Configuring an ADAM-6017 to use current input, Advantech(EN)

Поделиться
HTML-код
  • Опубликовано: 14 дек 2024

Комментарии • 5

  • @shingami6444
    @shingami6444 3 года назад

    What is the problem when we put 4-20ma, it will mention overcurrent

  • @wellingtonpazmino58
    @wellingtonpazmino58 6 лет назад

    Please, I need your help: I have a ADAM 6017 module and I want to connect this module with my PLC and I need to know: which is the type data to read AI is: INT, UINT, HEX, etc. In addition which is the byorder Endian Big or Endian Litle. please I need to know this information for my application. NOte: The protocol is MODBUS TCP.
    Regarsd,
    Wellington Pazmiño.
    ECUADOR

    • @AdvantechCorp
      @AdvantechCorp  6 лет назад

      Hi Wellington,
      Thanks for your inquiry, please refer to the instruction below.
      ADAM-6017 support Modbus TCP, and we define the Modbus address for every channel AI value.
      You can find the Modbus address in the User manual.
      support.advantech.com/Support/DownloadSRDetail_New.aspx?SR_ID=1-95WMW&Doc_Source=Download
      Each Analog input value which stored in the address is from 0000~FFFF(in hex)
      Regarding the big endian and little endian problem - please go for “big endian”.
      If you have more quetion, please contact our AOnline team for further technical support at www.advantech.com/contact/inquiryrequestform?subject=technical%2bsupport
      We look forward to hearing from you. :)