    Generator is running normally, when we started a heavy motor then suddenly generator stopped what is the reason.( Generator rated power is more than that of motor)

    • @mmdexamtips
      @mmdexamtips  16 дней назад +1

      It can happen due to the overload because the starting current of the motor is approximately 5 to 7 times higher than the running current which can cause the voltage deep or search and can create overload

  • @marinerstarget63
    @marinerstarget63 19 дней назад

    Sir, why we do not use ig in bunker tank ?

    • @mmdexamtips
      @mmdexamtips  16 дней назад +1

      Venkat and sister heavy few line and they don't have the volatile components.

    • @mmdexamtips
      @mmdexamtips  16 дней назад +1

      Heavy few royal are the residual fuels as it is used for running the vessel it is cheap but it does not create the explosive situation in the bunker tank so mostly we are not using IG in the bunker tank. Include while the situation is different they have so many volatile components and the explosive atmosphere created in the cargo tanks so IG is used over there.

    • @mmdexamtips
      @mmdexamtips  16 дней назад +1

      Heavy fuel oil