How to Wire Discrete DC Sensors to PLC - Part 2

Поделиться
HTML-код
  • Опубликовано: 4 ноя 2024

Комментарии • 231

  • @mikeduman358
    @mikeduman358 Год назад +3

    I have been an electrician for 20 yrs I understood the concept but the kiddies on the job always took the PLC wiring and us older guys did the heavy lifting, motors,conduit this helped me greatly thank you

  • @caffeinatedinsanity2324
    @caffeinatedinsanity2324 4 года назад +39

    To those who might struggle with sinking vs sourcing input plc cards:
    Sinking means that the input needs to be connected to +24 V to cause it to be detected as "activated".
    Sourcing cards mean that you need to connect the inputs on the negative of the 24 V.
    And now for PNP vs NPN:
    PNP: when the sensor detects something, it's signal (or load. Black wire) gets connected to +24 V, so it "pushes" or "sources" 24 V.
    NPN: when detecting something, the signal wire gets connected to the negative, so it will "pull" or "sink" current.
    Same logic applies if you want to use 2 wire sensors in both types of cards.

    • @enverismail6864
      @enverismail6864 3 года назад

      So on the npn card you need -24 power supply. That must be connected to the bottom of the IO card (the very last slot) and the common must be connected to the very first slot; where the +24 would normally be supplied. It's the only way this is making sense to me

    • @remingtonnathaniel6730
      @remingtonnathaniel6730 3 года назад

      sorry to be so offtopic but does anyone know a tool to log back into an instagram account?
      I was stupid lost the login password. I appreciate any tips you can give me!

    • @bentondarren9521
      @bentondarren9521 3 года назад

      @Remington Nathaniel instablaster =)

    • @remingtonnathaniel6730
      @remingtonnathaniel6730 3 года назад

      @Benton Darren thanks for your reply. I found the site through google and I'm waiting for the hacking stuff now.
      Looks like it's gonna take quite some time so I will reply here later with my results.

    • @remingtonnathaniel6730
      @remingtonnathaniel6730 3 года назад

      @Benton Darren it worked and I finally got access to my account again. Im so happy:D
      Thanks so much, you saved my account :D

  • @eugenepohjola258
    @eugenepohjola258 3 года назад +4

    Howdy. Nice presentation. A couple of comments.
    1. Using 2 -wire sensors (= Namur) the leaking current may be large enough to be detected as ON by the PLC DI card. To remedy this an external resistor of, say 10 k, may be connected over the input channel to deliver proper "sinking".
    2. Separate 24 VDC power supplies should be used for input circuits and outout circuits. This prevents inductive load backspikes from generating "ghost" ON detections in input circuits.
    Alternatively the +24 rail may be splitted into two secondary + rails using two diodes in a back-flow blocking configuration. P600J is a 6 A diode. One secondary + rail powers the inputs and the other powers the outputs. The output secondary + rail should be fitted with a large electrolytic capacitor after the diode, say 2200 uF, between the + and the - to provide a place to go for possible backfire spikes. Electrolytic capacitors are not necessarily fast enough to kill spikes effectivery so a plastic capacitor of, say 1 uF, may be connected in parallel with the electrolytic capacitor.
    Regards.

    • @realpars
      @realpars  3 года назад

      Thank you, Eugene! We appreciate your insightful comments!

  • @isaacadokwah2739
    @isaacadokwah2739 5 лет назад +2

    One of the best PLC videos ever. Very elaborate for easy understanding. Thanks for these great videos.

    • @realpars
      @realpars  5 лет назад

      What a great compliment, Isaac! Thanks a lot! We are always extremely happy to hear such positive feedback! If you ever have any questions, feel free to reach out to us. Happy learning!

  • @TheGoodSon89
    @TheGoodSon89 3 года назад +2

    Massive respect for sharing knowledge. Keep going!

    • @realpars
      @realpars  3 года назад

      Much appreciated!

  • @suheladesilva2933
    @suheladesilva2933 2 месяца назад

    Great video, cleared a lot of my doubts, thanks.

    • @realpars
      @realpars  2 месяца назад

      Glad it helped! Happy learning

  • @bobbyyoung2831
    @bobbyyoung2831 2 года назад

    Great Free advice and videos. Much appreciated.

    • @realpars
      @realpars  2 года назад

      Glad you like them!

  • @rodrigocardenassill4700
    @rodrigocardenassill4700 5 лет назад +5

    The best channel to learn, thank you for your valious content

    • @realpars
      @realpars  5 лет назад

      Thanks for your comment! Happy to hear that!

  • @D0m1n4t0r33
    @D0m1n4t0r33 4 года назад +1

    Thanks alot for your videos, they surely are helpful if you're setting up stuff for the first time!

    • @realpars
      @realpars  4 года назад

      Great to hear that, Bas! Thanks for sharing.

  • @suchayanmondal9858
    @suchayanmondal9858 6 лет назад +5

    Very Informative videos. Thanks for providing us for the knowledge. Please produce more nice videos on several PLC related topics like this in future. Awaiting for the next.

  • @mernilodeleon4081
    @mernilodeleon4081 6 лет назад +1

    Yes sir...thanks a lot everyday i am watching your shared videos ...coz directly related to my work now...i wish i ciuld able to join your training....one of these day. Thanks and more power....

    • @realpars
      @realpars  6 лет назад

      Thank you Mernilo! Glad to hear that you're enjoying the videos.

  • @juliuscontrolsandautomatio6861
    @juliuscontrolsandautomatio6861 2 года назад

    So great! So good! 👏👏👏👏 I'd like to learn about how to Wire Discrete DC Sensors to Variable Frequency Drive.

    • @realpars
      @realpars  2 года назад

      Great suggestion! Thanks for sharing and happy learning, Julius!

  • @darbarisid
    @darbarisid 5 лет назад

    Very good explanation

  • @spatikmedia
    @spatikmedia Год назад

    Awesome..thank you Realpars

    • @realpars
      @realpars  Год назад

      You're very welcome!

  • @yosefali7729
    @yosefali7729 9 месяцев назад

    is it safe to power the Sensors and field devices through the PLC input card, most cards have really low limit on current so connecting like 10 - 12 devices might be risky,
    how about powering it through a Power supply instead from the PLC input card ? wouldn't that be better ? appreciate your efforts in simplifying this great effort

    • @realpars
      @realpars  9 месяцев назад

      Thank you for your question. In our videos, we focus on sensors specifically designed to interface with a PLC. The input cards are responsible for receiving signals from these sensors, while the output cards supply power to your device according to your engineering specifications and current requirements. If necessary, the output cards can also power relays for handling larger currents. Every industrial PLC manufacturer typically provides a manual detailing how to use and program their PLCs. Additionally, it's important to ensure you have a suitable power supply to energize your system. Happy learning!

  • @BW-xz6ol
    @BW-xz6ol 3 года назад

    14:30 if connecting to plc input 3 shouldn’t black wire Goto B? I think you meant to say if it connects to plc input 2 then it goes to terminal A. I’m new to all this... so thank you very much for all your videos

  • @franciscojorge6568
    @franciscojorge6568 2 года назад

    That's so cool plc exemple.

  • @lukaskohout419
    @lukaskohout419 5 лет назад +5

    8:00 i think there is error in diagram--- if we talk about Voltage which is difference in potential between two poles then if you are showing +24VDC as positive pole and -24VDC as negative pole then you have potential of 48V! So it should be +24V and 0V or +12V and -12V etc...

    • @realpars
      @realpars  5 лет назад +2

      The blue wire is common, or the negative side of the 24VDC power supply. The voltage difference between +24VDC and what is shown as -24VDC (common) is 24VDC. To be clearer, the common connection should have been shown as 0 VDC. Thank you for the observation and comment.

  • @michaelcostello6991
    @michaelcostello6991 5 лет назад +2

    well explained with appropriate diagrams. Only guys like you should have a license to teach !!!

    • @realpars
      @realpars  5 лет назад

      That's a great compliment, Michael! Thanks a lot!

  • @Rexbo12
    @Rexbo12 3 года назад

    Really well explained. Thank you

    • @realpars
      @realpars  3 года назад +1

      Glad you liked it!

    • @Rexbo12
      @Rexbo12 3 года назад

      I'm just starting to learn about plc as its going to be needed for my new position thanks a lot even dumb ass like me can understand

  • @mernilodeleon4081
    @mernilodeleon4081 6 лет назад

    Great job...more technician like could benefits this learning....please continue...

    • @realpars
      @realpars  6 лет назад

      Thanks for watching Mernilo!

  • @jimbass924
    @jimbass924 3 года назад

    Very informative, great graphics!!

    • @realpars
      @realpars  3 года назад

      Much appreciated!

  • @ahmedadebakin8189
    @ahmedadebakin8189 6 лет назад

    Really nice video but I have one question concerning NPN sensors. If I give positive to the brown wire from the PLC will I still connect same to common of the Input card?

  • @MrPromerican
    @MrPromerican 4 года назад

    Thank you real pars

    • @realpars
      @realpars  4 года назад

      You are very welcome!

  • @andyhandyman2118
    @andyhandyman2118 3 года назад

    Always like and subscribed!

    • @realpars
      @realpars  3 года назад

      Thank you, Andy!

  • @eng.mohamedfandod1937
    @eng.mohamedfandod1937 5 лет назад +1

    excellent
    Go ahead i will support your channel in every where .

    • @realpars
      @realpars  5 лет назад +1

      Thanks a lot for your support, Mohamed!

  • @KevinNguyen-tw5ml
    @KevinNguyen-tw5ml 6 месяцев назад

    Thank you very much !

    • @realpars
      @realpars  6 месяцев назад +1

      You are welcome!

  • @toddmaggio2032
    @toddmaggio2032 2 года назад

    Thank you for your educational videos. I have a two question that you might have already answered elsewhere. If so I'd be grateful for the links. Can a proximity sensor be used as a SPDT switch?
    Say I want a conveyor belt go back and fort. Can the wiring be tweaked in such way that sensor reverses the direction of the electrical circuit and make the conveyor belt reverse its direction?

    • @realpars
      @realpars  2 года назад

      A proximity sensor be used as a SPDT switch only if it is designed as a SPDT switch. Many (if not most) proximity switches used today are solid state, so there is only one output available, and it is transistor output, not a Form C contact. For your second question, you can use the proximity switch input as a trigger for PLC logic to act to reverse the belt. You likely will also need some timers in this logic as well. If you were to do this in a hardwired system, it can be done with a series of relays, sensors, and timers, but the proximity sensors would still be wired as shown in this video.

  • @adriandeluna8906
    @adriandeluna8906 3 года назад

    Perfect video congrats to your channel..

    • @realpars
      @realpars  3 года назад

      Thank you very much, Adrian!

  • @user-ro6ou5vb8y
    @user-ro6ou5vb8y 3 года назад

    Thanks God for sharing this matter i indeed very interested and i wish i could learn more about plc such as how to program.

    • @realpars
      @realpars  3 года назад

      You are welcome!

  • @xhuljan11
    @xhuljan11 3 года назад

    Thanks a lot ❤️

  • @yem.t.3930
    @yem.t.3930 6 лет назад

    Very comprehensive ! Thanks

    • @realpars
      @realpars  6 лет назад

      You're very welcome!

  • @dilantharuwan7373
    @dilantharuwan7373 3 года назад

    Nice explane and great work.keep it up

    • @realpars
      @realpars  3 года назад

      Glad you liked it, Dilantha!

  • @kittylayyon2789
    @kittylayyon2789 4 года назад

    Thanks real pars

    • @realpars
      @realpars  4 года назад

      You are very welcome!

  • @marcbiss5953
    @marcbiss5953 5 лет назад

    Very clear and informative! Thanks

    • @realpars
      @realpars  5 лет назад

      Great to hear that, thank you!

  • @mateorenai
    @mateorenai 6 лет назад

    Hello.. Thankyou for your clear explanation about this. I am just learning about this PLC thing. but i have more question. how do you connect multiple let say 4 Proximity sensor. Thanks again

  • @longhungtruong7980
    @longhungtruong7980 5 лет назад

    I have one question for RealPars:
    What exact function difference between 2-wire and 3-wire DC sensor? Use the 2-wire one is more easier than 3 wire when we connect with PLC. So, Why we don't have 2-wire DC sensor for Level switch and pressure switch?
    The information of this video is excellence. Please help me answer previous question.
    Thank RealPars.

    • @realpars
      @realpars  5 лет назад +1

      The difference is fairly simple to explain. Sensors that are simple contact closures, such as limit switches, flow switches, hall-effect proximity switches, and vibratory level switches are all two-wire devices. One wire is 24VDC+ and the other is common, or 0VDC. These sensors are either mechanically or magnetically actuated or can use the 24VDC+ wire to power the device. Sensors based on solid-state technology require 3 wires. Solid-state devices are based on transitor circuits which require 3 wires: 24VDC+ applied to the base, a signal wire that goes back to the PLC as the input from the collector, and a ground wire for the emitter. Solid state devices are smaller and many times configurable as to setpoint, trip point, etc., but they also require 3 wire connections. That is why it is important to understand how to properly connect these to the PLC.

    • @longhungtruong7980
      @longhungtruong7980 5 лет назад

      @@realpars So, Thanks for your explanation.
      I'm clear about function of both sensors types.
      Please release more videos like this.
      I keep following and learning with you.

  • @eliehajj3777
    @eliehajj3777 Год назад +2

    A "Sinking" PLC input card has (0 VDC) commonly connected to all its Inputs. Therefore it needs PNP Sensors to be connected to it.
    A "Sourcing" PLC input card has (+24 VDC) commonly connected to all its inputs. Therefore it needs NPN Sensors to be connected to it.
    So for the example in the video above the inputs (from I0.0 to I1.7 ) should be commonly connected to ( - ), therefore terminals 10 and 11 should be connected to ( - ), not to (+24 VDC) because it is a "Sinking" input card and only accept PNP sensors.
    I hope that I'm wrong.😀

  • @thairaltimemy7287
    @thairaltimemy7287 5 лет назад

    Thanks a lot for your good ,brief , explanation....keep going

    • @realpars
      @realpars  5 лет назад

      You are very welcome, Thair! Happy learning.

  • @night_grinder1378
    @night_grinder1378 4 года назад +1

    Greatvideo. Real pars.
    Can you make video how to troubleshoot devices.? Thanks it will help a lot.

    • @realpars
      @realpars  4 года назад

      Thanks for your support, Christian!
      And thanks for the topic suggestion, I will definitely go ahead and forward this to our creator team.
      Happy learning!

  • @DannyJaves
    @DannyJaves 3 года назад

    The best information excellent

  • @boothhits6144
    @boothhits6144 4 года назад

    great channel thank you so much

    • @realpars
      @realpars  4 года назад

      Thanks for your support!

  • @sakirdag2976
    @sakirdag2976 5 лет назад

    Tank you very much for very informative vedios

    • @realpars
      @realpars  5 лет назад

      Thank you! We are always extremely happy to hear such positive feedback! If you ever have any questions, feel free to reach out to us. Happy learning!

  • @javierferrer4634
    @javierferrer4634 6 лет назад

    Very nice video!

  • @hiwaabdulrazaq7920
    @hiwaabdulrazaq7920 3 года назад

    Thanks

  • @sntgjmb6195
    @sntgjmb6195 6 лет назад

    Thanks for the information, from Ecuador

    • @realpars
      @realpars  6 лет назад

      You're very welcome! Happy to have viewers from all over the world! Happy learning ;).

  • @tomcasarella6061
    @tomcasarella6061 2 года назад

    A PNP device is wired to a PNP card the common on the card is Negative input to the card is Positive

  • @hayel2015
    @hayel2015 6 лет назад

    You are the best to explain the PLC💝💝💝👍👍👍

  • @photog1529
    @photog1529 4 года назад

    New to this, but a question. at about 14:34, you state if the proximity switch is connected to terminal 3, the load wire would be connected to "A"...shouldn't the load be connected to "B"?

    • @realpars
      @realpars  4 года назад

      At that point in the video, the schematic correctly shows a PNP sensor connected to the first channel of the PLC card, which is at terminal 2 of the input card, or terminal A on the marshalingpanel. The narration says "PLC input channel 3", the black wire should be connected to C, which is connected to screw terminal 4 on the PLC card.

  • @jcerranom
    @jcerranom 3 года назад

    Simply Awesome!!

    • @realpars
      @realpars  3 года назад

      Glad you like it, Julio!

  • @zukhriddinmirzaumarov1758
    @zukhriddinmirzaumarov1758 5 лет назад +1

    Thanks, really good job!

    • @realpars
      @realpars  5 лет назад

      Great to hear! You are very welcome.

  • @imamulkabirhimel7477
    @imamulkabirhimel7477 4 года назад

    What if i want to connect npn switch. Should the brown be connected to 20 and blue to 10?

  • @P.J16
    @P.J16 3 года назад +1

    7:49 Blue wire should be -24 Vdc or just O V?

    • @realpars
      @realpars  3 года назад +1

      It is best to consider the blue wire as common, or 0V.

  • @ardentdfender4116
    @ardentdfender4116 5 лет назад

    Along with this very well explained video, can you please add a video for “loop Checking” or how to properly Loop Check of devices to Terminal Block or Input Card/ Output Card module for the RealPars video team to do.

    • @realpars
      @realpars  5 лет назад +2

      Thank you, Ardent! I have gone ahead and forwarded your topic suggestion to our creator team. Hopefully, they can add it to the list. Thanks again!

  • @eliosgreek8028
    @eliosgreek8028 5 лет назад

    Great video

  • @tipko1863
    @tipko1863 3 года назад

    Am I missing something or is the wiring diagram for the PNP type switch around 9:09 (where - is the common wire on the input cards) different than than the one shown around 13:57 where the +24V is the common for the 2 groups of inputs?

    • @realpars
      @realpars  3 года назад +1

      No. in both cases, the (-) is attached to terminal 20 on the I/O card, which is common (blue wire).

    • @tipko1863
      @tipko1863 3 года назад

      @@realpars Alright, so then the wires connecting pins 10 and 11 to 24 V are used to power those groups of inputs or something else?

  • @bitebonumbere1426
    @bitebonumbere1426 3 года назад

    Awesome videos.
    Please can you upload the subtitles? The auto-generated one is difficult to follow. Thanks.

    • @realpars
      @realpars  3 года назад +1

      Hi Bitebo,
      Thanks for your comment!
      We have English subtitles for almost all our RUclips video courses. Unfortunately, some of our older video courses do not have this, and only have the auto-generated option.
      Sorry about that, hopefully you are still able to enjoy them!

    • @bitebonumbere1426
      @bitebonumbere1426 3 года назад

      @@realpars meaning is it impossible to add subtitles?

  • @abrahamgreenidge8924
    @abrahamgreenidge8924 5 лет назад

    Hello, do you have any basic basic basic instructional video on the wiring of PLC? I’m neww to this & has 0 experience.

    • @realpars
      @realpars  5 лет назад

      This video and the companion Part 1 video provides good instruction on wiring discrete devices to the PLC. Other RealPars videos give instruction wiring other modules, power supplies, etc.

  • @maruthiprasad8184
    @maruthiprasad8184 4 года назад

    Team,Thank you so much for valuable information. I have a doubt on control valve resolution concept from long time. Is it possible to make a video on this concept. It will be great help to everybody.

    • @realpars
      @realpars  4 года назад

      Hi Maruthi!
      Thanks for your comment and your suggestion. I will pass this on to our course developers!
      Thanks for sharing and happy learning!

  • @venkatvijayakumar6176
    @venkatvijayakumar6176 4 года назад

    Hi, I have two Level Sensors which is 4-20mA type. But, I have only one 24 VDC supply adapter. Is it possible share the DC supply to two sensors to get the 4-20mA output?

    • @realpars
      @realpars  4 года назад +1

      Yes, as long as your power supply can output at least 50ma (20ma for each sensor). This is normally how analog circuits are set up: common power supply with individual milliamp signals back to an analog input card. The sensor is the device that regulates the milliamp signal.

    • @venkatvijayakumar6176
      @venkatvijayakumar6176 4 года назад

      @@realpars Thanks a lot, I'll check on that.

  • @wasuts.444
    @wasuts.444 6 лет назад

    Your videos very helpful, Thanks very much. and I saw the subtitles start at 15:35 explain about PNP but your are talking about NPN first, I think the subtitles was wrong place, just let you know.

    • @realpars
      @realpars  6 лет назад

      You're right! Thank you for letting us know.

    • @wasuts.444
      @wasuts.444 6 лет назад

      RealPars You’re welcome.

  • @isidrovaldez2391
    @isidrovaldez2391 4 года назад +6

    I don’t think that an inductive proximity switch could detect a box. I was under the impression that an inductive prox only detected ferrous metals, and a capacitive proximity switch would be used to detect things like plastics, wood, liquids, and boxes.

  • @psi23k
    @psi23k 4 года назад

    @8:23 you show the brown wire from the npn sensor connected to the negative of the I/O card. Is that correct? Shouldn't it be connected to 10 or 11?

    • @realpars
      @realpars  4 года назад +1

      For a sinking sensor, the brown wire is connected to the most positive terminal on the PLC card. In this configuration, 24VDC is applied to the common terminal of the PLC card, as shown. This is true for the Siemens DI card chosen, but it is always good to check the specific wiring diagram for the card you are using before connecting a sensor. Some manufacturers have different models of DI card depending on the sensor type (sinking or sourcing).

  • @andersonsardinha1504
    @andersonsardinha1504 2 года назад

    Perfect 😃

  • @priceless55
    @priceless55 6 лет назад

    Simplicity is the key. :)

  • @davidpalmer963
    @davidpalmer963 3 года назад

    Image result for what can a inductive proximity switch detect?
    Inductive proximity sensors can only detect metal targets. They do not detect non-metal targets such as plastic, wood, paper, and ceramic

  • @mikemwabilwa572
    @mikemwabilwa572 5 лет назад

    Many thanks

    • @realpars
      @realpars  5 лет назад

      You are very welcome, Mike!

  • @runbou3485
    @runbou3485 2 года назад

    Thankអរគុណ👏

  • @shuhaibvk2456
    @shuhaibvk2456 5 лет назад

    Very informative👌🏼

    • @realpars
      @realpars  5 лет назад

      Happy to hear that! Thank you, Shuhaib!

  • @GRant16NCH
    @GRant16NCH 6 лет назад

    Thanks for video

  • @mprv3755
    @mprv3755 6 лет назад +4

    Great video. Possibly a video on how to use “scale/ scaling ” PID instruction on Analog instrumentation on Siemens or Allen Bradley?

    • @realpars
      @realpars  5 лет назад +1

      This topic is covered in a 9-part course on using the PID instruction in an S7-1500 on the Realpars.com learning site. Come subscribe and give it a try!

  • @phillyo51
    @phillyo51 4 года назад

    How can you find out which cards are compatible with PNP or NPN?? I've checked the siemens support website but have found no information. Cheers.

    • @realpars
      @realpars  4 года назад

      Check out this article: support.industry.siemens.com/cs/document/23451499/what-is-the-meaning-of-the-terms-sinking-(german%3A-p-lesend-)-and-sourcing-(german%3A-m-lesend-)-in-digital-modules-of-simatic-?dti=0&lc=en-WW
      The cards compatible with NPN and PNP wiring are listed toward the bottom of the article referenced above.

  • @glaucioferreira13
    @glaucioferreira13 5 лет назад

    Thanks for this usefull video!

    • @realpars
      @realpars  5 лет назад

      You are welcome, Glaucio!

  • @suhail8086123757
    @suhail8086123757 6 лет назад

    Wonderful videos

  • @grow8151
    @grow8151 6 лет назад

    Very good

  • @SinhPV
    @SinhPV 6 лет назад

    Useful a video ! Thank for sharing...

    • @realpars
      @realpars  6 лет назад +1

      You're very welcome!

  • @deku4497
    @deku4497 3 года назад

    I am confused with the explanation in time stamp 14:00. I thought if we will be using a PNP sensor, we need to use a Sinking Input Card. From what i know the input card he uses to demonstrate it is a Sourcing Input Card. Because the +24V is the one that is shared to the terminals 10 and 11. Please help I'm a beginner and I'm confused.

    • @deku4497
      @deku4497 3 года назад

      Or maybe I'm wrong for thinking that it is a Sourcing Input Card based on it's internal connection. Please correct me if im wrong

    • @realpars
      @realpars  3 года назад

      The card shown is one of several Siemens SM321 digital input cards that can support 2, 3, and 4-wire sensors in any configuration. [support.industry.siemens.com/cs/mdm/8859629?c=97343653771&lc=en-MY]. The PNP sensor is sourcing, so the +24VDC is applied to the sensor (brown wire) and when switched, the current is sunk to ground through the DI input terminal to ground. In the above link, follow the signal through the circuit to "M", which is connected to terminal 20 (ground).

  • @richatpurba9047
    @richatpurba9047 4 года назад

    so if we accidentally buy a PNP switch when it should be an NPN switch, we can't just switch the wiring termination to make it works?

    • @realpars
      @realpars  4 года назад

      This can be done only if the PLC card supports sourcing and sinking type switches. An NPN sensor requires a sourcing PLC input and a PNP sensor requires a sinking PLC input.

  • @mnada72
    @mnada72 4 года назад

    Sinking switch (NPN) needs sourcing module hence the common of the module is positive
    Sourcing switch (PNP) needs sinking module hence the common of the module is negative

  • @samisrour3129
    @samisrour3129 4 года назад

    great videos.. hope to be fine

  • @alhassanalmusawy2056
    @alhassanalmusawy2056 5 лет назад

    thanks,and please keep going

    • @realpars
      @realpars  5 лет назад

      You are very welcome! Thanks for your support!

  • @vishnukr8010
    @vishnukr8010 2 года назад

    Hi, Can we ever connect a PNP sensor to PNP I/O card? I got a qsn like that in an assesment, any possiblity please help.

    • @realpars
      @realpars  2 года назад

      Yes, it is possible, but you will need to modify the circuit with a resistor and non-standard wiring connections. I do not recommend doing this because it will confuse other techs who may need to maintain the system.

    • @vishnukr8010
      @vishnukr8010 2 года назад

      @@realpars I got this as a qsn on one assesment..? Is there a proper answer for that ..is that just a pull down resistor

    • @realpars
      @realpars  2 года назад +1

      @@vishnukr8010 I believe the 24VDC connection at the I/O card is removed, and a 10k resistor is placed between the (-) terminal and ground for the digital input. Again, this is not standard and would require specific detailed documentation to avoid future issues. I would say the proper answer to an assessment question would be "no" if the question was looking for a binary choice. If you were to able to provide an explanation in the answer, I would respond, "yes, but the solution is non-standard and should not be implemented unless absolutely necessary".

    • @vishnukr8010
      @vishnukr8010 2 года назад

      @@realpars thank you mate.. Its not a boolean type I have to draw the electrical circuit and submit. Anyway, thank for your reply it was very helpful.

  • @amilabalasooriya8944
    @amilabalasooriya8944 6 лет назад

    Thanks.keep going

    • @realpars
      @realpars  6 лет назад

      Thanks for watching!

  • @suhelpatel2028
    @suhelpatel2028 6 лет назад +1

    Beautiful 👌

  • @3498137
    @3498137 2 года назад

    Excellent¡

  • @hoangzxc2467
    @hoangzxc2467 4 года назад

    oh hi, in this video, is proximity switch the same proximity sensor ? (at 6:01)

    • @realpars
      @realpars  4 года назад

      Yes. A proximity sensor is typically a solid state switch that is tripped when the sensor is moved near a target.

  • @keerthi47kv
    @keerthi47kv 6 лет назад +2

    Please keep going

  • @MegaRyad
    @MegaRyad 2 года назад

    if you put electrons going in and out in the animation it would have been better to understand this pnp and npn sensors , thank you

    • @realpars
      @realpars  2 года назад

      Thanks for the feedback! I will happily go ahead and pass this on to our course creators.
      Thanks again for sharing and happy learning

  • @anwarmuzamil6972
    @anwarmuzamil6972 4 года назад

    Which type of PLC is used for connecting dc sensors??

    • @realpars
      @realpars  4 года назад

      Most any PLC can interface to DC sensors. You just need to have I/O, either connected to the PLC or in remote I/O racks that support DC sensor signals. It is the type of I/O card that determines the signal interface allowed at that card, not the type of PLC itself.

  • @charliechimples
    @charliechimples 5 лет назад

    Great vid once again, well explained. 🐵

  • @frankietrenado9327
    @frankietrenado9327 5 лет назад

    I believe if wiring into IO channel 0.3 the black input wire should go to terminal D

    • @realpars
      @realpars  5 лет назад

      It does. In video, terminal 1 is 24VDC, terminal 2 is I0.0, terminal 3 is I0.1, terminal 4 is I0.2, and terminal 5 is I0.3, connected to "D".

  • @pradippatole1328
    @pradippatole1328 6 лет назад

    plz share video related to potential free contact and wetted contact

    • @realpars
      @realpars  6 лет назад

      Glad to have you as a subscriber! :)

  • @ieight8234
    @ieight8234 5 лет назад +1

    blue wire is -24v? so potential difference between blue and brown (+24v) is 48v? 😉

    • @scottsommer6480
      @scottsommer6480 5 лет назад

      The blue wire is common, or the negative side of the 24VDC power supply. The voltage difference between +24VDC and what is shown as -24VDC (common) is 24VDC.

    • @jeremyk2173
      @jeremyk2173 5 лет назад +1

      @@scottsommer6480 the difference between +24 and -24 is 48v. The blue wire is 0v, not -24v

    • @scottsommer6480
      @scottsommer6480 5 лет назад

      @@jeremyk2173 Technically, yes.

  • @Logical_Controls
    @Logical_Controls 6 лет назад +1

    Informative video. Thanks. FYI slight text error @ 7:53

    • @realpars
      @realpars  6 лет назад

      Thank you! Happy to hear! I just double checked to video. However, I couldn't spot any error.

    • @Logical_Controls
      @Logical_Controls 6 лет назад +1

      Thanks for the reply Realpars. Nothing major, it's just says +24VCD instead of +24VDC. Also shouldn't it be 0VDC for the blue wire as opposed to -24VDC which is a negative voltage instead of a ground?

    • @chuchuokeke
      @chuchuokeke 5 лет назад

      Also, plc terminal 2 is point A on the marshaling terminal block..i think you said point 3 is A..great work, very informative. Keep it up for more likes!

  • @rongulamhusain981
    @rongulamhusain981 3 года назад

    I want to learn plc course, kindly let me know how should I connect to u

    • @realpars
      @realpars  3 года назад

      Hi Ron!
      Thanks for your comment!
      Great to hear your motivation in regard to learning PLC Programming. 

Our course library is specifically designed in a way where it provides all the tools needed for beginners to evolve into an advanced level through our hands-on courses.
      Feel free to browse through our course library to see all the different topics we are covering. bit.ly/30AVJaR
      Just to let you know, that we also have a free course on PLC Hardware bit.ly/2XnnUrF

      If you are interested, you will obtain full access to our complete course library (400+ video courses) by subscribing to either our monthly package for €22.12 a month or our yearly package for €159.28,-.
      

Additionally, you will have access to our Technical Team - consisting of high ranking engineers with a lifetime of experience - who are here to help you out with any questions you might have along the way! 

      Hope this helps! If I can be of any further assistance, please let me know - I’m more than happy to help!

    • @oyekanmibamidele6196
      @oyekanmibamidele6196 3 года назад

      @@realpars Sir, I'm seen different prices on your website?

    • @oyekanmibamidele6196
      @oyekanmibamidele6196 3 года назад

      @@realpars l would have sub for a year package

  • @erturkmemmedli1790
    @erturkmemmedli1790 6 лет назад

    In 13:43, you show connection for pnp. So I guess for npn, unlike pnp, red wire must connect to 20 (negative terminal) and blue wire must connect to 10 (positive terminal). However, for npn, in 8:43, you showed red wire is connected to positive terminal of power source and blue one is connected to negative terminal of power source. I didn't get it. With that way, we connect positive terminal of power source to 20 in PLC (negative side), how is it possible?

    • @realpars
      @realpars  6 лет назад +1

      You make a good observation. But remember what was indicated in the video: a sinking discrete input card (for use with pnp sensors) and a sourcing discrete input card (for use with npn sensors) operate differently and are also wired differently. The function of Terminal 20 in each type of card is also different. Most plants will use pnp sensors with sinking input cards, simply because they are most common and are easier to wire. The npn and sourcing input cards sensors are mentioned because there are some industries where these type sensors are more common, and most manufacturers offer products with both types of configurations. It is therefore important to know the differences and specify the right type of sensor, and the right type of PLC card.

    • @erturkmemmedli1790
      @erturkmemmedli1790 6 лет назад +1

      Thank you very much. I haven't noticed that the connections for sinking and sourcing discrete input cards are different. Now, everything is totally okay :)

    • @almir2673
      @almir2673 6 лет назад

      RealPars in the video npn is sinking type and pnp is sourcing, very useful video by the way, thanks for sharing your knowledge.

  • @syedjawadable
    @syedjawadable 6 лет назад

    please make videos on encoders and resolver .

  • @hoangzxc2467
    @hoangzxc2467 5 лет назад

    oh hi, It makes me confused and wondered when the actual PLC I/O cards in this video that's not shown the actual power supply used to power the card(I mean it's just shown that the card requires +24VDC power and there's only +24VDC (shown by number) to the terminals(at 12:20). it's quite different to the PLC module's common terminal shown at (8:28) ), please help me to understand that correctly

    • @realpars
      @realpars  5 лет назад

      In order to highlight the important wiring connections, we often just represent the power connection as +24VDC and common connection as COM. If we had shown the actual power supply in the diagram, +24VDC and COM would be connected to the power supply at terminals of the same name.

  • @GRant16NCH
    @GRant16NCH 6 лет назад

    Make vedio.. different connection AI, AO analog detection

  • @ikramantaki
    @ikramantaki 6 лет назад

    I WANT THE COURSES¡¡¡ WITH YOUR HELP I´LL GET A JOB

    • @realpars
      @realpars  6 лет назад

      Happy to hear your motivation! Have you looked at our course library yet? realpars.vhx.tv/browse

    • @ikramantaki
      @ikramantaki 6 лет назад

      RealPars yes, I already subscribed