12 head ESFR activation / demonstration

Поделиться
HTML-код
  • Опубликовано: 27 окт 2024

Комментарии • 5

  • @pumper51
    @pumper51 5 лет назад +1

    Outstanding!

  • @icureyou7965
    @icureyou7965 5 лет назад +2

    Looks about right - are they measuring amount of water out of the system - to compare it to the calcs...

    • @thefritz8959
      @thefritz8959  5 лет назад +2

      I Cure You no! This was demonstration put on by the installing contractor before the final C/O. They invited all of the surrounding agencies to come watch the demonstration as well. The heads were K-16.8@52 psi which is typically delivers around 1400 GPM. During the observed flow we saw closer to 1700 GPM. This is a very robust system with a strong infrastructure behind it. This particular system will be protecting a large tire distribution warehouse with high piled storage.

    • @ironmatic1
      @ironmatic1 Год назад

      @@thefritz89591454 x 1.17 = 1701, seems about right for friction loss overflow

  • @MichaelFerreira101
    @MichaelFerreira101 5 лет назад

    Location?