end of line resistor (EOL) must be installed in the last devices for supervisory if someone removes the devices no trouble or supervisory in the control panel
If someone press the manual extinguishant release will the horn and strobe lights activated then within 10 seconds it will release the aerosol? And in the disablement/supervisory will the manual release led light will turn on?
@@engineersguide4249 thanks. But as you clarified. The resisiter will isolate the signal in the panel. And if there any cut in wire it will not appears in a board of the panel!
Hello, how are you Mr , I have a simple question Why does a signal appear? Release trouble When connecting the selenoid to the cylinder As soon as I turn off the selenoid, the signal disappears. I hope you can find a solution for me
Dear brother nice video... Can you pls explain me about the additional relay for AC shutdown. From where you provide power to the relay and from where you will provide input signal to the relay , if we want to shutdown the AC in first stage... Thanks
1.5MM ARE USED FOR INPUT DEVICES AND 2.5MM FOR OUTPUT DEVICES BECAUSE WHENTHERE IS AN ALARM THE AMPS INCREASES WHEN ITS AT WORK.SO TO ESCAPE FAULTS LIKE GROUND FAULT DURING ALARM ACTIVATION AND OTHER RELATED TROUBLES ITS RECOMMENDED TO USE 2.5MM
first and foremost you have detect where the earth fault is coming from by removing the device cables one after the other till u see the earth fault gone so u can find the root cause of it .there is a code to disable earth fault trouble but the earth fault light will still be on ..check and update me and will advice you on what to do
Thank you very much sir. I found it ,zone 1 detector cable when remove Earth fault going . Spare pair cable was there i connect it now normal. Thanks for ur advice . If i have any doubt i message u sir
Sir can you help me i have also a same panel that you have my problem was i already put two zone and my alarm bell was put on nac1 but when i was try to activate the detectors it shows panel only trouble not fire can you help me about this please thanks alot
Mainly the key access needs to be turned to access the functioning of the buttons. There is one key switch called enable access turn it to the right side and access it, if it's another issue too pls let me know tnx 😊
Low pressure switch two wiring same colour will be connected From the Panel Red Colour Cable added 470k Resistance with other side 6.8k resistor another side of 6.8k resister will connect with black wire coming from the panel
Try removing the cables one after the other while checking which one will let the fault go then if u get the particular cable inspect to find out where the short is and correct it
end of line resistor (EOL) must be installed in the last devices for supervisory if someone removes the devices no trouble or supervisory in the control panel
Can this board that you are explaining on be replaced with a shppro control board (fike) while keeping the same devices?
@@أيوبالجرهمي-ق8ع yes you can but few modifications has to be done
Thank you so much
If someone press the manual extinguishant release will the horn and strobe lights activated then within 10 seconds it will release the aerosol? And in the disablement/supervisory will the manual release led light will turn on?
Thanks for clarification. My question is for stage 1, stage 2 & trouble relay there are resistance, why that?
it is for the fire alarm module and since the panel is the end of line,so we connect incase it gets open or removed it will notify fire alarm
@@engineersguide4249 thanks. But as you clarified. The resisiter will isolate the signal in the panel. And if there any cut in wire it will not appears in a board of the panel!
@@losta7008 it wont but it will appear on the fire alarm panel
It would be helpful to know the value of the register
What is the use of resistors connected on top side of the controller and what is their value
It's called end of line resistor to keep system normal and monitor each line ..6.8k and 10k
Pleas clarify the connection of shield A-xT fm 200 panel to detctor ,manual releas and soundr,electric bell
It's same as connecting conventional detectors,the mps needs 470ohms resistor to trigger it
Hello, how are you
Mr , I have a simple question
Why does a signal appear?
Release trouble
When connecting the selenoid to the cylinder
As soon as I turn off the selenoid, the signal disappears. I hope you can find a solution for me
@@safaakadhim5040 share with me the type of solenoid you using
Sir How solve Exiting trbl ?
check your diode at the extiguishant area and replace it if possible
Our general trouble then I check silence/sounds alarm after fire light coming
Dear brother nice video...
Can you pls explain me about the additional relay for AC shutdown.
From where you provide power to the relay and from where you will provide input signal to the relay , if we want to shutdown the AC in first stage...
Thanks
you can directly loop the neutral cable of the AC using the fire relay in normally closed condition...it will go off on 1st stage alarm
Nice video .. could you support me with any book in programming or in this field in general .. please
All the programmings are pasted at the door of the panel when you open it ..will do a video on that to help out
I have one question why they use 2.5mm cable for horn strobe and bell instead 1.5mm because the supply is 24vdc only
1.5MM ARE USED FOR INPUT DEVICES AND 2.5MM FOR OUTPUT DEVICES BECAUSE WHENTHERE IS AN ALARM THE AMPS INCREASES WHEN ITS AT WORK.SO TO ESCAPE FAULTS LIKE GROUND FAULT DURING ALARM ACTIVATION AND OTHER RELATED TROUBLES ITS RECOMMENDED TO USE 2.5MM
Please help me sir . Earth fault comming always i found it Earth. detector cable not possible cahange cable. iwant stop Earth trouble .
first and foremost you have detect where the earth fault is coming from by removing the device cables one after the other till u see the earth fault gone so u can find the root cause of it .there is a code to disable earth fault trouble but the earth fault light will still be on ..check and update me and will advice you on what to do
Thank you very much sir. I found it ,zone 1 detector cable when remove Earth fault going . Spare pair cable was there i connect it now normal. Thanks for ur advice . If i have any doubt i message u sir
How to disable earth fault
Sir how to solve and reset cpu foult pleas help...
Showing cpu foult led and general foult led
you can only solve that by removing the power supply and battery to make the panel off for 30 secs and fix back problem is solved
How do I connect Ac shutdown, GSM, and the 2nd stage sounder can not silence when I press the button
get an external relay rather than connecting direct
What abt Nac3 what is the use of Nac3
NAC-01 USED FOR INDOOR BELL ( INSIDE THE ROOM) AND NAC-3 WILL USED OUT DOOR SOUNDER WITH FLASHER (OUT SIDE THE ROOM)
I want to stop / disbale the panel sound which is contionusly beeping
Turn off the access key
Sir can you help me i have also a same panel that you have my problem was i already put two zone and my alarm bell was put on nac1 but when i was try to activate the detectors it shows panel only trouble not fire can you help me about this please thanks alot
which way do you trigger the alarm, is it through the smoke detector or mcp lemme know
I have fire zone and whenever I connect the power the alarm sounds will start. How can I stop and clear this
check the device connections well
How to solve power troubles problems?
check on your ac supply it suppose to be 220v and battery 24v
ALL QUESTIONS AND SUGESTIONS WILL BE ANSWERED AND TAKING INTO ACCOUNT RESSPECTIVELY WHEN THE CONCERNS ARE RAISED HERE..THANK YOU
We are using these panel but most of the panel key problem when we turned the key panel not working
Could you send me photos of the panel and what u want to do I will be glad to help
Mainly the key access needs to be turned to access the functioning of the buttons. There is one key switch called enable access turn it to the right side and access it, if it's another issue too pls let me know tnx 😊
Please after installing the panel all the zone light is on please what's that place
Please can i get ur contact ?
How to troubleshoot the cpu trouble
just turn off the panel both ac and dc then turn it back on
In this panel how to remove releasing trouble
get a diode as your end of line it will be fine
Can you pressure switch connect send pictures
Low pressure switch two wiring same colour will be connected From the Panel Red Colour Cable added 470k Resistance with other side 6.8k resistor another side of 6.8k resister will connect with black wire coming from the panel
General trouble and power trouble how to close
check the small indication light below it will give you the exact trouble,but the main is AC power loss or Battery low or battery failure
How we can remove earth fault from panel
Try removing the cables one after the other while checking which one will let the fault go then if u get the particular cable inspect to find out where the short is and correct it
How can i disable or stop the beep beep continous sound..
TURN THE ACCESS KEY TO THE OTHER SIDE