السلام عليكم ورحمة الله وبركاته استاذ محمد هل توجد شروحات حول مناولة ال REL 670 بأسلوبك الراقي وكمية المعلومات الوفيرة والقيمة والتي تنتقل بالمتلقي الى مراحل ممتازة ونتمنى من الله عز وجل ان يمن عليك بالصحة والسلامة والموفقية وان يجعل ماتقدمة في ميزان حسنات اعمالك .
If a drop-off situation happens, that is, a fault suddenly disappears before the operate delay is exceeded, the timer reset state is activated. The functionality of the timer in the reset state depends on the combination of the Operating curve type, Type of reset curve and Reset delay time settings. When the DT characteristic is selected, the reset timer runs until the set Reset delay time value is exceeded. When the IDMT curves are selected, the Type of reset curve setting can be set to "Immediate", "Def time reset" or "Inverse reset". The reset curve type "Immediate" causes an immediate reset. With the reset curve type "Def time reset", the reset time depends on the Reset delay time setting. With the reset curve type "Inverse reset", the reset time depends on the current during the drop-off situation. The START output is deactivated when the reset timer has elapsed.
جزاك الله خيرا على هذا الموضوع المهم
جزاك الله خير
جازاك الله خيراً أخي محمد , في انتظار جديدكم
بارك الله بيك
شرح ممتاز جدا
السلام عليكم ورحمة الله وبركاته
استاذ محمد هل توجد شروحات حول مناولة ال REL 670 بأسلوبك الراقي وكمية المعلومات الوفيرة والقيمة والتي تنتقل بالمتلقي الى مراحل ممتازة
ونتمنى من الله عز وجل ان يمن عليك بالصحة والسلامة والموفقية وان يجعل ماتقدمة في ميزان حسنات اعمالك .
عﻻء حسين عباس بإذن الله انا في مراحل التجهيز وان شاء ارفعها قريب
عﻻء حسين عباس اسف جدا علي التأخير في الرد وذلك لظروف شخصية
لو تكرمت يا هندسه عاوز اتواصل مع حضرتك وانت وعدتني ولسه ما ردتش عليا
خطوات مسح ALARMS IN REF620
مشكووووور
بالنسبة لل type of reset curve
عند اختيار inverse reset مالذي يحصل ؟ وكيف يعمل اختيار reset delay time في هذه الحالة؟ ارجوو الرد
لما هتقل قيمة العطل عن ال Pickup الريلاي هيعمل reset بنفس المعادلة اللي استخدمها في ال pickup
If a drop-off situation happens, that is, a fault suddenly disappears before the
operate delay is exceeded, the timer reset state is activated. The functionality of the
timer in the reset state depends on the combination of the Operating curve type,
Type of reset curve and Reset delay time settings. When the DT characteristic is
selected, the reset timer runs until the set Reset delay time value is exceeded. When
the IDMT curves are selected, the Type of reset curve setting can be set to
"Immediate", "Def time reset" or "Inverse reset". The reset curve type "Immediate" causes an immediate reset. With the reset curve type "Def time reset", the reset
time depends on the Reset delay time setting. With the reset curve type "Inverse
reset", the reset time depends on the current during the drop-off situation. The
START output is deactivated when the reset timer has elapsed.
لو ممكن ايميلك ارسلك عليه التفاصيل اكتر
what is the software you used to simulate the signal?
the other software you use to test the over current protection
is it a free download software?
@@jeffryleodones5936 it is the Automatic Software for Freja300 Test Kit, Called Frejawin
@@jeffryleodones5936 yes
شرح ممتاز جدا
what is the software you used to simulate the signal?