Requesting to cover CT saturation in relay protection coordination study, if possible
Will do very soon
Thank you, but transformer full current shall be 65.6A in Primary --> 100/1 or 100/5 and 656 A in secondary --> 800/1 or /5 right?
For the version 19.0.1 , There is no CT sizing option. Isn't it the problem of that version??
Probably so,, however it is available from 20.5.0 version onwards I think..
Requesting to cover CT saturation in relay protection coordination study, if possible
Will do very soon
Thank you, but transformer full current shall be 65.6A in Primary --> 100/1 or 100/5 and 656 A in secondary --> 800/1 or /5 right?
For the version 19.0.1 , There is no CT sizing option. Isn't it the problem of that version??
Probably so,, however it is available from 20.5.0 version onwards I think..