Why VA rating of metering CT shall be lower and protection CT shall be higher

Поделиться
HTML-код
  • Опубликовано: 29 ноя 2024

Комментарии • 15

  • @subratamohapatra6478
    @subratamohapatra6478 Год назад

    Very nice learning

  • @bheemeshbatta2172
    @bheemeshbatta2172 Год назад

    Of course your explanation may be correct isf and Alf but the reason for low burden for Metering class CTs is due to the metering CTs should be accurate compared to protection class CTs in order to be accurate low burden indicates less secondary voltage which in turn less magnetising current and less magnetising current means actual current is closer to measured current.

  • @bheemeshbatta2172
    @bheemeshbatta2172 Год назад

    just imagine the CT Circuit model and saturation depends on magnetising current. More is the secondary voltage more will be burden and more will be magnetising current. So if actual burden connected is more compared to rated burden than at less current (less than rated ALF or isf) CT gets saturated.

  • @shantanumajhi5408
    @shantanumajhi5408 2 года назад

    Very useful.
    Sir kindly make a lecture video on VCB selection.

  • @Doti_231
    @Doti_231 2 года назад

    very good explanation
    thank you for sharing

  • @surendrakverma555
    @surendrakverma555 2 года назад

    Very good. Thanks 🙏🙏🙏🙏

  • @jaydhokai8364
    @jaydhokai8364 2 года назад

    Very useful. Thanks.

  • @shankhachongder6065
    @shankhachongder6065 Год назад

    Thank you sir

  • @sanjeevrana8317
    @sanjeevrana8317 2 года назад

    Keep it up

  • @rukmagoud
    @rukmagoud 2 года назад +1

    In Protection class CT we find one more class PS. In class PS CT manufacturer never specifies any burden. He specifies only knee point voltage. How much burden shall be connected to this CT?

    • @electricaltechnologyandind5335
      @electricaltechnologyandind5335  2 года назад +3

      PS class CT has some other method. However its VA rating could be also determined. I shall make video on that....

    • @sanjeevrana8317
      @sanjeevrana8317 2 года назад

      @@electricaltechnologyandind5335 video awaited

  • @thinkseeeatthroughvickus4555
    @thinkseeeatthroughvickus4555 2 года назад

    How to find minimum required ALF for a relay?

  • @RajeshSharma-ge8ui
    @RajeshSharma-ge8ui 2 года назад

    If Sn will increase then we have to choose above 5P20 rating of CT