Fisher DVC-6200 manual calibration

Поделиться
HTML-код
  • Опубликовано: 29 ноя 2024

Комментарии • 9

  • @salmandal5797
    @salmandal5797 2 года назад +2

    loop checking ka video banao calibration ka bji

  • @tecknos665
    @tecknos665 2 года назад +1

    Hum nawaz tata mundara ak fisher dvc 6010 model no 657 h isko revers kar na h

  • @surinderjohn5996
    @surinderjohn5996 2 года назад +1

    Hello
    I have YT1000RSn13 electropnuematic positioner, it's rotating my butterfly valve to fully open when given input air pressure even without any mA input given
    What should be the problem??

    • @instrumentationandsolution5013
      @instrumentationandsolution5013  2 года назад

      1. Single acting or double acting actuator.
      2. New installation or suddenly having this issue.

    • @surinderjohn5996
      @surinderjohn5996 2 года назад +1

      @@instrumentationandsolution5013 1. Double acting
      2. I joined company recently & they have not used since

    • @instrumentationandsolution5013
      @instrumentationandsolution5013  2 года назад

      @@surinderjohn5996 if double acting then interchange port A and B tubes once ..

    • @surinderjohn5996
      @surinderjohn5996 2 года назад +1

      @@instrumentationandsolution5013
      Have same problem with single acting valve also??

    • @instrumentationandsolution5013
      @instrumentationandsolution5013  2 года назад

      @@surinderjohn5996 which port of the positioner connected to actuator and check cam of that positioner, with the help of cam we can change ATO to ATC or ATC to ATO...