Bosch AMC2-4WCF modullar controller DLL RCV failed

Поделиться
HTML-код
  • Опубликовано: 19 окт 2024
  • BIS installations with an unresponsive AMC2-4WCF modular controller. Device cannot be configured. Firmware upgrade is failing and there is no data traffic between the device and the BIS software. Device firmware is v.00.47. All attempts to upgrade to the applicable V.37.23 fail. BIS displays the following message: "DLL RCV failed"
    (CRC ERROR in receiving new download program).

Комментарии • 12

  • @syproful
    @syproful 2 месяца назад

    Hi, is it possible to run a AMC2 4W without LAC services ? I'm in the process of a system save. Previous installer has passed away and i have a client which is asking for help. I'm quite sure it is running standalone at the moment without a LAC link is that possible ? Thanks !

  • @javierandrade7294
    @javierandrade7294 2 года назад

    como soluciono problemas de reseteo en mi controlador ya que automaticamente ella sola perdio la configuracion

  • @DenisFlorentino
    @DenisFlorentino Год назад

    Good evening, how can I update the firmware of an AMC2 4W?
    Since I can't find it, I have 6 unresponsive panels, is there a way to revive them?
    greetings.

    • @PanagiotisKaragiannisChannel
      @PanagiotisKaragiannisChannel  Год назад

      If you download the software from your regional Bosch webpage you will see that it also includes the "AMC IP Config" tool plus the required firmware for your devices. BIS software platform has also internal tools for that.

    • @DenisFlorentino
      @DenisFlorentino Год назад

      @@PanagiotisKaragiannisChannel we have the AMS 4, with this software is it possible?, since the firmware cannot be found and when restoring the panels to bafrica values they remain in bootloader. greetings.

  • @nelsongutierrez4624
    @nelsongutierrez4624 4 года назад

    Please, which one si the solution?

  • @nelsongutierrez4624
    @nelsongutierrez4624 4 года назад

    Solution?

    • @PanagiotisKaragiannisChannel
      @PanagiotisKaragiannisChannel  3 года назад +1

      Sorry for the late reply. You need to clear the buffered memory. Multiple power cycles are needed without the battery and a forced compact flash rewrite. Proceed with CAUTION as this might lead to a completely unusable device.

    • @CarlitoJrCastillo
      @CarlitoJrCastillo 4 месяца назад

      We have a very similar issue with AMC, what's the solution on this? Appreciate your input.

  • @sureshtamu5273
    @sureshtamu5273 3 года назад

    Plz can you share wiring diagram

    • @PanagiotisKaragiannisChannel
      @PanagiotisKaragiannisChannel  3 года назад

      This is not a wiring issue. Two doors with entry/exit Wiegand readers are connected on this unit. If you want to know more about the connections, you can have a look at the installation manual: resources-boschsecurity-cdn.azureedge.net/public/documents/AMC2_4W_Installation_Manual_enUS_17921126411.pdf

    • @sureshtamu5273
      @sureshtamu5273 3 года назад

      @@PanagiotisKaragiannisChannel thank you sir for your response. Actually I am new to this and I am very eager to know abt the wiring diagram with this amc2 controller for eg:- Mag Lock, Door contact/sensor, Push Button, Break glass, card reader. I would be grateful to you, if you provide me complete chart of wiring diagram.