It was good informative video that who worked in instrumentation filed especially in fild side.if you possible plse put more different type of positioner configuration and caliberation. For instance azbil
Sir, Thank you very much for your appreciation. I'm glad that my small video is helping thousands of people across the globe which was my main Moto for this upload.
Sir EK problem Araha Hai valve auto calibration karne ke baad bhi valve 20 % hai aur command bhi 20 % araha Hai auto mode me lekin dcs me 0%show kar raha Hai valve kya karun ki valve fully close hojayye valve hamara fail to close Hai
@@jayyadav9412 Parameter No. 7 For command and Parameter No. 37 for feedback. But It may be different for Single/Double Acting or Profibus Smart Positioner. Therefore please check Model No. of your positioner and refer to instruction manual which comes along with Positioner.
It's upper limit or open limit is not in the range that's why that error arises. So adjust the feedback positioner link with control valve and adjust in open condition with the help of friction clutch gear available on positioner.
Press & hold “ - ” button and note that control valve is fully closed, set it as your “ Yend 1 limit”. Similarly, press & hold “ + ” button and note that control valve is fully opened. This will be your “ Yend 2 limit”.
Auto mode me bhi kar sakte hai. Parameter no. 4 access karke “ + ” button Ko 5 seconds k liye hold karo to auto calibration start ho jayega. Also I had made a seperate video for auto calibration procedure so please watch that stuff on my RUclips channel. Thanks
after a manual calibration, i am getting a negative number on the positioner display because the valve is seating which is desired but the negative number is not. How do i make the display read zero when going under the lower set point of the manual calibration?? Please Help!
Your Positioner is mounted on which system i.e. Air to open/close actuator or power cylinder? Case 1: If ‘Air to Close’ type pneumatic actuator then check air pressure and ensure that it does not exceed specified limit. Case 2 : If power cylinder then you adjust through cushioning screw. And then repeat manual calibration procedure as explained in this video.
@@shantilaldhakar9967 it is a fail to close valve. On a diaphragm actuating control valve. The system set points requires the valve to jump up to 20% open as soon as any Ma signal is applied. So the valve was manually calibrated to set the lower limit to that 20% open so when Ma is applied it would automatically go to 20% open and achieve desired set points. Since the new 0% is manually calibrated to 20% open and the positioner closes the valve all the way to its seat once it gets the close signal. the display will read a negative number now because it thinks it is -20% to the seat. I was wondering if there is any way to zero that number out on the display or a better way to set up that valve to be able to achieve those set points. Thanks for the Help.
Sir ek problem hai 100% command pe 66 % arha hai... Input Kya kare 12 no parameters me ja ke chenge kar ke dekh liya par ho nahi rha . Please iska kya problem hai btae
Check air leakage after positioner output from tube joints and actuator diaphragm. If this check is found normal then check the feedback positioner link connection. It may be loose or very tight so adjust link and properly tight again. After all that please make positioner calibration, I think your problem will get resolved.
In case of linear actuators, if valve stroke is less than 20 mm then we select 33° transmission ratio else for valve stroke more than 20 mm we select 90°.
Check your actuator specification and if it is air to close type actuator then set air pressure. Also, you may set pressure 5-10% higher than rated pressure. Secondly, if above things checked and ok but problem not resolved then ensure that actuator spring tension is ok or not. It may be due to high spring tension of actuator so adjust it properly. 👍
Error in RUN 1 means either actuator/power cylinder is jammed or air pressure is not sufficient. Please check air pressure, pressure seal condition and jamming of valve/actuator.
@@mrinmoysahoo8626 RUN 4 : Positioner check and determine the minimum increment length so if error means there may be air leakage through actuator/power cylinder pressure seal parts. Please check and ensure that their is no any such leakages. 👍
Dear friend, RUN 4 step during calibration “ Determine the minimum increment length ” means positioner will increment command by smaller fractions in decimal points & simultaneously check feedback and if it doesn't match then positioner stucks in RUN 4. Solution:: (A) There may be leakage from fittings/diaphragm so check all fitting tightness. (B) The position FB link may be loose so check tightness. And then calibrate again you will definitely success. Thanks for your query and I hope this information helps you a lot.
Please adjust the zero and span range and accordingly it's feedback too. The difference must be greater than 80% and then calibrate using above explained procedure. Thanks buddy
Operate the valve using + & - buttons on positioner and set Feedback 0 at zero check and atleast 80 to 86 at span check. Then calibrate the positioner in auto/manual mode.
Hunting problem caused due to these possibilities :: 1. Instrument air pressure drop after positioner output by any means including ALR failure or air leakage problem. 2. If the spring tension is loose than required then it happens. Thanks for appreciation and query.
Check parameter No. 7 and 38. If position feedback is just reverse then change parameter no. 38 from rise to fall and vice versa. And if command signal is reverse then change parameter no. 7 as explained above. I hope you got solution, further feel free to contact if you have any query. Thanks
Please check perameter no. 7 & 38 both parameters must be selected “ rise ” instead of “ Fall ” and then calibrate in manual mode as described in this video. I hope your problem will be resolved.
बहुत बहुत धन्यवाद भैया ये वीडियो बहुत helpful ह मेरे लिए ओर भी वीडियो बनाओ
God bless u sr💐💐
शुक्रिया, आपका आशिर्वाद बना रहे 🙏🙏
@@shantilaldhakar9967 भगवान से प्राथना करते ह आप हमेशा तरक्की कर ऐसे ही लोगो का भला करते रहे हेल्प करते रहे🙏💐😊
Excellent Sir & Very Thanks for showing how to calibrate Siemens Sipart PS 2 Positioner.
Very Thanks Sir.
💐💐💐💐💐💐💐🙏🙏🙏🙏🙏🙏🙏
Thanks for appreciation 👍
Bahut sundar explanation thank you sir 🙏🙏
Good morning Sir,...🎉 Udaipur se
@@SNMandal-j4n good morning
Thank you very much for great video
Good work bhai
Very good video
Thank you so match
Thanks for appreciation 😊
Thanks ji for good posted. please do more videos on Siemens positioner troubleshootings also.
Thanks for appreciation and I will accept your feedback regarding video on troubleshooting.
Thanks again...
Very Good &Knowledgeable Video.👍👍👍👍👍💐💐💐💐💐🙏🙏🙏🙏
Thank you for the video
Thank you my friend..good job and very useful information
Sir, nicely explained, impressive. Keep doing such great work
Thank you so much for your appreciation.
Thank you very much . Good information.
excellent and so more helpful presentation
Thanks for appreciation. It means a lot for me 🙏
Nice representation, done the same and valve was properly calibrated
Thanks
Comprehensive! Thank you sir..
You are welcome
Plz ...any vacancy for Instrument technician I am diploma in instrumentation and control engineering with 8year experience.plz give me your WhatsApp number...Pravin CHAVDA Gujarat Jamnagar
It was good informative video that who worked in instrumentation filed especially in fild side.if you possible plse put more different type of positioner configuration and caliberation. For instance azbil
Thanks brother for appreciation.
Wa. Bhai .. Superb....
Thanks
Thank you helpful video
Thanks a lot. nice presentation. (y)
Sir, Thank you very much for your appreciation.
I'm glad that my small video is helping thousands of people across the globe which was my main Moto for this upload.
Open karne keliye EK button ya do boton EK sath push karna zaruri Hai kya
Single button se slowly open hoga
and Two buttons ek sath press karne se fast open hoga.
@@shantilaldhakar9967 thank you sir for reply
Sir EK problem Araha Hai valve auto calibration karne ke baad bhi valve 20 % hai aur command bhi 20 % araha Hai auto mode me lekin dcs me 0%show kar raha Hai valve kya karun ki valve fully close hojayye valve hamara fail to close Hai
Sir auto calibration me run 2 me fans jaraha aur P 8.1 uske niche fault ka symbol and up 1 show kar raha Hai kaise setting karenge
Valve is either jam or may not open/close properly.
There may be air leakage from seal/diaphragm in output side.
Check for these issues
Thank you sir 🙏
Sir feedback or command Ka kon sa no. Hai
.
@@jayyadav9412 Parameter No. 7 For command and Parameter No. 37 for feedback.
But It may be different for Single/Double Acting or Profibus Smart Positioner.
Therefore please check Model No. of your positioner and refer to instruction manual which comes along with Positioner.
V good one.
Sir Forbes Marshall positioner ka callibration ka video bnaeye
Zero karne ke liye bhi +ve and -ve button ek sath press kar rahe h and 100 karne ke liye bhi same kar rahe h ?
Action fast karne k liye Aisa Kiya ha.
+ve button press & hold and then press -ve button
In this way your action become fast.
Thank you 🙏, Nicely explained.
Thanks
auto caliberation ke time run2 me up 1 error dikha raha hai....kya problem ho sakta hai???
It's upper limit or open limit is not in the range that's why that error arises.
So adjust the feedback positioner link with control valve and adjust in open condition with the help of friction clutch gear available on positioner.
Thank you very much
Thanks bhai
Great job 👍
Thanks
y end 1&2 ka limit set krne k liye - aur + ko ek saath press krna he kya
Press & hold “ - ” button and note that control valve is fully closed, set it as your “ Yend 1 limit”.
Similarly, press & hold “ + ” button and note that control valve is fully opened. This will be your “ Yend 2 limit”.
Sir hm jb bhi esko calibrate karenge manual mode me le Jake hi krenge.auto me nhi Kar sakte hai kya
Auto mode me bhi kar sakte hai.
Parameter no. 4 access karke “ + ” button Ko 5 seconds k liye hold karo to auto calibration start ho jayega.
Also I had made a seperate video for auto calibration procedure so please watch that stuff on my RUclips channel.
Thanks
up and down dono saath me push karte ho , ye to bolte nhi ho
If positioner not operate in manual mode & not vary the opening percentage during manual command from positioner
Plz help & how to contact you
My contact number 8003228484
May be air supply pressure is not sufficient or control valve/actuator is mechanically jammed.
Thank you
You are welcome
Sir. Run 3 और run 5 क्या दिखाता है
Thanks for this video bt sipart ps2 all models calibration plz video make
Parameters ka video banaye plz
after a manual calibration, i am getting a negative number on the positioner display because the valve is seating which is desired but the negative number is not. How do i make the display read zero when going under the lower set point of the manual calibration?? Please Help!
Your Positioner is mounted on which system i.e. Air to open/close actuator or power cylinder?
Case 1: If ‘Air to Close’ type pneumatic actuator then check air pressure and ensure that it does not exceed specified limit.
Case 2 : If power cylinder then you adjust through cushioning screw.
And then repeat manual calibration procedure as explained in this video.
@@shantilaldhakar9967 it is a fail to close valve. On a diaphragm actuating control valve. The system set points requires the valve to jump up to 20% open as soon as any Ma signal is applied. So the valve was manually calibrated to set the lower limit to that 20% open so when Ma is applied it would automatically go to 20% open and achieve desired set points. Since the new 0% is manually calibrated to 20% open and the positioner closes the valve all the way to its seat once it gets the close signal. the display will read a negative number now because it thinks it is -20% to the seat. I was wondering if there is any way to zero that number out on the display or a better way to set up that valve to be able to achieve those set points. Thanks for the Help.
सर मैं जैसे ही End1 देकर hand press कर रहा हूं Range लिखा आ रहा है End 2नही आ रहा है क्या चेक करू
“Range”means your range selected in “End1” or “End2” is incorrect. Please set it inbetween 10% to 85% at zero and span respectively. 👍
Good sir
Sir ek problem hai 100% command pe 66 % arha hai... Input
Kya kare
12 no parameters me ja ke chenge kar ke dekh liya par ho nahi rha .
Please iska kya problem hai btae
Factory reset your positioner and then re-calibrate in manual mode. If you got any issue then feel free to comment regarding problem.
RESET :: Go to parameter no. 50 and then press and hold “+” button for 5 seconds. This action will factory reset your positioner.👍
@@shantilaldhakar9967 sir mere positioner me zero command dene pe 20% command aa rha h to kya problem hoga command zero nhi aa rha
🙏 Thanks 🙏
Eska full video dekhao with industry ka sir
AoA
sir my control valve ps2 positioner continue stuck on RUN 5 but not show finish option please giuide me
if stroke 20 mm then we select 90 or 30
but now i select 90 and selector switch on 90 same as follow in parameter 2 according to manual
@@sajidaziz2862 please select 33° angle and then lock that position at 33°.
ok i will try now
@@shantilaldhakar9967 sir but when we select 90??if stroke is more than 20??
@@shantilaldhakar9967 Thanks for guidelines my job is done.
Me Ra ek positioner auto/manual calibration nehi leraha he. Next Kia karunga
Please what's app your query/screenshot of error so that I may help you in a better way.
What's app number 8003228484
Positioner display is not getting power on ....22 v DC ... What will be the solution
If power is healthy then it's interface card may be faulty.
Solution: Contact to supplier/vendor for repairing/replacement.
Thnx via
Its my pleasure.
Nice
har waqt kya dono + aur - button ko press kar k karna padega...agar nahi to dono ungli se kyon chek dete ho...
Har waqt nhi,
Jab quick open ya close karna ho tabhi Aisa karn ha.
how can i attach a position feedback module?
How to solve hunting and overshoot problems. There is no tube leakage but also hunting.
Check air leakage after positioner output from tube joints and actuator diaphragm.
If this check is found normal then check the feedback positioner link connection. It may be loose or very tight so adjust link and properly tight again.
After all that please make positioner calibration, I think your problem will get resolved.
how to set her feedback deviation
Good job
Good
Sir ye 90°And 33 ° me kush samj nahi aa raha kush jyada jankari de sakte he please... Sir...
In case of linear actuators, if valve stroke is less than 20 mm then we select 33° transmission ratio else for valve stroke more than 20 mm we select 90°.
@@shantilaldhakar9967 ok thank you sir
Muje bi isme samaj nahi aaraha hy
Mera position reverse may kam kar rahahey kya karu
Check parameter no. 7 and select proper parameter i.e. “rise” or “fall”.
Your problem will be resolved.
@@shantilaldhakar9967 thanks
👍
19 mA mai 100% open karna hai to kya kare please batayiye
Tube ulta kardo
Cylinder ka bta rha
Sir mera actuator 0mm tk close nahi ho raha hai please help
Check your actuator specification and if it is air to close type actuator then set air pressure.
Also, you may set pressure 5-10% higher than rated pressure.
Secondly, if above things checked and ok but problem not resolved then ensure that actuator spring tension is ok or not.
It may be due to high spring tension of actuator so adjust it properly. 👍
Agar run 1 ya run 4 ma error ageya to kya karna chahiye
Error in RUN 1 means either actuator/power cylinder is jammed or air pressure is not sufficient.
Please check air pressure, pressure seal condition and jamming of valve/actuator.
@@shantilaldhakar9967 thanks
Or run 4 kya matlab hai
@@mrinmoysahoo8626 It's my pleasure to help you 😊
@@mrinmoysahoo8626 RUN 4 : Positioner check and determine the minimum increment length so if error means there may be air leakage through actuator/power cylinder pressure seal parts.
Please check and ensure that their is no any such leakages. 👍
Sir my calibration is running at run4 continuously is not going at run5 please help me
Dear friend,
RUN 4 step during calibration “ Determine the minimum increment length ” means positioner will increment command by smaller fractions in decimal points & simultaneously check feedback and if it doesn't match then positioner stucks in RUN 4.
Solution::
(A) There may be leakage from fittings/diaphragm so check all fitting tightness.
(B) The position FB link may be loose so check tightness.
And then calibrate again you will definitely success.
Thanks for your query and I hope this information helps you a lot.
What is meant by U- di error
means positioner feedback is inappropriate with respect to command signal.
futher you may adjust it by roller gear mounted just below display.
Siemens positioner ko kese single action karenga.?
Make one output lower side port dummy and connect connect control valve to the remaining port.
Vai step by step full process me video banaiye
If 41 blinking on screen then what will do
Check the Instrument air pressure, if it is not sufficient to open/close valve then this error occurred 👍
VEnd2 ke baad Range ka option aa rha hai , calibration nhi hota hai ,,kya kru bataye
Please adjust the zero and span range and accordingly it's feedback too.
The difference must be greater than 80% and then calibrate using above explained procedure.
Thanks buddy
Operate the valve using + & - buttons on positioner and set Feedback 0 at zero check and atleast 80 to 86 at span check.
Then calibrate the positioner in auto/manual mode.
@@shantilaldhakar9967 span and zero kaise set kare? Hindi me bataye sir
@@shantilaldhakar9967 Jab Range ka Option aata hai us time + button press karne se Vend2 aa jata hai fir se
how to adjust the display contrast ?
please share details/model no. of your Siemens positioner.
It will be like “ 6DR5051 or 6DR5052” .
I had gone through the positioner manual but did not find any information about contrast control.
FYI 👍
I have confusion for parameter 7 and 38 could anyone can explain please.
Feedback kaise set krenge
Using rotary cluch , located just below display
Good brother what about hantting
Hunting problem caused due to these possibilities ::
1. Instrument air pressure drop after positioner output by any means including ALR failure or air leakage problem.
2. If the spring tension is loose than required then it happens.
Thanks for appreciation and query.
Yar agir new install karna hai tu kary ga
Same procedure will be followed for newly installed positioner.
Please share your email ID so that I may help you by providing sufficient documents.
Thanks
alijee.aj137@gmail.com
1 error cord haya sir aap ky harna
0 jaga pe 100%dikhae और 100 % जगा 0 dekha to kya karne ka
केवल फीडबैक गलत आ रहा है या कंट्रोल रूम से कमाण्ड ही गलत आ रही है।
Check parameter No. 7 and 38.
If position feedback is just reverse then change parameter no. 38 from rise to fall and vice versa.
And if command signal is reverse then change parameter no. 7 as explained above.
I hope you got solution, further feel free to contact if you have any query.
Thanks
Bhai maan ge chorre
Control valve mera open hai to zero dikha raha hai.. Or close hone par 100 dikha raha esa kyu
Please check perameter no. 7 & 38 both parameters must be selected “ rise ” instead of “ Fall ” and then calibrate in manual mode as described in this video.
I hope your problem will be resolved.
Yes correct ji.
Friend if possible English language
Can you learn me sir ji
Sure 👍
kavi kavi error aati h calibration nhi leta h wo
Try manual calibration procedure.
Check operation in manual mode.
Good work
Thanks
thank you
Good