Siemen's SIPART PS2 Manual Calibration ! SIPART PS2 Calibration in Hindi

Поделиться
HTML-код
  • Опубликовано: 29 ноя 2024

Комментарии • 168

  • @Ram-sx5mv
    @Ram-sx5mv 4 года назад +2

    बहुत बहुत धन्यवाद भैया ये वीडियो बहुत helpful ह मेरे लिए ओर भी वीडियो बनाओ
    God bless u sr💐💐

    • @shantilaldhakar9967
      @shantilaldhakar9967  4 года назад +1

      शुक्रिया, आपका आशिर्वाद बना रहे 🙏🙏

    • @Ram-sx5mv
      @Ram-sx5mv 4 года назад +1

      @@shantilaldhakar9967 भगवान से प्राथना करते ह आप हमेशा तरक्की कर ऐसे ही लोगो का भला करते रहे हेल्प करते रहे🙏💐😊

  • @vinaysane5435
    @vinaysane5435 Год назад +1

    Excellent Sir & Very Thanks for showing how to calibrate Siemens Sipart PS 2 Positioner.
    Very Thanks Sir.
    💐💐💐💐💐💐💐🙏🙏🙏🙏🙏🙏🙏

  • @sohankumarsahu1764
    @sohankumarsahu1764 18 дней назад

    Bahut sundar explanation thank you sir 🙏🙏

  • @SNMandal-j4n
    @SNMandal-j4n 23 дня назад

    Good morning Sir,...🎉 Udaipur se

  • @pareshrathod1482
    @pareshrathod1482 4 года назад +1

    Thank you very much for great video
    Good work bhai

  • @Hewagej
    @Hewagej 3 года назад +1

    Very good video
    Thank you so match

  • @kishoreKumar-wt4vi
    @kishoreKumar-wt4vi 5 лет назад +1

    Thanks ji for good posted. please do more videos on Siemens positioner troubleshootings also.

    • @shantilaldhakar9967
      @shantilaldhakar9967  5 лет назад

      Thanks for appreciation and I will accept your feedback regarding video on troubleshooting.
      Thanks again...

  • @vinaysane5435
    @vinaysane5435 Год назад

    Very Good &Knowledgeable Video.👍👍👍👍👍💐💐💐💐💐🙏🙏🙏🙏

  • @Marafeq344
    @Marafeq344 2 года назад +2

    Thank you for the video

  • @sreenubabu6488
    @sreenubabu6488 4 года назад

    Thank you my friend..good job and very useful information

  • @unfilteredwithprakash6970
    @unfilteredwithprakash6970 4 года назад

    Sir, nicely explained, impressive. Keep doing such great work

  • @sureshkumarverma5094
    @sureshkumarverma5094 3 года назад

    Thank you very much . Good information.

  • @mr.nizamulhoq851
    @mr.nizamulhoq851 4 года назад

    excellent and so more helpful presentation

  • @waqashabib1674
    @waqashabib1674 5 лет назад +2

    Nice representation, done the same and valve was properly calibrated

  • @vthls
    @vthls 5 лет назад

    Comprehensive! Thank you sir..

    • @shantilaldhakar9967
      @shantilaldhakar9967  5 лет назад

      You are welcome

    • @pravinchavda9226
      @pravinchavda9226 5 лет назад

      Plz ...any vacancy for Instrument technician I am diploma in instrumentation and control engineering with 8year experience.plz give me your WhatsApp number...Pravin CHAVDA Gujarat Jamnagar

  • @manikr9465
    @manikr9465 4 года назад +1

    It was good informative video that who worked in instrumentation filed especially in fild side.if you possible plse put more different type of positioner configuration and caliberation. For instance azbil

  • @himmatgarg2239
    @himmatgarg2239 5 лет назад

    Wa. Bhai .. Superb....

  • @BhagwanSingh-sv3kh
    @BhagwanSingh-sv3kh 2 года назад

    Thank you helpful video

  • @rajeshsinghcimac
    @rajeshsinghcimac 5 лет назад +1

    Thanks a lot. nice presentation. (y)

    • @shantilaldhakar9967
      @shantilaldhakar9967  5 лет назад

      Sir, Thank you very much for your appreciation.
      I'm glad that my small video is helping thousands of people across the globe which was my main Moto for this upload.

  • @haidarquarrar8848
    @haidarquarrar8848 3 года назад

    Open karne keliye EK button ya do boton EK sath push karna zaruri Hai kya

    • @shantilaldhakar9967
      @shantilaldhakar9967  3 года назад

      Single button se slowly open hoga
      and Two buttons ek sath press karne se fast open hoga.

    • @haidarquarrar8848
      @haidarquarrar8848 3 года назад

      @@shantilaldhakar9967 thank you sir for reply

    • @haidarquarrar8848
      @haidarquarrar8848 Год назад

      Sir EK problem Araha Hai valve auto calibration karne ke baad bhi valve 20 % hai aur command bhi 20 % araha Hai auto mode me lekin dcs me 0%show kar raha Hai valve kya karun ki valve fully close hojayye valve hamara fail to close Hai

  • @haidarquarrar8848
    @haidarquarrar8848 Год назад

    Sir auto calibration me run 2 me fans jaraha aur P 8.1 uske niche fault ka symbol and up 1 show kar raha Hai kaise setting karenge

    • @shantilaldhakar9967
      @shantilaldhakar9967  Год назад

      Valve is either jam or may not open/close properly.
      There may be air leakage from seal/diaphragm in output side.
      Check for these issues

  • @jayyadav9412
    @jayyadav9412 3 месяца назад

    Thank you sir 🙏
    Sir feedback or command Ka kon sa no. Hai
    .

    • @shantilaldhakar9967
      @shantilaldhakar9967  3 месяца назад

      @@jayyadav9412 Parameter No. 7 For command and Parameter No. 37 for feedback.
      But It may be different for Single/Double Acting or Profibus Smart Positioner.
      Therefore please check Model No. of your positioner and refer to instruction manual which comes along with Positioner.

  • @mohammedabdulsaleem3302
    @mohammedabdulsaleem3302 Месяц назад +1

    V good one.

  • @pushpasahu1910
    @pushpasahu1910 4 года назад

    Sir Forbes Marshall positioner ka callibration ka video bnaeye

  • @SonuKumar-ju2ok
    @SonuKumar-ju2ok 6 месяцев назад

    Zero karne ke liye bhi +ve and -ve button ek sath press kar rahe h and 100 karne ke liye bhi same kar rahe h ?

    • @shantilaldhakar9967
      @shantilaldhakar9967  6 месяцев назад

      Action fast karne k liye Aisa Kiya ha.

    • @shantilaldhakar9967
      @shantilaldhakar9967  6 месяцев назад

      +ve button press & hold and then press -ve button
      In this way your action become fast.

  • @abhijitpadhiary4349
    @abhijitpadhiary4349 3 года назад +1

    Thank you 🙏, Nicely explained.

  • @vipulgp9843
    @vipulgp9843 5 лет назад +1

    auto caliberation ke time run2 me up 1 error dikha raha hai....kya problem ho sakta hai???

    • @shantilaldhakar9967
      @shantilaldhakar9967  5 лет назад

      It's upper limit or open limit is not in the range that's why that error arises.
      So adjust the feedback positioner link with control valve and adjust in open condition with the help of friction clutch gear available on positioner.

  • @aamirkh4064
    @aamirkh4064 3 года назад

    Thank you very much

  • @sunilrathod663
    @sunilrathod663 Год назад +1

    Thanks bhai

  • @kunalpareta5908
    @kunalpareta5908 3 года назад

    Great job 👍

  • @402san
    @402san 5 лет назад

    y end 1&2 ka limit set krne k liye - aur + ko ek saath press krna he kya

    • @shantilaldhakar9967
      @shantilaldhakar9967  5 лет назад

      Press & hold “ - ” button and note that control valve is fully closed, set it as your “ Yend 1 limit”.
      Similarly, press & hold “ + ” button and note that control valve is fully opened. This will be your “ Yend 2 limit”.

  • @mdfarhan3259
    @mdfarhan3259 5 лет назад

    Sir hm jb bhi esko calibrate karenge manual mode me le Jake hi krenge.auto me nhi Kar sakte hai kya

    • @shantilaldhakar9967
      @shantilaldhakar9967  5 лет назад +2

      Auto mode me bhi kar sakte hai.
      Parameter no. 4 access karke “ + ” button Ko 5 seconds k liye hold karo to auto calibration start ho jayega.
      Also I had made a seperate video for auto calibration procedure so please watch that stuff on my RUclips channel.
      Thanks

  • @Diwa94
    @Diwa94 Год назад +3

    up and down dono saath me push karte ho , ye to bolte nhi ho

  • @RamSingh-nj8mr
    @RamSingh-nj8mr 2 года назад

    If positioner not operate in manual mode & not vary the opening percentage during manual command from positioner
    Plz help & how to contact you

    • @shantilaldhakar9967
      @shantilaldhakar9967  2 года назад

      My contact number 8003228484

    • @shantilaldhakar9967
      @shantilaldhakar9967  2 года назад +1

      May be air supply pressure is not sufficient or control valve/actuator is mechanically jammed.

  • @dalimnath614
    @dalimnath614 4 года назад +1

    Thank you

  • @lakhendrabaghmar7261
    @lakhendrabaghmar7261 4 месяца назад

    Sir. Run 3 और run 5 क्या दिखाता है

  • @soumyaranjanjilu7816
    @soumyaranjanjilu7816 2 года назад

    Thanks for this video bt sipart ps2 all models calibration plz video make

  • @jitendrakumarsahu4087
    @jitendrakumarsahu4087 5 лет назад +1

    Parameters ka video banaye plz

  • @thomaselsen1672
    @thomaselsen1672 2 года назад

    after a manual calibration, i am getting a negative number on the positioner display because the valve is seating which is desired but the negative number is not. How do i make the display read zero when going under the lower set point of the manual calibration?? Please Help!

    • @shantilaldhakar9967
      @shantilaldhakar9967  2 года назад

      Your Positioner is mounted on which system i.e. Air to open/close actuator or power cylinder?
      Case 1: If ‘Air to Close’ type pneumatic actuator then check air pressure and ensure that it does not exceed specified limit.
      Case 2 : If power cylinder then you adjust through cushioning screw.
      And then repeat manual calibration procedure as explained in this video.

    • @thomaselsen1672
      @thomaselsen1672 2 года назад

      @@shantilaldhakar9967 it is a fail to close valve. On a diaphragm actuating control valve. The system set points requires the valve to jump up to 20% open as soon as any Ma signal is applied. So the valve was manually calibrated to set the lower limit to that 20% open so when Ma is applied it would automatically go to 20% open and achieve desired set points. Since the new 0% is manually calibrated to 20% open and the positioner closes the valve all the way to its seat once it gets the close signal. the display will read a negative number now because it thinks it is -20% to the seat. I was wondering if there is any way to zero that number out on the display or a better way to set up that valve to be able to achieve those set points. Thanks for the Help.

  • @INSTRUMENT_GYAN
    @INSTRUMENT_GYAN 2 года назад

    सर मैं जैसे ही End1 देकर hand press कर रहा हूं Range लिखा आ रहा है End 2नही आ रहा है क्या चेक करू

    • @shantilaldhakar9967
      @shantilaldhakar9967  2 года назад

      “Range”means your range selected in “End1” or “End2” is incorrect. Please set it inbetween 10% to 85% at zero and span respectively. 👍

  • @AshokPrajapati-ec3qh
    @AshokPrajapati-ec3qh 3 года назад

    Good sir

  • @kirtandas1974
    @kirtandas1974 4 года назад

    Sir ek problem hai 100% command pe 66 % arha hai... Input
    Kya kare
    12 no parameters me ja ke chenge kar ke dekh liya par ho nahi rha .
    Please iska kya problem hai btae

    • @shantilaldhakar9967
      @shantilaldhakar9967  4 года назад

      Factory reset your positioner and then re-calibrate in manual mode. If you got any issue then feel free to comment regarding problem.

    • @shantilaldhakar9967
      @shantilaldhakar9967  4 года назад

      RESET :: Go to parameter no. 50 and then press and hold “+” button for 5 seconds. This action will factory reset your positioner.👍

    • @Pawankavlog24
      @Pawankavlog24 Год назад

      @@shantilaldhakar9967 sir mere positioner me zero command dene pe 20% command aa rha h to kya problem hoga command zero nhi aa rha

  • @madhavrabari4756
    @madhavrabari4756 2 года назад

    🙏 Thanks 🙏

  • @PradeepKumar-qk3qo
    @PradeepKumar-qk3qo 4 года назад

    Eska full video dekhao with industry ka sir

  • @sajidaziz2862
    @sajidaziz2862 4 года назад

    AoA
    sir my control valve ps2 positioner continue stuck on RUN 5 but not show finish option please giuide me

    • @sajidaziz2862
      @sajidaziz2862 4 года назад

      if stroke 20 mm then we select 90 or 30
      but now i select 90 and selector switch on 90 same as follow in parameter 2 according to manual

    • @shantilaldhakar9967
      @shantilaldhakar9967  4 года назад +1

      @@sajidaziz2862 please select 33° angle and then lock that position at 33°.

    • @sajidaziz2862
      @sajidaziz2862 4 года назад

      ok i will try now

    • @sajidaziz2862
      @sajidaziz2862 4 года назад

      @@shantilaldhakar9967 sir but when we select 90??if stroke is more than 20??

    • @sajidaziz2862
      @sajidaziz2862 4 года назад +1

      @@shantilaldhakar9967 Thanks for guidelines my job is done.

  • @sbibhureddy2255
    @sbibhureddy2255 4 года назад

    Me Ra ek positioner auto/manual calibration nehi leraha he. Next Kia karunga

    • @shantilaldhakar9967
      @shantilaldhakar9967  4 года назад

      Please what's app your query/screenshot of error so that I may help you in a better way.
      What's app number 8003228484

  • @nikhilkapoor4561
    @nikhilkapoor4561 3 года назад

    Positioner display is not getting power on ....22 v DC ... What will be the solution

    • @shantilaldhakar9967
      @shantilaldhakar9967  3 года назад

      If power is healthy then it's interface card may be faulty.
      Solution: Contact to supplier/vendor for repairing/replacement.

  • @himanshushekharpandey7186
    @himanshushekharpandey7186 11 месяцев назад

    Thnx via

  • @MdAli-vg2ko
    @MdAli-vg2ko Год назад

    Nice

  • @sambalpurisongsulhabaysi.8343
    @sambalpurisongsulhabaysi.8343 Год назад

    har waqt kya dono + aur - button ko press kar k karna padega...agar nahi to dono ungli se kyon chek dete ho...

    • @shantilaldhakar9967
      @shantilaldhakar9967  Год назад

      Har waqt nhi,
      Jab quick open ya close karna ho tabhi Aisa karn ha.

  • @iqbalmehedi3423
    @iqbalmehedi3423 4 года назад

    how can i attach a position feedback module?

  • @RizwanAhmad-wg6fs
    @RizwanAhmad-wg6fs 4 года назад

    How to solve hunting and overshoot problems. There is no tube leakage but also hunting.

    • @shantilaldhakar9967
      @shantilaldhakar9967  4 года назад

      Check air leakage after positioner output from tube joints and actuator diaphragm.
      If this check is found normal then check the feedback positioner link connection. It may be loose or very tight so adjust link and properly tight again.
      After all that please make positioner calibration, I think your problem will get resolved.

  • @Ajayyadav-nh3qb
    @Ajayyadav-nh3qb Год назад

    how to set her feedback deviation

  • @rajarajan6291
    @rajarajan6291 5 лет назад

    Good job

  • @hadiyalshailesh9748
    @hadiyalshailesh9748 4 года назад +1

    Good

  • @parmarashvin3993
    @parmarashvin3993 4 года назад

    Sir ye 90°And 33 ° me kush samj nahi aa raha kush jyada jankari de sakte he please... Sir...

    • @shantilaldhakar9967
      @shantilaldhakar9967  4 года назад

      In case of linear actuators, if valve stroke is less than 20 mm then we select 33° transmission ratio else for valve stroke more than 20 mm we select 90°.

    • @parmarashvin3993
      @parmarashvin3993 4 года назад

      @@shantilaldhakar9967 ok thank you sir

    • @mayankparmar4850
      @mayankparmar4850 3 года назад

      Muje bi isme samaj nahi aaraha hy

  • @odishabirdlovers3827
    @odishabirdlovers3827 2 года назад

    Mera position reverse may kam kar rahahey kya karu

    • @shantilaldhakar9967
      @shantilaldhakar9967  2 года назад

      Check parameter no. 7 and select proper parameter i.e. “rise” or “fall”.
      Your problem will be resolved.

    • @odishabirdlovers3827
      @odishabirdlovers3827 2 года назад

      @@shantilaldhakar9967 thanks

  • @devispatel50
    @devispatel50 4 года назад

    👍

  • @jitubabusay2826
    @jitubabusay2826 5 месяцев назад

    19 mA mai 100% open karna hai to kya kare please batayiye

    • @StarkinesHits
      @StarkinesHits Месяц назад

      Tube ulta kardo
      Cylinder ka bta rha

  • @tariqueanwer9329
    @tariqueanwer9329 2 года назад

    Sir mera actuator 0mm tk close nahi ho raha hai please help

    • @shantilaldhakar9967
      @shantilaldhakar9967  2 года назад

      Check your actuator specification and if it is air to close type actuator then set air pressure.
      Also, you may set pressure 5-10% higher than rated pressure.
      Secondly, if above things checked and ok but problem not resolved then ensure that actuator spring tension is ok or not.
      It may be due to high spring tension of actuator so adjust it properly. 👍

  • @mrinmoysahoo8626
    @mrinmoysahoo8626 2 года назад

    Agar run 1 ya run 4 ma error ageya to kya karna chahiye

    • @shantilaldhakar9967
      @shantilaldhakar9967  2 года назад +1

      Error in RUN 1 means either actuator/power cylinder is jammed or air pressure is not sufficient.
      Please check air pressure, pressure seal condition and jamming of valve/actuator.

    • @mrinmoysahoo8626
      @mrinmoysahoo8626 2 года назад

      @@shantilaldhakar9967 thanks

    • @mrinmoysahoo8626
      @mrinmoysahoo8626 2 года назад

      Or run 4 kya matlab hai

    • @shantilaldhakar9967
      @shantilaldhakar9967  2 года назад +1

      @@mrinmoysahoo8626 It's my pleasure to help you 😊

    • @shantilaldhakar9967
      @shantilaldhakar9967  2 года назад

      @@mrinmoysahoo8626 RUN 4 : Positioner check and determine the minimum increment length so if error means there may be air leakage through actuator/power cylinder pressure seal parts.
      Please check and ensure that their is no any such leakages. 👍

  • @atanuhalder322
    @atanuhalder322 5 лет назад

    Sir my calibration is running at run4 continuously is not going at run5 please help me

    • @shantilaldhakar9967
      @shantilaldhakar9967  5 лет назад

      Dear friend,
      RUN 4 step during calibration “ Determine the minimum increment length ” means positioner will increment command by smaller fractions in decimal points & simultaneously check feedback and if it doesn't match then positioner stucks in RUN 4.
      Solution::
      (A) There may be leakage from fittings/diaphragm so check all fitting tightness.
      (B) The position FB link may be loose so check tightness.
      And then calibrate again you will definitely success.
      Thanks for your query and I hope this information helps you a lot.

  • @sagarmali8393
    @sagarmali8393 Год назад

    What is meant by U- di error

    • @shantilaldhakar9967
      @shantilaldhakar9967  Год назад

      means positioner feedback is inappropriate with respect to command signal.

    • @shantilaldhakar9967
      @shantilaldhakar9967  Год назад

      futher you may adjust it by roller gear mounted just below display.

  • @sbibhureddy2255
    @sbibhureddy2255 4 года назад

    Siemens positioner ko kese single action karenga.?

    • @shantilaldhakar9967
      @shantilaldhakar9967  4 года назад

      Make one output lower side port dummy and connect connect control valve to the remaining port.

  • @prithwishkundu96
    @prithwishkundu96 19 дней назад

    Vai step by step full process me video banaiye

  • @pradipkumaryadav252
    @pradipkumaryadav252 4 года назад

    If 41 blinking on screen then what will do

    • @shantilaldhakar9967
      @shantilaldhakar9967  4 года назад

      Check the Instrument air pressure, if it is not sufficient to open/close valve then this error occurred 👍

  • @jitendrakumarsahu4087
    @jitendrakumarsahu4087 5 лет назад

    VEnd2 ke baad Range ka option aa rha hai , calibration nhi hota hai ,,kya kru bataye

    • @shantilaldhakar9967
      @shantilaldhakar9967  5 лет назад

      Please adjust the zero and span range and accordingly it's feedback too.
      The difference must be greater than 80% and then calibrate using above explained procedure.
      Thanks buddy

    • @shantilaldhakar9967
      @shantilaldhakar9967  5 лет назад

      Operate the valve using + & - buttons on positioner and set Feedback 0 at zero check and atleast 80 to 86 at span check.
      Then calibrate the positioner in auto/manual mode.

    • @jitendrakumarsahu4087
      @jitendrakumarsahu4087 5 лет назад

      @@shantilaldhakar9967 span and zero kaise set kare? Hindi me bataye sir

    • @jitendrakumarsahu4087
      @jitendrakumarsahu4087 5 лет назад

      @@shantilaldhakar9967 Jab Range ka Option aata hai us time + button press karne se Vend2 aa jata hai fir se

  • @hooshangalizadeh637
    @hooshangalizadeh637 3 года назад

    how to adjust the display contrast ?

    • @shantilaldhakar9967
      @shantilaldhakar9967  3 года назад

      please share details/model no. of your Siemens positioner.
      It will be like “ 6DR5051 or 6DR5052” .

    • @shantilaldhakar9967
      @shantilaldhakar9967  3 года назад +1

      I had gone through the positioner manual but did not find any information about contrast control.
      FYI 👍

  • @GauravKumar-xu9gh
    @GauravKumar-xu9gh 2 года назад

    I have confusion for parameter 7 and 38 could anyone can explain please.

  • @8899122246
    @8899122246 2 года назад

    Feedback kaise set krenge

  • @manekmanek2617
    @manekmanek2617 5 лет назад

    Good brother what about hantting

    • @shantilaldhakar9967
      @shantilaldhakar9967  5 лет назад

      Hunting problem caused due to these possibilities ::
      1. Instrument air pressure drop after positioner output by any means including ALR failure or air leakage problem.
      2. If the spring tension is loose than required then it happens.
      Thanks for appreciation and query.

  • @alijee4876
    @alijee4876 4 года назад

    Yar agir new install karna hai tu kary ga

    • @shantilaldhakar9967
      @shantilaldhakar9967  4 года назад

      Same procedure will be followed for newly installed positioner.

    • @shantilaldhakar9967
      @shantilaldhakar9967  4 года назад

      Please share your email ID so that I may help you by providing sufficient documents.
      Thanks

    • @alijee4876
      @alijee4876 4 года назад

      alijee.aj137@gmail.com

  • @KasturiSagar-v2b
    @KasturiSagar-v2b Месяц назад

    1 error cord haya sir aap ky harna

  • @parmarnil4748
    @parmarnil4748 3 года назад

    0 jaga pe 100%dikhae और 100 % जगा 0 dekha to kya karne ka

    • @shantilaldhakar9967
      @shantilaldhakar9967  3 года назад

      केवल फीडबैक गलत आ रहा है या कंट्रोल रूम से कमाण्ड ही गलत आ रही है।

    • @shantilaldhakar9967
      @shantilaldhakar9967  3 года назад

      Check parameter No. 7 and 38.
      If position feedback is just reverse then change parameter no. 38 from rise to fall and vice versa.
      And if command signal is reverse then change parameter no. 7 as explained above.
      I hope you got solution, further feel free to contact if you have any query.
      Thanks

  • @SurenderSingh-sk3kn
    @SurenderSingh-sk3kn 4 года назад +1

    Bhai maan ge chorre

  • @mayurparmar104
    @mayurparmar104 5 лет назад

    Control valve mera open hai to zero dikha raha hai.. Or close hone par 100 dikha raha esa kyu

    • @shantilaldhakar9967
      @shantilaldhakar9967  5 лет назад +1

      Please check perameter no. 7 & 38 both parameters must be selected “ rise ” instead of “ Fall ” and then calibrate in manual mode as described in this video.
      I hope your problem will be resolved.

    • @kishoreKumar-wt4vi
      @kishoreKumar-wt4vi 5 лет назад

      Yes correct ji.

  • @sreenubabu6488
    @sreenubabu6488 4 года назад

    Friend if possible English language

  • @PradeepKumar-qk3qo
    @PradeepKumar-qk3qo 4 года назад

    Can you learn me sir ji

  • @bhagwansinghlodha939
    @bhagwansinghlodha939 3 года назад

    kavi kavi error aati h calibration nhi leta h wo

  • @PradeepKumar-qk3qo
    @PradeepKumar-qk3qo 4 года назад +1

    Good work

  • @surajkumarkhunte1181
    @surajkumarkhunte1181 2 года назад +1

    thank you

  • @janmuhammad2751
    @janmuhammad2751 3 года назад

    Good