1. Dg operator practical training ruclips.net/video/T77bZHVUAXM/видео.html 2.Plc industrial automation free video tutorial course ruclips.net/video/hk1WTmLujrA/видео.html 3. Dse 7320 full course video tutorial ruclips.net/video/bsZ8875Xo58/видео.html 4. How to read Electrical Drawings Video tutorial ruclips.net/video/IHHCT43sdYM/видео.html 5.how to bypass generator AVR ruclips.net/video/JzuFHKMkKyA/видео.html
no, the DSE does not control droop, it is controlled by the AVR via the quad droop CT's and the electronic governour control the speed, ther DSE can control the reactive power.
Can you recommend an electronic governor, actuator, and mag pick up switch capable of working on a Perkins 2006 TTag 380 kva. I was looking at an ADC 175 actuator , is this OK for this size Generator,
My issue is the 20KV generator is meant to supply power to office, kitchen and laundry, however I have noticed that once we turn on the cooker it the generator shuts down,I want to know exactly how I can solve this problem,is it under voltage issue?
Nice explanation sir actually I had a small problem that was the dg was on but few seconds ofter then shutting down the display shows AGF V3 LOSE what I candoo now could you tell plzz sir
Nice information? let you do detail wiring with explanation on deep sea electronics 7320 amf controller with all componemts like contactor, glass relay...
Hello sir how are you, sir i have a genset kta 38 cummins 1000kva dse 7320 if the genset start line to neutral 230v line to line 400v, but the problems is frequency indicate 53hertz not stable to 60hertz how to fix this problems, thanks and take care sir
Make a video on trouble shooting a genset that shuts down after seconds or minutes after starting stating or explaining all possible reasons to what the cause can be
Can you make a troubleshooting video of a generator which cannot be shutdown using the DSE6010 controller. Even the emergency stop button doesn't work anymore.
Dse 8610MKII synchronizing controller full training Part 1 video Link: ruclips.net/video/7SSpPzUazdA/видео.html Part 2 video link: ruclips.net/video/-NJ8BpXdrjs/видео.html Part 3 video Link: ruclips.net/video/ly_3RiZNg2w/видео.html DSE 8610 Part 4 VIDEO LINK configuration: ruclips.net/video/eNnEgmlzYuI/видео.html Practical training 8610 video Link: ruclips.net/video/zwLP5X9gGhc/видео.html
My Perkins generator is showing over voltage alarm and stopping. Phase to phase is 380 v and line to phase is 270 but actual is 220v so how can we adjust the line to phase voltage.
3 phase Ship Generator sometime getting high voltage alarm (more then 106%) and on attempting paralleling with other generator Blackout occured. Voltage 480v instead if 440v. 2. Same Generator in off load condition, sometime getting high voltage alarm Please advise for the root cause
Bro! How to troubleshoot generator.gulf power 125kv.this senario.without load the voltage is ok.but if you put load the voltage flunctauting voltage.what is the problem.
Can explain how configure digital output based on speed. I want configure 3 output on different speed plz make video on it. thanks your video was so useful for new learners. God bless you sir.. Keep making more videos ... 🙏🙏🙏🙏
Santosh thanks for liking 👍 I would like to inform you there is no option to select three outputs for 3 different speeds selection you can do it with different configuration selections
I have a Bundu 20kva Generator it's new but it's failing to take my four laundry machines, 2 speed Queen dryers and 2 commercial washers , it just shuts down when they are all running, what could be the problem
The Gen. we have here shutdown after working for about 3 minutes and it is displaying uh with an alarm sound, what could be the problem? II. How can I solve the problem?
Thanx Engineer Muzamir,I request to demonstrate this practically on controller how to go about transient voltage setting, 10% high and low voltage allowance setting..
FAILED TO REACH LOADING VOLTAGE, If the engine fires but the generator fails to reach the loading voltage before the end of the Safety On timer a shutdown is initiated, how can fixed it?
My caterpillar generator is running but frequency is stuck at 62hz and showing message on main panel NO COMMUNICATION WITH MAIN UNIT plz give some suggestions.
Great video , you explain it very well and the step's to take to fault find. I've watched a lot of videos on generators and yours are the best by far.
All videos on our channel is full of information u can join membership to acess premium content
This is educating and it help to solve my problem immediately. Thank you for enlightenment.
Thanks
1. Dg operator practical training
ruclips.net/video/T77bZHVUAXM/видео.html
2.Plc industrial automation free video tutorial course
ruclips.net/video/hk1WTmLujrA/видео.html
3. Dse 7320 full course video tutorial
ruclips.net/video/bsZ8875Xo58/видео.html
4. How to read Electrical Drawings Video tutorial
ruclips.net/video/IHHCT43sdYM/видео.html
5.how to bypass generator AVR
ruclips.net/video/JzuFHKMkKyA/видео.html
Thank you so much very educative, I need a video on how to do factory reset of a d500 control panel
Noted
Thank u. In case of synchronizing 2 same size gensets, do we need to activate voltage and speed droop characteristics in the dse 8610
Yes sure
Even if the gensets r working off grid. In a remote area?
no, the DSE does not control droop, it is controlled by the AVR via the quad droop CT's and the electronic governour control the speed, ther DSE can control the reactive power.
Can you recommend an electronic governor, actuator, and mag pick up switch capable of working on a Perkins 2006 TTag 380 kva.
I was looking at an ADC 175 actuator , is this OK for this size Generator,
I think there is no 2006 TTag engine in my info is this generator engine
My issue is the 20KV generator is meant to supply power to office, kitchen and laundry, however I have noticed that once we turn on the cooker it the generator shuts down,I want to know exactly how I can solve this problem,is it under voltage issue?
Bro i have problem under voltage shutdown phly engine 380 tha maine 220kia uske baad yahi horha hai under voltage shutdown iska kuch btao ?
Nice explanation sir actually I had a small problem that was the dg was on but few seconds ofter then shutting down the display shows AGF V3 LOSE what I candoo now could you tell plzz sir
Which DG controller u have
@@DieselGeneratortraining Greenvens DG EMS927V4 Sir
Please reply sir
Thank you so much for the knowledge shared. My Diesel generator 52KVA shuts down citing low loading frequency. how do i solve that problem?
What is engine model record a video n sent us on
Info.powerlearning@gmail.com
Nice information? let you do detail wiring with explanation on deep sea electronics 7320 amf controller with all componemts like contactor, glass relay...
Hello sir how are you, sir i have a genset kta 38 cummins 1000kva dse 7320 if the genset start line to neutral 230v line to line 400v, but the problems is frequency indicate 53hertz not stable to 60hertz how to fix this problems, thanks and take care sir
Check ur speed sensor circuit
The mpu sir ok 2 speed sensor is install i check, thanks sir
what is the rpm?
@@shahariaakter4393 1800rpm sir
throw the mag pickup in the bin and use frequecncy detection.
What shoud i do when generator over voltage and it will automatically shutdown the genset
Expert inspection
Adjust the power to it's max and instal the sensor line.
Make a video on trouble shooting a genset that shuts down after seconds or minutes after starting stating or explaining all possible reasons to what the cause can be
Which type of engine 🤔
Thanks. But show us practical solutions to solve over voltage
I will show you that in my next video.
When replacing contoller..
I encounter under voltage alarm.. even the phasing and rated v was reconfigured..
Any advise sir
Which controller model u have and what exact alarm is trigger
Can you make a troubleshooting video of a generator which cannot be shutdown using the DSE6010 controller. Even the emergency stop button doesn't work anymore.
Air shutoff valve.
Thank you so much, Nice explanation
Glad it was helpful!
can i get a video of confiheration of deepsea and sycronization of two or more DGS
Dse 8610MKII synchronizing controller full training
Part 1 video Link:
ruclips.net/video/7SSpPzUazdA/видео.html
Part 2 video link:
ruclips.net/video/-NJ8BpXdrjs/видео.html
Part 3 video Link:
ruclips.net/video/ly_3RiZNg2w/видео.html
DSE 8610 Part 4 VIDEO LINK configuration:
ruclips.net/video/eNnEgmlzYuI/видео.html
Practical training 8610 video Link:
ruclips.net/video/zwLP5X9gGhc/видео.html
Need a video for smart gen controller for Automatic transfer switch setup in the settings of the controller and wirings.
Ur from which country
Sir Good day.about REVERSE POWER can You please make a lecture or content in your blog.
Thank you...
Yeah sure soon
Make video regarding CAT et and Volvo vodia
My Perkins generator is showing over voltage alarm and stopping. Phase to phase is 380 v and line to phase is 270 but actual is 220v so how can we adjust the line to phase voltage.
Try from AVR
Can you explain further why frequency increase and how to reset the frequency?
on the governour
3 phase Ship Generator sometime getting high voltage alarm (more then 106%) and on attempting paralleling with other generator Blackout occured. Voltage 480v instead if 440v.
2. Same Generator in off load condition, sometime getting high voltage alarm
Please advise for the root cause
Make insulation test
poor voltage control
Sir my 1000 kva cummins is showing high ac voltage after I increase one of the voltage phases, what should I do.
Adjust ur AVR as first step
Please I need all the steps I to take thanks
Good morning pls help my Gen cat 450 kva couple of second it will sort down it showing high vote sort down pls what could that be the problem sir
Please share what is the generator model n controller type
Bro! How to troubleshoot generator.gulf power 125kv.this senario.without load the voltage is ok.but if you put load the voltage flunctauting voltage.what is the problem.
Which Country & city ?
Im here saudi arabia
How to trouble shoot
could be the load or the AVR.
Can explain how configure digital output based on speed. I want configure 3 output on different speed plz make video on it. thanks your video was so useful for new learners. God bless you sir.. Keep making more videos ... 🙏🙏🙏🙏
Santosh thanks for liking 👍 I would like to inform you there is no option to select three outputs for 3 different speeds selection you can do it with different configuration selections
@@DieselGeneratortrainingThanks for feedback, plz suggest how I can achieve from DSE 7320 for said above problem
Asalaamu allykum why is a generator starting after few seconds it shut down
you can if the DSE has the PLC internal function
sir, if our generator shutdown on low voltage even load is not connected. whats the reason?? please answer
low voltage?
Thank you so much for information
Ur welcome
How do reset low voltage fault on kj power generator using a d500 control panel
Hi sir
Can you explain what is a transient delay?
My dg set not started alerms under voltage ans under frequency please solve the problem
What could be the fault, I start a new dcec dongfeng Cummins model 4bta3 9-g13 but all the bulbs are blinking?
Thanks for sharing. Very useful for gen set operation.
why does the generator give an error low voltage of the generator? DTK controller
I have a Bundu 20kva Generator it's new but it's failing to take my four laundry machines, 2 speed Queen dryers and 2 commercial washers , it just shuts down when they are all running, what could be the problem
i have a problem of over voltage and under voltage after 7sec from starting the cumins generator ,adjust avr but not respon to this issue..help pliz
What happened for my generator suddenly shutdown and it mention low voltage
Hi sir,can you advise how to increase value of L1,L2 and L3?
L1-L2.....374V
L2-L3.....380V
L3-L1.....366V
How to fix this?
Please help
What is ur laod
By AVR
check your neutral.
كيف حال يا اخي فين شغل انت؟
انا في موجود جازان.
نحنا موجود جده
إن شاء الله يا أخي سألتقي بكم.
In synchronization generator 2 different KVA 800&500 under voltage tripping after running some times on load
what will be the possible causes of a generator that starts and run for 2 to 3 minutes and dies?
There is many reason
blocked fuel/air filter
I have a generator that works a little and then stops and gives a frequency alarm runaway What's the problem?
Please can you answer me I still can't figure out why
@@dark-mb1bsI'm having the same issue.
overspeed?
Boss I want to be like u
The Gen. we have here shutdown after working for about 3 minutes and it is displaying uh with an alarm sound, what could be the problem?
II. How can I solve the problem?
Our generator not giving load for the output..type diesel 800kVa
Contact our team via email
Sir Urdu language please Vedo information
Thanx Engineer Muzamir,I request to demonstrate this practically on controller how to go about transient voltage setting, 10% high and low voltage allowance setting..
its in the manual
Nice to herd
FAILED TO REACH LOADING VOLTAGE, If the engine fires but the generator fails to reach the loading voltage before the end of the Safety On timer a shutdown is initiated, how can fixed it?
how did you fix it??
what is it set at ? have you tested the speed controler.
Nice one!
i have a300kw generator 12 cylinder starts and runs for a couple of seconds then shuts off it is not a fuel problem mybe a voltage drop i dont no
you have check alarm on the controller to start ur troubleshooting
Want to under frequency stop problems
Thank you so much as usual.
Generator locked out
Stop mode
Please explain this
Voltage is running okay but rpm is over raping and stoping generator
My generator give alarm charg failyer waht problem
Check dynamo
Super bro
When the oil sensor cable taken off engine continues with ac 265 vlts
My caterpillar generator is running but frequency is stuck at 62hz and showing message on main panel NO COMMUNICATION WITH MAIN UNIT plz give some suggestions.
Which controller and engine model u have try to adjust speed
if EMPC 2 bin it.
If the timing of c32 caterpillar generator 1000kva is in correct will it start
Which timing 🤔
Dse 7320
Voltage problem full load
हिन्दी मै भी समझाना होगा
Under ampere reason
Ampere depends on ur connected load
Thanks for advise
Voltage problem
Under speed alarm how can fix that
raise speed.