Pendawaian Pemanas Air Mandian Elektrik | Water heater

Поделиться
HTML-код
  • Опубликовано: 11 янв 2025

Комментарии • 361

  • @akuahmad1475
    @akuahmad1475 19 часов назад

    ni baru ilmu yg betul,bkn mcm yg satu lg tu,terpalinggg pakar lektrik😄🤭..tp ilmu yg disampaikn byk yg tak betul...

  • @ahmadamirul3095
    @ahmadamirul3095 2 года назад +43

    Alhamdulillah. Setakat ni saya rasa dalam banyak² video yang saya pernah tengok, video ni paling lengkap dan detail tentang pemasangan water heater dari A to Z. Beginner tengok pun boleh faham ni sebab siap sekali dengan tutorial. Terbaik Mr Saiful77 👏👏👏👍👍👍

    • @mrsaiful7776
      @mrsaiful7776  2 года назад +1

      Terima kasih tuan 👍🏻

    • @hairulanuarrosman4822
      @hairulanuarrosman4822 2 года назад +2

      Penerangan yg sgt Baik dan jelas. Tak kedekut ilmu… semuga terus berjaya dan cemerlang cikgu

    • @Rain-lu9zz
      @Rain-lu9zz Год назад

      betul tu

    • @333nevermind-ql6wo
      @333nevermind-ql6wo Год назад

      Betul Kan ...penerangan yg totally daat difahami....terbaik 👍👍👍👍👏👏👏👏

    • @kaduk
      @kaduk Год назад

      ​@@mrsaiful7776 salam tuan. Boleh sy mahu hubungi tuan.

  • @SimpleLife-q9r
    @SimpleLife-q9r Месяц назад

    panjang betul la video ni.. tapi sangat la detail. terima kasih tuan atas perkongsian ilmu

  • @roostersam9793
    @roostersam9793 Год назад +3

    penerangan yg baik..x gugup..saya chinese pun bole faham..siap dgn st law skali...
    lain kali buat tuk 3 fasa pulak..tq cikgu

    • @mrsaiful7776
      @mrsaiful7776  Год назад +2

      Terima kasih sudi singah 👍🏻
      3fasa sama je dgn 1fasa, beza dlm Db je

  • @aieezuhairi8851
    @aieezuhairi8851 10 месяцев назад

    Penerangan yg jelas lagi bersuluh terima kasih cikgu

  • @mustafakamalmohamad6865
    @mustafakamalmohamad6865 11 месяцев назад

    abg saiful punya penerangan mmg terbaiklah...sgt detail dan mudah fhm...mmg terbaik lah..i like this channel..

  • @bungkongbakar1432
    @bungkongbakar1432 9 месяцев назад +1

    Tutorial yang terbaik yang pernah saya layari. Terima kasih mr Saiful

  • @djs4312
    @djs4312 Год назад +1

    Alhamdulillah,terbaik cikgu di atas penjelasan yg disampaikan,mudah difahami dn bermanfaat untuk menambahkan ilmu👍👍👍

  • @CoconutGarage
    @CoconutGarage Год назад

    Alhamdulillah, terima kasih memberi ilmu yg sangat details. Mudah saya nak faham.

  • @guesswho1664
    @guesswho1664 Год назад +1

    sangat2 membantu, semoga pahala terus mengalir kepada tuan..terima kasih.

  • @alposto4204
    @alposto4204 Год назад +1

    Terbaik 👍 tunjuk ajar lengkap dengan praktikal.

  • @panjisemarang1
    @panjisemarang1 2 года назад +5

    video ni antara yg terbaik sy pernah singgah. pendetailannya bagus, betul2 mcm masuk kelas belajar. gaya pon mcm cikgu elektrikal. ini baru ku tahu dah ada larangan pakai soket. dah connector jer pula. terbaik usaha tuan. semoga dimurahkan dan bertambah rezeki. sememangnya disarankan kpd yg mencari2 panduan dan ilmu. well done & recommended!

  • @norismanaziz8598
    @norismanaziz8598 Год назад

    Terbaik sifu....👍👍👍 Sungguh bermanfaat ilmuan nya

  • @mr4581
    @mr4581 Год назад +1

    jelas & sangat berinformatif.
    Boleh buat kelas online.

    • @mrsaiful7776
      @mrsaiful7776  Год назад

      Terima kasih,
      klas online dh stop, masa tak mengizinkan

  • @sahimibashah1327
    @sahimibashah1327 Год назад

    Mmg terbaik penerangan secara terperinci bos.....tq bg ilmu bos

  • @kklum6998
    @kklum6998 8 месяцев назад

    The most complete wiring tutorial. Can even beat Maha engineering RUclips. Kudos

  • @nejineji7970
    @nejineji7970 Год назад

    Sangat berguna. Sebab esok sy nak pasang water heater sy. Tapi soket connecter tiada. Pakai je biasa2 tu hehe

  • @firdausravindar977
    @firdausravindar977 6 месяцев назад

    Terima kasih byk2 kerana upload video ini ke youtube. 😊😊😊

  • @amirizzuddin7221
    @amirizzuddin7221 Год назад

    Alhamdulilah ilmu baru..baru tau kewujudan splash proof water heater connector..ni..heheh harga blh thn ikut jenama... Tq cikgu

  • @Rizal-em2ki
    @Rizal-em2ki Месяц назад

    entahlah. saya paling takut nak kacau DB. x confident 😅. btw. video paling kenas yg saya jumpa. layak dot byk view

  • @tmashrul
    @tmashrul Год назад

    Syukur alhamdulillah. Terima kasih yang tidak terhingga buat Encik Saiful yang berkongsi video ini. Amat2 membantu terutamanya untuk orang yang kurang mahir berkenaan wiring, seperti sy ini. 🫰🫰

  • @rafiedlatief2543
    @rafiedlatief2543 2 года назад +1

    Video2 memang terbaik..sangat memberi input yg berguna..👍👍

    • @mrsaiful7776
      @mrsaiful7776  2 года назад

      Terima kasih sudi singah 👍🏻

  • @anak_perantau
    @anak_perantau Год назад

    Alhamdulillah kongsi penerangan pasal elektrik,semoga tuan di beri rezeki dan kesihatan dunia hingga akhirat.. Aamiin 🤲

    • @mrsaiful7776
      @mrsaiful7776  Год назад

      Amin amin amin
      Tqvm sudi singah 👍🏻

  • @laksamanadaud845
    @laksamanadaud845 Год назад +1

    Terima kasih bang ilmu rcbo Tu bang

  • @fajarfaezah9402
    @fajarfaezah9402 Год назад +1

    Alhamdullilah, terima kasih tuan. Penerangan dan tunjuk ajar yg sangat jelas.

  • @AmbeChannel
    @AmbeChannel 2 года назад +1

    Alhamdulillah... penjelasan penuh ilmiah.. moga perkongsian ini memberi manfaat pada ramai.
    Mohon tuan buat video berkenaan Sub DB .. contoh Main DB dah penuh.. dan plan nak letak Sub DB di kawasan dapur utk handle DB di bahagian dapur..teermasuk plug utk water heater, microwave, fryer dan dryer..yg heavy2 tu...
    terima kasih tuan..

    • @mrsaiful7776
      @mrsaiful7776  2 года назад +1

      Terima kasih sudi singah
      Utk video sub DB dah atau tuan
      Tekan link dibawah tu je 👇🏻👇🏻👇🏻
      ruclips.net/video/6uI19gp3YCU/видео.html

  • @bengkeeooi9084
    @bengkeeooi9084 Год назад

    Cikgu, mantap sekali dan terima kasih.👍👍👍

  • @mohamadsukriyie2907
    @mohamadsukriyie2907 2 года назад +3

    Abang Mr Saiful77 wahh..🙂 akhirnya muncul jugak video yang saya nantikan pendawaian Water heater nie dari abg.. banyak dah dapat ilmu dari abg.. video yang abg tunjukkan nie memang sangat jelas.. jarang nak jumpa dalam setiap orang yang buatkan video macam abg nie. Terbaik..👍🙂 saya bagi 10 bintang kat abang Mr Saiful77 ⭐⭐⭐⭐⭐⭐⭐⭐⭐⭐

    • @mrsaiful7776
      @mrsaiful7776  2 года назад +2

      Tq, tq, tq....
      jgn puji tinggi sangat banyak je kekurangan dlm video saya ni..
      Tq for support 👍🏻

    • @mohamadsukriyie2907
      @mohamadsukriyie2907 2 года назад

      @@mrsaiful7776 sama2 Abang..🤭🤭

    • @zishamneo6762
      @zishamneo6762 2 года назад

      5min tgk terus subscribe.. Terima kasih Tuan berkongsi ilmu.. Semoga terus maju..

  • @kay-vm8ro
    @kay-vm8ro Год назад +1

    Tima ksh.ilmu yg brmanfaat👍

  • @amirkhamis5852
    @amirkhamis5852 2 года назад +2

    Terbaik Cikgu. Ilmu yg bermanfaat. Semoga Allah murahkan rezeki kepada Cikgu kita. Aminnn...

  • @abdulrazakrozally3140
    @abdulrazakrozally3140 Год назад

    Alhamdulillah, penjelasan sangat jelas mudah utk difahamkan. Terima kasih Tuan, terbaik. Done subscribed

  • @mohdayubkamsani6633
    @mohdayubkamsani6633 Год назад

    Very good illustration. Well done Tuan.

  • @belitong
    @belitong 2 года назад +1

    terbaekk cikgu mcm ni... penerangan yg lengkap sekali dgn praktikal yg selari dgn perkara yg diterangkan tu.. alhamdulillah mudah faham mcm ni 👍👍👍👍👍 terima kasih

    • @mrsaiful7776
      @mrsaiful7776  2 года назад

      Terima kasih tuan, kalau suka boleh share le pada kwan2 👍🏻

  • @PCleo
    @PCleo Год назад

    Terbaik sekali cikgu. Sangat jelas dan mudah difahami. 👍🏻👍🏻👍🏻

  • @kujuhjoe-zc1ib
    @kujuhjoe-zc1ib Год назад

    Padat penerangannya cikgu..mudah faham. Terima kasih..terbaik.

  • @MrOtakduit
    @MrOtakduit Год назад

    terbaik tuan lengkap jelas saya rasa mcm masuk kelas elektrikal semoga allah murah rezeki dan lanjut usia cikgu aminnn

  • @hamdishaffie4076
    @hamdishaffie4076 2 года назад +1

    Sangat2 bermanfaat untuk diy cegu...terima kasih atas share ilmunya...

    • @mrsaiful7776
      @mrsaiful7776  2 года назад

      Terima kasih sudi singah 👍🏻

  • @dadadidi1196
    @dadadidi1196 Год назад

    Terbaik che gu...cara penerangan yg jelas.senang difahami.

  • @aslanjuke2929
    @aslanjuke2929 11 месяцев назад

    Terima kasih cikgu... Terbaik... Minta halal ilmu cikgu

    • @mrsaiful7776
      @mrsaiful7776  11 месяцев назад

      Sama sama, saya halalkan semoga bermanafaat

  • @mohdhanif3042
    @mohdhanif3042 Год назад +1

    Tq bang atas ilmu

  • @Arrowdynamic92
    @Arrowdynamic92 Год назад

    Thanks cikgu. Banyak saya belajar.

  • @superpooper_2030
    @superpooper_2030 Год назад +4

    I can tell you why the authority banned wiring water heater with socket. It's due to evaporation whereby water will change to light molecules and will enter the socket which in long run will affect the conductivity of alloy metal/copper where the socket and plug connectivity will deteriorate overtime. This is dangerous and will probably affect the conductivity which in turn a high ohm resistance will destroy your wire and eventually heated up and will melt the wire insulation and eventually a fatal short circuit will occur when wires touch each other.
    In other countries, technician are required to apply silicone grease to socket and plug to prevent this and install additional waterproof junction box. Due to the complexity and unavailability of such tools/products, Malaysia government just change it to socket cover with PG connector. In some countries, the PG socket is built-in with RCCB for extra protection but Malaysia manufacturers have not produced such socket yet.
    My 2 cents

  • @bedjack4088
    @bedjack4088 Год назад

    Terima kasih cikgu..sy buat rujukan dan refresh...halalkan ilmu ini ya cikgu.done subscribe.👍👍👍

    • @mrsaiful7776
      @mrsaiful7776  Год назад

      Terima kasih sudi singah, ya saya halalkan semua.

  • @radiesadz1050
    @radiesadz1050 2 года назад

    Alhamdulillah..kongsi ilmu..Terbaik cikgu..

  • @akusuk
    @akusuk 11 месяцев назад

    20:43 kabel 4mm boleh cover up to 3570 watt

  • @muhamadamzar2095
    @muhamadamzar2095 2 года назад

    Semoga Allah murah kan rezeki cikgu. Video terbaik untuk mula
    belajar.

    • @mrsaiful7776
      @mrsaiful7776  2 года назад +1

      Amin... tqvm👍🏻

    • @muhamadamzar2095
      @muhamadamzar2095 2 года назад

      Maaf cikgu tumpang tanya. Apa kesan kalau x guna rccb 10mA atau rcbo?

    • @muhamadamzar2095
      @muhamadamzar2095 2 года назад

      Satu lagi cikgu. Boleh x kalau x pakai connector? Direct ke suis dua kutub terus

  • @PersatuanPendudukPangsapuriSub
    @PersatuanPendudukPangsapuriSub 2 месяца назад

    Terbaik Tn.. 👍

    • @mrsaiful7776
      @mrsaiful7776  2 месяца назад

      Semoga bermanafaat utk semua, TQVM.

  • @syukurmakmur6222
    @syukurmakmur6222 8 месяцев назад

    Terimakasih banyak cikgu

  • @azizijmal5358
    @azizijmal5358 2 года назад +1

    Terbaik, cikgu..mudah faham

    • @mrsaiful7776
      @mrsaiful7776  2 года назад

      Terima kasih sudi singah 👍🏻

  • @Matir58.
    @Matir58. Год назад

    Terima kasih perkongsian wiring water Heather yg lebih baik dn selamat.

  • @hairulanuarahmad
    @hairulanuarahmad 2 года назад +1

    Terima Kasih Tuan Kongsi Ilmu..👍😎👍

  • @kyedowh
    @kyedowh Месяц назад

    Alhamdulillah. Terima kasih ilmunya tuan. Saya nak bertanya kalau rumah mempunyai lebih dari satu unit water heater, jadi rccb dan mcb tu pon kene tambah utk setiap satu unit water heater nya ke tuan?

  • @zsafuan
    @zsafuan 11 месяцев назад

    10 mA itu adalah rccb tu akan bertindak balas memutuskan litar (triggered @ 10mA residual current) jika ada leakage 10mA

  • @zaheredge5998
    @zaheredge5998 Год назад +2

    Salam tuan...boleh tak buat pendawaian untuk water pump .start Dari DB

  • @nizamnizam5540
    @nizamnizam5540 2 года назад

    Channel terbaik

  • @RHJ2023
    @RHJ2023 2 года назад +1

    Padu la tuan pul... Tp tula mcm bnyk lak prosesnye utk power sampai ke water heater ... 😅

    • @mrsaiful7776
      @mrsaiful7776  2 года назад +1

      Tu semua utk keselamatan kita atau org tersayang 🤗.

  • @LeeMooEez
    @LeeMooEez 2 года назад

    Belajar sini lagi senang paham dari masa study dulu wkakakah🤣🤣🤣

    • @mrsaiful7776
      @mrsaiful7776  2 года назад

      Jgn mcm tu tuan, dulu masa belajar benda ni kita masih baru dlm bidang ni tu yg rasa susah, tapi bila tuan dah ada asas kita tngok skit pn kita dah tahu.
      Tq sudi sungah 👍🏻

  • @mohammadnazmeerkhidzir8543
    @mohammadnazmeerkhidzir8543 2 года назад +2

    Harap cikgu belanja video kawalan moto seperti dol,star delta fwrd reverst,auto tran😅

    • @mrsaiful7776
      @mrsaiful7776  2 года назад

      Insyakallah, dlm proses boh 👍🏻

  • @azamab
    @azamab Год назад

    Terbaik..nak kena tengok balik

  • @alpocot67
    @alpocot67 2 месяца назад

    Terima kasih atas penerangan yang sangat jelas!!! Setiap heater perlu RCCB yang berasingan cikgu?

    • @mrsaiful7776
      @mrsaiful7776  2 месяца назад

      Ya, 1 RCCB 10mA = 1 pemanas air

  • @boroideboroiabis2241
    @boroideboroiabis2241 11 месяцев назад

    Assalam Mr Saiful. One question. ST stipulates that 4.0mm cable is the minimum requirement. In your video between the connector and the water heater you have used a 3 core cable. Where can we find a 3 core cable with minimum 4.0mm thickness. Thank you for your video.

  • @boroideboroiabis2241
    @boroideboroiabis2241 Год назад +1

    Salam Mr Saiful, pardon my ignorance, but would it make any difference if we do not install the connector, just pull the wiring direct from the 2 Pole 20Amp Switch to the water heater. Esp since there appears to be no fuse in the connector, just the 3 connectors. So its of little use.
    Thank you Sir.

    • @boroideboroiabis2241
      @boroideboroiabis2241 Год назад +1

      Another question Sir, since the cable size from the 10mA RCCB to the water heater unit is 4.0 mm in size, would it make any difference if the cable from the 20A MCB to the RCCB is only of 4.0mm size instead of the 10.0 mm size as you had shown, considering thats the max power from the RCCB to the heater unit only requires 4.0 mm cables.
      Thank you Sir.

  • @hakimfadzil9459
    @hakimfadzil9459 Год назад +1

    Wayar kelabu dari suis 2 kutub ke water heater tu boleh panjang berapa jauh?

  • @surkezz
    @surkezz 2 года назад +1

    Penerangan yang sangat lengkap. Nak tanya, setahu saya RCBO tu gabungan RCBB dengan MCB. Bukan ke kalau sambung ke RCBO, x perlu sambung ke MCB?

    • @mrsaiful7776
      @mrsaiful7776  2 года назад +1

      Ya betul dah tu RCBO = RCCB+MCB, jadi nak pasang mcn 20a boleh atau taknak pasang mcb 20a pn boleh ikut kesesuaian / keadaan tempat dan ikut yg mana lebih mudah utk kita buat penyambungan, tq sudi singah 👍🏻

    • @bontotayam8477
      @bontotayam8477 2 года назад

      Owh rcbo xpayah sambung la dgn mcb 20tu..so sambung dr mana suis utama ke?

    • @mrsaiful7776
      @mrsaiful7776  2 года назад

      @@bontotayam8477RCBO kena lalu RCCB 100ma, baru boleh smbung ke RCBO, selepas RCCB tu lah MCB jadi MCB ni nak pakai boleh tak pakai pn boleh, ikut kesesuaian sambung wiring kita.

    • @bontotayam8477
      @bontotayam8477 Год назад

      @@mrsaiful7776 owh bermakna kalau xnak pakai rccb 10mA dan mcb 20A,kita join rcbo dekat rrcb 100mA litar pencahayaan tu kan,ambik dekat busbar c6 boleh jgk kan..

  • @ultramantiganosekai
    @ultramantiganosekai 2 года назад

    Nanti buat video contest mengenai pendawaian & penggunaan soket 13A litar kuasa sesuai untuk pa system

    • @mrsaiful7776
      @mrsaiful7776  2 года назад

      Utk pa system guna 13A gelang atau jejari je bos.

  • @muhammad8741
    @muhammad8741 Месяц назад

    kalau fius semua dh penuh, just beli rcbo tambah je ke? x perlu dh beli mccb c20 tu?

  • @CikguSarid
    @CikguSarid 2 года назад

    Terbaik Pok Mat

  • @ruslankhairuddin2590
    @ruslankhairuddin2590 5 месяцев назад

    Terbaik

  • @amiamenet8764
    @amiamenet8764 Месяц назад

    Sehingga kini (2024), adakah soket 15A boleh digunakan utk aircon?

  • @syahirhir1470
    @syahirhir1470 2 года назад

    Terima kasih cikgu

    • @mrsaiful7776
      @mrsaiful7776  2 года назад

      Terima kasih juga sudi singah 👍🏻

  • @niezam1729
    @niezam1729 2 года назад

    Diharamkan tu ..🤘

    • @mrsaiful7776
      @mrsaiful7776  2 года назад

      🤭🤭🤭
      Tq sudi singah 👍🏻

  • @jamilhashimhassan7581
    @jamilhashimhassan7581 Месяц назад

    Salam tuan, rumah sewa saya tuan rumah pakai mcb c32. Max water heater baru saya 16amp je. Dan wiring lama tak ada rccb/rcbo. Boleh ke pakai mcb c32 tu? Kalau ok saya nak tambah rccb/rcbo berapa?

  • @AiC36
    @AiC36 2 года назад +1

    kasi on ....mantap ni

  • @mohdaizuddin4630
    @mohdaizuddin4630 Год назад

    terima kasih tuan

  • @syanofa_pelbagai_ilmu
    @syanofa_pelbagai_ilmu 2 года назад

    Tolong buatkan video bang mcm mna mnukar wat kepada hours power

    • @mrsaiful7776
      @mrsaiful7776  2 года назад

      1 hp = 746watt
      atau tekan je link 👇🏻👇🏻👇🏻
      www.menukar-unit.info/menukar+Watt+kepada+Kuasa+kuda.php

  • @mrsjuliyaahamdani8434
    @mrsjuliyaahamdani8434 Год назад

    Dari suis 2 kutub,boleh terus direct ke w,heater ke tuan? Xpyah pakai connecter?

  • @HasrulHasrul-t4u
    @HasrulHasrul-t4u Год назад

    Assalam tuan,nak tanye dlm water heater dah including elcb,perlu ke Kita tambah rccb 10 ma/rcbo 10ma lagi?

  • @azizyusop4883
    @azizyusop4883 Год назад

    Assalamualaikum bang .tlg tunjuk tutorial nk buat suis ON/OFF pada kipas dinding tanpa plug in ke soket ..

  • @ehsanmuri8898
    @ehsanmuri8898 Год назад

    Ape akan jadi kalau tak guna connector? Bagaimana kalau sambung direct kpd suis je?

  • @shaiful831
    @shaiful831 Год назад

    Owh br tgk kena pakai connector tu,br ni psang umah mak,adik beli brand apa ntah wter heater,dtg skali dgn connector mcm dlm video

  • @ashleyhee827
    @ashleyhee827 2 года назад +1

    Salam MR SAIFUL 77 ,terbaik vedio . Saya ada satu soalan ? Saya nak tanya Kalau tak pakai coneter terus masuk ke water heater boleh tak ?

    • @mrsaiful7776
      @mrsaiful7776  2 года назад +2

      Salam.
      Boleh, tapi suis 2kutub tu kena adalah.

    • @ashleyhee827
      @ashleyhee827 2 года назад

      Ok, faham terbaik

  • @Hammett849
    @Hammett849 Год назад +3

    Thanks for your excellent explanation. I think so far this is the best guide for water heater installation. I did some research and I am convinced that RCBO/RCCB with higher sensitivity say 30ma (versus 10ma) would provide much better protection against risk of electrocution caused by faulty heater. This is due to much lower threshold given when residual imbalance detected and trip can happen much early. Do you concur?

    • @mrsaiful7776
      @mrsaiful7776  Год назад +4

      10ma for wet places
      30ma for power circuits,
      Both have their own functions, and usually this 10ma is more sensitive sir
      Thank you for your support 🤞

    • @Hammett849
      @Hammett849 Год назад +1

      @@mrsaiful7776 Thank you.

    • @Hammett849
      @Hammett849 Год назад +4

      @@mrsaiful7776 I found this QA section in an online article interesting. Maybe you have some insights to share with.
      Why is the 30mA RCCB circuit breaker more suitable for houses and home?
      The 30mA trip current of RCCB is determined according to the human body’s ability to withstand current and its duration.
      The human body can tolerate smaller currents for a long time and tolerate larger currents in a shorter period of time.
      According to the test results, 30mA is considered to be a suitable and safe leakage protection circuit breaker for household use.
      The low-sensitivity type leakage protector with leakage action current value of 50mA and above cannot be used as household leakage protection.
      So, can we use the 10mA RCCB in the household? The answer is: There are certain problems, it is easy to malfunction, and also affect normal use.
      It can be seen that the 30mA specification is the best. It can not only achieve effective preventive electric shock protection but also take into account the direct contact click protection.

    • @boroideboroiabis2241
      @boroideboroiabis2241 Год назад +1

      Just wondering, as you have said 30mA RCCB is the preferred size. Any plausible reasons why airconds and water heaters which are power hungry be on the 100mA circuit instead of the 30mA circuit? In fact the water heater is required to have 10mA RCCB which is closer to the 30mA circuit.
      For that matter why not all circuits, power and lighting, be connected just to the 30mA circuit, a more sensitive and safer RCCB. Saves cost without the 100mA too.

    • @zsafuan
      @zsafuan 11 месяцев назад

      ​@@mrsaiful777630mA utk handheld devices mcm grinder dan drill. Seandainya ada residual current yg leak pada 30mA rccb akan bertidak memutus litar
      Tapi ia x sesuai.dlm enviroment devices bermotor cth dlm lab spt

  • @amiruladliabdaziz9069
    @amiruladliabdaziz9069 11 месяцев назад

    Terima kasih tuan atas perkongsian.. sy sedang bercadang untuk memasang water heater... DB box sy nampak macam dah ada RCCB 10mA tp 16A, bukan 20A or 25A mcm dalam video.. wiring dan suis 2 kutub semua sudah ada, tinggal nak dapatkan connector shj.. masih boleh proceed ke tuan? water heater sy 3.8kW..

  • @pakda
    @pakda Год назад

    Cantik...

  • @redzuanmalik568
    @redzuanmalik568 5 месяцев назад

    Dr mcb ke rcbo cable wajib 10mm kalau 4mm tak boleh ke?

  • @JSkids69
    @JSkids69 2 месяца назад

    Assalamualaikum cikgu..
    Jika Waterheater 3.8kW kena guna cabel 6mm ke?

  • @harunhm9214
    @harunhm9214 2 года назад +1

    Terbaik video ni.... nak tanye, cable jumper yg sesuai masok incoming RCCB 10mA tu pakai size brapa.
    4mm ke?

    • @mrsaiful7776
      @mrsaiful7776  2 года назад +1

      Bergantung pada load/beban tuan, kalau beban rendah guna 6mm tapi kalau beban tinggi guna 10mm dan keatas.

    • @PCleo
      @PCleo Год назад

      @@mrsaiful7776 oh, bukan ikut saiz cable yang masuk ke suis 20A kah, iaitu 4mm?

  • @ayieeazri
    @ayieeazri Год назад

    Salm bang..klau simulasi dri db. Rcbo👉 ke suis 2 kutub👉dan trus ke lond tangki air pnas boleh x.. x pyah pkai cnntor. Blh x... Sbb sy pkai tangki wter hter.. x pkai yg wter hter pncut..

    • @mrsaiful7776
      @mrsaiful7776  Год назад

      salam,
      Boleh tuan, cnntor tu ganti pada soket 15A je, tujuan soket/cnntor tu untuk memudahkan kita nak servis / nak baiki je.

  • @salhahsuhot
    @salhahsuhot Год назад

    Kira kalau technician dah pasang soket, kena tukar pada connector lah?

  • @hoihaihoi
    @hoihaihoi Год назад

    Terbaek tuan. Soalan saya.. Selamat tak kalo 10 mA rcbo itu dipasang bukan kat dB tapi ditempat sblm suis 2 kutub tu... Saya tanya demikian sbb slot db saya dah penuh dan terpaksa tukar kotak baru kalo ikut cara diatas....

  • @zulhabirjul2873
    @zulhabirjul2873 2 года назад

    Mantap tuan

  • @ahm8084
    @ahm8084 Год назад

    Terima kasih atas penerangan tuan, kalau untuk oven yang besar caranya sama juga ke.. ambik dari MCB litar cahaya ... cuma tidak perlu RCCB 0.01A.. betul ke?

  • @zainalbos
    @zainalbos 8 месяцев назад

    TERBAIK SIFU

  • @Fauzi91-t1h
    @Fauzi91-t1h 2 года назад

    tuan minta tunjuk cara pasang contactor dan delay untuk motor 3 fasa..bagaimana pemasangannya dari db pergi ke motor

    • @mrsaiful7776
      @mrsaiful7776  2 года назад

      Dlm proses

    • @adiwira1351
      @adiwira1351 Год назад

      ​@@mrsaiful7776 ada video khusus ttg kelebihan dan kekurangan tiga fasa atau fasa tunggal dalam setiap pembinaan rumah ...

  • @mdjab7234
    @mdjab7234 2 года назад

    👍Terbaik tuan.

  • @Hammett849
    @Hammett849 Год назад +1

    Since RCBO is a combination of RCCB and MCB, may I know is there any particular reason(s) for redundant MCB connection as described in your video section installation with RCBO?

    • @mrsaiful7776
      @mrsaiful7776  Год назад +1

      for RCBO installation (mcb is not required) but for easy cable connection (for me) sir

    • @miscthings2559
      @miscthings2559 Год назад

      @@mrsaiful7776 I see a lot of youtuber/electrician says to wire RCBO to MCB. Should the RCBO be connected to an independent neutral bar to avoid 'nuisance tripping'?

  • @abusofia6633
    @abusofia6633 2 года назад +1

    susah nak cari suis base connector macam cikgu tunjuk jenis alpha tu...

    • @mrsaiful7776
      @mrsaiful7776  2 года назад

      ada je dikedai elektrik,
      atau banyak dikedai online
      shopee.com.my/Alpha-Splashproof-Waterproof-Water-Heater-Connector-with-Wire-i.67479754.13213855485?sp_atk=9511706a-5050-4d84-80dc-f50f493df345&xptdk=9511706a-5050-4d84-80dc-f50f493df345

    • @abusofia6633
      @abusofia6633 2 года назад

      @@mrsaiful7776 kawasan saye xde..penah cari dah bln-bln sblm ni..

  • @tokjanggut9143
    @tokjanggut9143 9 месяцев назад

    Kalau live rcbo tarik dr incoming mcb boleh x tuan...bukan dr outgoing mcb...

  • @St_1164
    @St_1164 Год назад

    As salam Tuan,
    Mintak pencerahan sedikit.
    Apa maksud nya tulisan pada cable " 3C x 23/0.16mm " .
    Terima kasih & selamat hari raya aidil fitri.

    • @mrsaiful7776
      @mrsaiful7776  Год назад +1

      Salam.
      Wau... ni soalan pw4 ni.
      3c = 3core
      23 = 23 lembar
      0.16 = diameter lembar

  • @mohamadhasrulnizam8991
    @mohamadhasrulnizam8991 Год назад

    Rumah saya dah ada lama WH tapi just guna MCB biasa so saya dah beli RCBO, nak remove MCB lama tu ganti tempat dia dgn RCBO, masalah saya mcm mana nak cari Neutral outgoing ikut wiring lama tu? Jenuh sy fikir and menung sorang². LIFE memang ready kat situ sbb MCB 1pole yg Neutral wiring lama tu mcm mana nak cari untuk tarik ke outgoing RCBO baru tu.

    • @mrsaiful7776
      @mrsaiful7776  11 месяцев назад

      Mudah je, boleh guna buzzer, testlamp, multimeter.
      Caranya
      1. Sambungkan atau pintaskan kabel bumi dgn kabel neutral pada W/H
      2. Buka semua kabel neutral pada DB sebelum tu *(offkan main suis@ buka fius TNB)
      3. Test guna buzzer @ meter diantara kabel bumi dgn kabel neutral yg kita buka tadi sehingga ada bunyi buzzer @ ada bacaan pada meter *kabel bumi x perlu buka semua
      Semoga berjaya 👍

    • @prince_camp
      @prince_camp 5 месяцев назад

      ⁠@@mrsaiful7776kalau xda peralatan seperti yg tuan nyatakan di ats, ada cara lain x utk cari cable neutral tersebut?