Hullo mr Jeck...I want to thank you so much for the brilliant Ideas......I have a daikin reefer the compressor whole covered by ice and the is no pull down in the frozen mode yet the freon is charged with 4.6 kgs and no leaks......help please your advice is important to me
@@malakadananjaya2046 Yes. Check comp wire components. Check voltage line to line, check comp contactor & wiring, check compressor resistance, check RPP, check compressor terminal. If all is good you must replaced the IO board.
Super
E103 COULD RESULT TO E707? AND WHEN E103 happpened PT/CT should be changed right?
Hullo mr Jeck...I want to thank you so much for the brilliant Ideas......I have a daikin reefer the compressor whole covered by ice and the is no pull down in the frozen mode yet the freon is charged with 4.6 kgs and no leaks......help please your advice is important to me
A new filter drier is replaced.. i don't know why it is repeating itself
Check EEV Coil & Body.
I had the f705 code and i reset the unit and it fired up again. Does it still need to be replaced?
Check the voltage first.
@reefercontainerph4182 thanks for the reply I'll do that this morning
unsa tong gi nailcut master?
Why should we cut the jump J1 and J2?
It depends on the model where you install the PT/CT. Just see the manual of PT/CT.
Do you have any idea about Lxe10e j model alarm F807 - Non connection of compressor terminal ?
Thanks 🙏
@@malakadananjaya2046 Yes. Check comp wire components. Check voltage line to line, check comp contactor & wiring, check compressor resistance, check RPP, check compressor terminal. If all is good you must replaced the IO board.