Thanks for your efforts to explain working of Sverker. During testing of MCB you wasted many seconds to build 8 ampere current but you counted the whole time. First you should start the set in on mode, after building the required 8 ampere you should turn it off. Then again press on+ time, the timer will start with 8 ampere. This time will be the accurate time. Secondly you should use Int. Mode for MCB testing. Here timer will stop with internal interruption of current. Then no auxillary contact is needed.
Sorry swaran singh. you are right, but some time you can't focus on every part of your vedio. We'll try to filter out such mistakes in upcoming vedios.
Dear sir, Today we make megger test for SWGR in Madina airport substation,but during the megger testing we got low value in Y - phase bus bar in section B only. otherwise R and B phase value is OK, but Y - phase bus bar megger value is not OK. For example :- R and B phase value in Giga - ohms Y Phase value in kilo ohms.. u have any idea to resolve this issue
Ma Sha Allah very well. Explain
excelent man. thanks a millions. very easy way
congratulations
Excellent you guys. Bravo! keep such excellent work going. Extend it to protection relays. Thanks
very excellent explanation
Good video.. Actually one doubt about the current. It injects AC or DC current. I guess it is only AC current that this kit can inject
Thank you very much
God bless you...
Thanks for your efforts to explain working of Sverker. During testing of MCB you wasted many seconds to build 8 ampere current but you counted the whole time. First you should start the set in on mode, after building the required 8 ampere you should turn it off. Then again press on+ time, the timer will start with 8 ampere. This time will be the accurate time. Secondly you should use Int. Mode for MCB testing. Here timer will stop with internal interruption of current. Then no auxillary contact is needed.
Sorry swaran singh. you are right, but some time you can't focus on every part of your vedio. We'll try to filter out such mistakes in upcoming vedios.
شکرا سیدی
Very good thank you
Thanks alot very nice video 😊👍🏻
Thanks you sir got this given information ❤
Plz sir make one vedio to test o/c and E/F relay thanks alot
From kuwait
Why second raw in list (expected time 40-400 seconds actual 28.4 seconds) you write ok?
Dear sir,
Today we make megger test for SWGR in Madina airport substation,but during the megger testing we got low value in Y - phase bus bar in section B only.
otherwise R and B phase value is OK, but Y - phase bus bar megger value is not OK.
For example :- R and B phase value in
Giga - ohms
Y Phase value in kilo ohms..
u have any idea to resolve this issue
ya sure you know the BB earth switch may be not open completely call me for any problem
Sir tell me How to enable ac voltage indication light
by press, the button called SEL and labeled as circuit (A)
can i get email address of this person or any other peerson related to testing and comissioning
asad abbasi engineeralisaleh@gmail.com
00966545338871
thankyou
Assalamualaikum sir...
Walicom islamo eng
@@engineeralisaleh5178.. Sir can you teach me how to calibration idmt?
@@kasmanosman7396 You can do this by injecting twice the current value and observing the time value. see the equation at manual