinkler system design calculation part-1" for side wall distance and sprinkler distance.
@@rehanzahid7591 I also needed.
@@mysamsunga3122 what you want
Love from India. I'm also a MEP Engineer.
Thanks dear
Very Nice Explanation.
Thanks
Me working in naffco and I am following your video sir thanks for im formation
Thanks
Masa allah very nice video sir
Thank you
Very informative 👍
Thank you
Awesome Explanation with patience.
Thanks
sir you are an amazing teacher.
Thanks
Informative Vedio
Sir Good presentation
Thank you
Good explained in easy way
Thank you so much 🙂
I here that as per NFPA-13, if height of false ceiling is 80cm ,than we have to use upright sprinkler above false ceiling. Up & down . Anyhow sir your vedios are very good & proffesional helping us very much
I am not perfect, if you have knowledge then please share with me through NFPA reference. It will be helpful for me as well as others.
G8 Bhai well explain ❤
Thanks
I m from india.. Your information is so useful..
Thank you
Well expalined ji...
Thanks ji
Thanks I was waiting for this vedio
Welcome
Isse Acha Koi ni bata sakta h sir thankss
Thanks 😊
Very good information sir
Thanks
so beautiful video
Thank you
Thank you Tanweer sahab
Welcome 😊🙏
Good day sir,,,thank you for the knowledge I've got from your explanation of fire protection
Welcome
Very useful...
Thanks
Once again, thanks dear sir.
Welcome
I am your new subscriber
Very helpful information
Thankyu bro
Thanks and welcome
Thank you very much. I requested this information some days ago. Pipe schedule method explained clearly. Please explain hydralic calculations in elite. I hope u covered all the topics in firefighting. Thank u for your information 🙏
Welcome, I will... insha'Allah
@@TanweerAhmed thank u in advance 🙏
@@mepworld3385 Welcome
always best one
Thanks
बहुत बेहतरीन जनाब!!!!
क्या आपने high hazard occupancy पर भी कोई video बनाया है। अगर हाँ तो कृपया रास्ता दिखाये!!! शुक्रिया!!👍👍👍👍
Join my Telegram group "HVAC|MEP Engineering" for technical discussion and documents
Good job sir
Thanks
Tanveer bhai septic tank Ki design Ki be AK video Bana den
Thanks for sharing knowledge.
InshaAllah
very informative and knowledge gaining sir, one small suggestion if you can also mention the NFPA Standard table number too.
This is taken from NFPA-13 but table number is different as per version. Suggest review this standard then you will find.
Great sir
Welcome
Nice video
Thanks 😊
Hello great video, in wich edition of NFPA 13 can I find the table with the diameters?
This table is available in each NFPA 13
Is the red colour for. Pipe line or we go for Interiors colour
Fire pipe standard color code is red. Suggested to follow standard color code for interior and exterior
Do you have video on Hydraulic calculation method..?
I have uploaded two videos on it
Residential building ka pipe sedule for like kitna pipe size pe kitna sprinkler lagega reply fast pls
You can use light hazard pipe schedule method for residentials buildings
@@TanweerAhmed thank u sir u r the best
In high rise building we use same size riser or different size riser pipe for floor to floor
For risers (Standpipe) pipe you have to follow "standpipe schedule method" my video is available on this topic
Sir can you make video about riser pipe size calculation
I have already make video on it. Kindly watch "nfpa-14 pipe schedule method for standpipe"
Sir
What is residuial pressure for remote sprinkler need to considered for sprinkler punp design I am not getting same in nfpa
Residual pressure is 15psi for light hazard and 20psi for ordinary hazard as per NFPA 13
Only upright sprinkler ke liye ??
For all
Sir finish floor se kitni maximum and minimum height pr sprinkler install hone chahiye
There are different heights. Refer NFPA-13
Hello sir, interesting video hoping i can learn more from you.
Welcome
Yery nice sir Mai Abhi BMS course kr rha hu sir
Very good
Sir valuable knowledge. Thank you so much , I request you to please full design course regarding HVAC & Firefighting in collaboration with some institute .It will very beneficial for new graduate like us. Unfortunately after many effort I didn't find any institute or training center which transfer this knowledge to young professional you are first who transfer this knowledge.I appreciated and hope sir you will think my suggestion and keep doing good work .Allah bless you...
Regards,
Engr Asif
Karachi....
Thanks
@@TanweerAhmed I wanna meet you sir... please give some valuable time ..
+923332472721 this is my WhatsApp number
@@TanweerAhmed Thank you so much sir...
If have 6 splinkers in one branch can we use 1.25" size pipe for 4 splinkers and 1" pipe for 2 splinkers
As per schedule you can reduce sprinklers quantities but can not increase sprinklers quantities
I will not increase but I will change size of pipe is it possible
Yes you can use larger pipe size
Sir do you have video for above 465 square meter area sprinkler system design, i mean the hydrolic calculation method
Same method used
Then what is the difference between hydrolic methord and pipe schedule methord
Sir,can we Pipe schedule method apply for spray system design ?
I think Yes, you can apply but suggested to refer relevant NFPA code for confirmation
Thanks
can u please prepare video on hydraulic pump calculation
Ok noted, in future insha'Allah
@@TanweerAhmed please provide as soon as possible i want to learn
Thank you sir....
Welcome
Sir
Expecting electrical related videos.......
Thankz
Assalamualaikum sir.
What will be the minimum residual pressure for ordinary Hazard 1, ordinary Hazard 2 ,Extra hazard -1, Extra Hazard -2 and High piled storage occupancies
W.Salam, Refer NFPA 13
Good sir
Thank you
Tanvir bhai iska kam Kaise rate se liya jata hai
Different rates as per country, project, quality, location, material brand, or labour rates etc.
Residential building which type of hazard , and which pipe schedule will use
Light hazard is used for residential building. Normally m.s pipe schedule 40 is used
@@TanweerAhmed Normally we are using Gi pipe class B
G.I pipe also used which is corrosion protected by galvanized
Did you worked in UAE
I only worked in Pakistan 🇵🇰
Sir ji nice vdo.
Lekin yahape mujhe aik bat puchni hai ki agar k 115 lenge to pipe size badh sakti hai na!
Yes
nice
Thanks
Sr.. sidewall sprinkler covering area can you explain please
Ok noted
All false ceiling required above sprinkler?
No, it depend on designer
Sir plz plz one lecture give for gpm means how pump size for ff and how many gpm required
Ok noted
Sir kab ham log upright sprinler lgate hai or kab pendant
If height hindrances or open false ceiling then use upright fire sprinklers, otherwise use pendent fire sprinklers
Please make video for hydraulic calculation
insha'Allah
Sir, We can calculate total number of sprinklers based on Sprinkler coverage area also .Please correct me if am wrong
Yes, you are right
1" me 2 sprinkler lagana lekin pipe ka length kitna hona chahiye Tanvir sir
Not more than 15 feet distance from sprinkler to sprinkler but length finalized as per hazard protection area selection
Wow. I make a good living by ripping out pipe scheduled systems. This is old school method, if you're not hydraulically calculating the system, you have zero clue on what head is getting desired pressure to operate.
Only reason to use pipe schedule is in a room requiring more than 2 sprinkler heads on the same branch line.
Agreed. My RUclips Channel is for beginners and junior Engineers for learning. I try to learn and teach from basic to advance. However, I have uploaded some videos on hydraulic calculation also.
Excellent explanation.If u could please explain with calculation sheets in excel & share them, it will be very useful.
Thanks and will try ...👍
Sir fire fighting pipe me kitna kg pressure dala jata hai
It is not fixed but change according to system type.
Sir may fire fighting system designing sikhna chati hu. Mai ne civil engineering me diploma Kiya hu ap suggested ki jiye
Yes you can do
hello sir..sir nfpa codes ko yad karne ki koi trick ho to pls share kare
Study NFPA codes and makes notes for remembering
Good news
Thanks
Sir my K factor is 115
How many sprinkler we can install in 25mm pipe 32mm pipe and 40mm pipe
Ordinary Hazard
You should check pipe schedule method of nfpa-13 as per hazard
Sir nfpa ki books mill jaen g pdf me agr ap k pas available hen to. Plz.
And ashare ki books.
Join my Telegram group "HVAC|MEP Engineering" link is available on my each video's description and community tab
Thank you
Welcome
بھترين ڊيئر
قرب
Very informative video..
Haw can I got the pdf of this video...
Thanks and share email address for pdf
@@TanweerAhmed ply provide any link to download it
Link not available
Karachi, Sindh, Pakistan
Sir 200 mm dia and 250 mm dia pipe me kitne hydrant points maximum install kar sakte hai ?
For commercial and industrial both.
Plz advice
As many as you but operate any two incase of emergency.
Please sent detail of fire pump room details
Detail is given my videos "How to read fire pump Room shop drawing" Part-1 & Part-2
Grooving pipe kitna size se suru Kiya jata hai kitna mm2 groove hota hai sir
Refer technical catalogue for groove pipes and fittings details
Assalamualaikum Engr.Tanveert Ahmed
You are really a great job.
Can you please guide me.
I have a query for design and quote sprinkler system of Diagnostic Block that has ground + 4 floor having area of single floor is 200*300=60,000 sqft.
So we can calculate it on pipe schedule method as you guide us as per NFPA.
Kindly suggest me or guide me pipe size for riser that will used for main riser.
As per Nfpa 13 guide for light hazard occupancy table shows pipe sizes till 4" and sustainable 100 sprinkler according to my knowledge.
Please sent me more sizes that sustain 500+ sprinkler.
Thanks in advance
Kindly watch my Pipe schedule method video of NFPA-13 (for sprinklers) and pipe schedule method NFPA-14 (for Standpipe or risers)
وعلیکم سلام
@@TanweerAhmed I have done.
But not find details as I requested.
kindly review my question briefly please.....
Assalamualykum, bhai
Above & below sprinkles how to differ ,
I mean when we have to use above sprinkle ,what should be the maximum height for ceiling to provide the above sprinkler.
W.salam, it depend on condition where these sprinklers are required for above & below sprinklers. Commonly under used sprinklers but in above ceiling rarely used sprinklers where many services are used above ceiling and you want to protect them.
No matter whatever height you wants above ceiling because you can increase height of above ceiling sprinklers
Sir upright sprinkler basically kha use hoty hh
Basements or where false ceiling is not fixed
Sir false ceilings k ander upright sprinkler used kar sakty h???
Yes you can use for above ceiling protection purpose only
Sir I am a nontechnical professional.After doing MEP course, can I able to design fire fighting system.
Yes you can
@@TanweerAhmed thank u sir for your quick reply. 😀
sir, can i get fire fighting building project report (design and calculation)
I haven't available, if found any then to be share with you
how to calculate fire pump hp to be use in designing Afss. thank you and can you suggest a book for this?
7:13, what's the purpose of having U piping pendent sprinker? we install piping for pendent sprinker this way and I don't know the reason behind this, could you explain it? thanks.
U-bends are used primarily to prevent sediment accumulation in the drop to the sprinkler.
Prevent mineral deposit, pipe scale, and sediment accumulation (NFPA 13 2002 8.14.18.2, 2007/2010 8.15.18.2, 2013/2016 8.15.19.2)
I suggest to read NFPA-20 regarding firefighting pump design & detail. Or share email address I will forward you
@@TanweerAhmed please do share., black.colours2018@gmail.com
thank you.
I have forwarded through email
without false ceiling sprinklers mai sprinklers kum use q hote hai
I don't think so...
Sir distance between two sprinkler kitna hona chaheye
"NFPA-13 sprinkler head distribution" this video on my channel will be helpful for you
Sir NFPA stand for what?
Firefighting systems
1.5 इंच ब्रांच पाइप के लिए मैन पाइप मे किस साइज का हाल करना पड़ेगा
Pipe size select according to number of sprinklers or flow.
@@TanweerAhmed I want to ask hole size
How can we find pipe size for sprinkler?
How can we decide for 2 sprinkles 1” pipe size ? From where we can have this calculation?
No need calculation for pipe size, NFPA-13 has given number of Sprinklers as per pipe size according to hazard therefore follow it
Hello, thank u for the presentation! , Could u give us a tutorial about an example of hydraulic calculation pls
Ok noted
Sir I need nfpa handbook
Join my Telegram group for handbook. Group name is "HVAC|MEP Engineering" link is given in each video link
Sir,
How can calculation underground wrapping tape for ms pipe?
Exam:for 6 inch
Consider overlapping one inch and then wrapping one feet pipe length and then multiply complete length
@@TanweerAhmed ok
But how can wrapping roll calculation
You know the diameter and length of pipe and also informed overlapping. At least you should know this working.
What is PM - 200
FM-200 or PM-200?
If you can explain also in english it can be more helpful....for new engineering students .
Ok noted
Many would benefit if this was in English,nevertheless good stuff
Thanks and I will subtitles in English
hello can i get nfba 13 pdf
Yes you can get. Join my Telegram group "HVAC|MEP Engineering" and link is given in each my RUclips video's description and also my community tab for joining
India me koi company hai kiya.
Please provide me link.
Kiya esme future bn skta hai .
No idea about India because I belong to Pakistan
What is light hazard&ordinary hazard
Light Hazard: Light hazard refers to places where there is a low risk of fires, like offices or homes, so they don't need a lot of fire protection.
Ordinary Hazard: Ordinary hazard refers to places with a medium risk of fires, like warehouses or factories, so they need some standard fire protection measures to keep people and property safe.
@@TanweerAhmed thanks sir only two typw of hazards
@@satheeshchandran23 There are also other types of hazards but you asked about two types therefore I replied accordingly.
please share the pdf of this lecture .....
How to share?
Plumbing pipe line ka rate kya rhta hai sir indian company or sub contractor ka india me
No idea because I belong to Pakistan