FIRE ALARM || CONVENTIONAL FIRE ALARM PANEL || TYY CONVENTIONAL PANEL ||
HTML-код
- Опубликовано: 7 фев 2025
- Lazada: bit.ly/3P9kwxN
Everything about Conventional Fire Alarm Panel well be discuss in this video.
If you are a beginners or want to know more, especially how the systems work, then this is for you.
Topics:
1. How the conventional Fire Alarm Panel Works.
2. What is the purpose of End Of Line (EOL) Resistor.
3. What is the correct termination of Manual Call Point (MCP) and BELL.
If you learn something in this video, Please do Like and Subscribe to this channel for more FDAS knowledge. \\
If we can reach 1000 subscriber, I will cover how the COOPER, GST and Morley-iAS Systems work.
From Termination, design and programming.
With programming software.
Thank you!!!!
PANEL:
www.lazada.com...
/ safetytechnician
COMPLETELY WRONG. IT IS NOT CURRENT SENSING. YOU SHOULD CHECK THE CIRCUIT FIRST.
Thank you. ikaw na check mo na?
@@whatever.TV88 yes wrong
@@whatever.TV88 if you can tell me the IC number then i will tell you you are wrong.
@@MarckAncajasMA Paano pala Master para ma correct ko.
@@whatever.TV88 i know what im talking about. all IDC circuit for conventional FACP is not current sensing. The EOL resistor is designed to comply for NFPA72 requirements to have a surpervised curcuit that monitors short circuit, open circuit and Alarm status but the circuit is not designed with current sensing. the answer is can be known thru ic number of IDC. i have been working IDC design. so i know im right.
Salamat sir
Salamat idol alam Kona
Cooper na man sir☺️☺️
pagmakahiram tayo panel Sir. hehehe. Wala na kace tayo ngayun sa Cooper.
Last August 9 2024 po pala Eim nc2 assesment po namin sa written exam at sa oral lang po ako nakapasa nyun po hindi po ako nakapasa nyun po sa actual dahil naabutan po ako ng oras dahil may timelimit po kasi ang pag install hindi ko po na tapos young ibang electrical devices sa pag install po reassesment po ako ulit young actual lang daw po retake ko yun daw po sabi ng assesor at sana po makapasa na po ako sa aking reassesment!🙏
Kaya mo yan Sir. Tiwala lang
Thankyou po!🙏
Master ok SA isang zone dalawang manual call point na tyy. 4wires. Po. Yng wiring. Sa terminal. Niya isang zonel pwd paanu po I termination po. Slmt master
2 wires lang kay TYY Master, naka patallel ang termination., kung ibang brand e install mo pwede naman peru kung dry contact type na MCP yan need mo ng trigger resistor kace shorted po lalabas nyan.
Paano kung line to line Ang sourse
Boss ask ko lng poh ..anu poh ang supply nyan 220 volts poh ba boss thanks poh god bless
220V/AC para sa power source ng panel. 24V/DC Panel output
Ok lang po kahit baliktaran ang pagkabit ng resistor..
wala pong polarity ang resistor. kaya okay lang
Kada zones po ba may sariling sounder?
Hindi. itong panel na to ay 4 zones peru may 2 sounder output lang at global sya. may mga conventional panel na may multiple output at pwede mo sya e assign every zones
ilang smoke detector sir pwedi gamitin sa zone 1
depende yan sa specs ng panel. sa video na to up to 30 detectors
Sir ask ko lang po paano po kung Yung connection na galing sa panel board ay line to line connection papaano po ito e connect sa facp ?
Di ko ma gets ano ibig mong sabihin sa line to line Master. pa explain ng maayos
@@whatever.TV88 diba Meron line to ground connection Meron din line to line connection na kadalasan sa urban area..or single phase three wires po..ang tanung ko po sana po masagot ninyu Yung connection po sa panel board ng fire alarm(facp) paano po e connect ang linya na parehong may 110 volts each?
@@AlvinAlid ahh okay. sa power source pala tinutokoy mo.
tatlo po terminal nyan parihu lang yan sa ibang mga appliances mayron Hot Neutral Ground.
master halimbawa umabot device mo ng 40 isang zone isang 10k ohms pa rin ilalagay?
sa specs master up to 30 device lang. baka magkaka fault na yan. di ako sure.
@@whatever.TV88 kaya po ng zone 1 ang 20 pcs sir
@@seferinoalvinezjr kaya po
Bos pag dalawang panel pwd ba e synchronised ang Bell to bell anong gamit na ma synchronised sya?
Dito sa panel natin Master conventional to kaya need mag add ng relay. bali double input single output and relay na e design
Sir may EOL resistor po ba sa sounder natin?
mayron dapat
4 zone panel po ba Ilan. Kaya sounder or horn strobe Kaya po ba 6pcs bell or strobe slmt master
kaya po yan.
Pwede ba pag line to line
Pwede naman
Series ba yan ang resistor sa mps master
Pag TYY MCP gamit mo no need na ang Resistor Master
sir pano e connect yumg resistor sa mcp?
Parallel connection
Sir sa bell namo Kay wala butangi...pwede BA sya madamge Ang bell.
coil kace ang bell kaya need mo ng diode para ma direct and current. may posibility na ang masira ay ang output ng panel.
4:25 principle of operation ng conventional fire detection alarm system/paano gumagana ang fdas
Current driven yan. wala pong data na binabato nya. nag depende yan sa current na dumadaloy sa Zones.
@@whatever.TV88 saan ko po siya sir pwede pag-aralan, may link ka po ba sir na tungkol sa conventional fdas?
@@markangeloimporta1614 Based on my experience and curiosity lang lahat yan Master. Kung gusto mo matoto nyan lahat pwede ka mag apply sakin 1on1 training. Paid po yun xiampre peru sabi ko sayo a decade of experience ang makukuha mo sa akin. pm ka lang.
Same lang po ba sila ng brand na arrow sir.??
Not sure. di pa ako nakagamit ng Arrow
Boss paano ikabit qng smoke detector fire guard yong bracket niya 1234 09-35v. Tapos gamit ko 24 v. Na conventional panel TYY salamat
Check mo muna bai kung pwede ba e two wires ang installation sa emu fireguard. wala pa naku na try
Bossing para San po Yung non-laching na push button sa TYY control panel ..
Saan banda nakalagay ang button master?
sir paano kng magtrigger ang MCP at hindi nag alarm ang FACP. ano po problema kapag ganon?
TYY po ba MCP mo?
Anu ang problema kapag nag test ng sd tapos umilaw hindi naman nag trigger ung strobe anu po problema.,
Same brand ba ang Detector at ang Control Panel?
Sir, ganda po ng pagka turo niyo po,
tanung ko lng paano po pag mag iinstall po ako ng 3pcs Alarm Bell 10" at 8pcs na 6" na Alarm Bell, at nabanggit niyo po upto 4 pcs Alarm Bell lng kaya ng Panel.
Ano po pwed gawin?
Salamat idol.
Para makapag install ka ng mas maraming output devices like Bell and Strobe light, need mo ng separate supply para sa kanila. tapus gumamit ka ng relay (SPDT) type na 24V with Diode dapat. marami sa electronics store yan. kung di mo kabisado ang connection at termination, message ka sakin.
@@whatever.TV88 sir magandang araw po pwede din po ba ako magpatulong hihingi din po kase sana nang guide para sa connection at termination para makapag kabit po nang maraming sounder sir
@@franconap2871 Dali lang yan Master. need mo lang ng extra power supply na may back up battery din dapat kace kung walang back up battery bagsak po yan sa standard.
hi boss, pwede ko kayo kunin for company in-house training and project installation?
maganda po pagkaturo nyo lalo sa mga beginner katulad ko
Pweding pwede Sir. contact mo lang ako. 09566756808
Location nyo master.pwede ba magtraining syo
Quezon City Master malapit lang sa Aguinaldo.
Same p yan panel sa assesment namin bakit ayaw gumana s1 isang bel at z1 isang detector at mps.. At may resistor naka series sa bell at meron din ressitor sa una bakit ayaw pumalo ang bell try ko pinalo ung mps nag alarm cignal. Lang ung panel. Bakit hindi tumotunog
Diode dapat nakalagay sa Bell. may polarity yun
kahit walang resistor ang zones pwede yun. may option ka djan na di gamitin ang EOL master. kung marami pa kayong di natutunan. punta kayo sa office. budget meal lang ang bayad.
boss panel zone 1, 2, 3, 4, 5 direct with resistor lang 1k walang nakakabit na SD, nagaalarm sya na fire. then yung ibang zone 6, 8,9, 10,11, 12 with resistor normal. ano kaya problema?
Sir. Trigger resistor po ang 1k. hindi sya EOL. Dapat po 10k ang nilalagay mo.
@@whatever.TV88 kung 10k ko kasi nilalagay katulad resistor ni sounder ng aalarm sya ng OC.. kung 1k normal po sya sa ibang zone.. iba naman fire
Posible ba defective na ang terminal?
Not Sure. bihira lang naman masira terminal. try mo recta sa terminal ang 10k kung mag okay.
@@MrJeonard1985
Ano brand panel mo Sir?
@@MrJeonard1985
Sir good day ayaw man mag bato Ng signal yong smoke at sa Ka push button,bkit sir? Anong gawin
TYY ba panel at mga device mo?
Sir bakit Hindi Humana Ang manual pull swicth
Anong MCP gamit mo Master? panoorin mo ulit paano mag install ng MCP.
Bosh paano mag wiring sa bell at saka manual call point
Si bell Idol may sariling terminal yan sa panel yun ang output terminal. c MCP naman pwede na yan sabay sa mga SD.
Good day master capacity Ng isang zone Ilan divice po pwd.
30 mximum sa TYY 4 BELLS per output
Bali sir Kada zone Ng bell apat ang Kaya gnun po ba Yun slmt master
Bali 8 Kaya na bell sa Tyy na 4zone panel sir Yun po ba Yun slmt
@@alexandercellon971 bali may 4 zones ang panel na to maximum of 30 detectors per zone. at may 2 output lang sya na kay ayun sa manual 4 bells per output
Lods di pa po aq naka ranas ng ganyan kaya nanunood aq
thanks for watching
anong specs ng diode master sa bell?
1n4001 master pwede na
Nagtetraining po ba kayo ng actual sir?
sa ngayun wala pa Sir. may inaayus lang ako para magka TESDA tayo. sayang kace
Ser bakit ang tyy mag ka troble kapag madame ang bell
4 bell lang ata nakalagay sa specs ng panel
Hello.idol ask ko lang if may natirang bakante pang zone or sounder need bang lagyan ng resistor un ?
Yes po. Dapat andjan palage ang EOL Resistor
Magkano po yan sir facp?
sakin mo kukunin 9,800.00
Sounder open sir khit tama connection
Check End Of Line Resistor. ilang sounder na ba naka connect?
Sir patulong Naman po, bakit naka open circuit parin kahit nagpalit na ko nang mga resistor.. Wala po akong smoke detector at heat detector, bell lang at mcp
@@whatever.TV881zone lang po Ang control panel ko
Try mo muna lagay ang mga resistor direct sa Zone terminal na walang load.@@leonimarcaquilala3381
@@whatever.TV88 maraming salamat po, try ko po bukas
hindi claro ung pagtorumo brand mahina
Bubo mo nmmn sir.. Klaro nga sakin
Medyo magulo explaination niu sir.di masyado detalyado. Magulo in short.
Hahaha. gawa nalang ako bago
So LAZY! NO ENGLISH SUB TITLES!!!!!!!
Sorry na Pre. di maalam magbutang sub.