Wet Alarm Valve

Поделиться
HTML-код
  • Опубликовано: 27 окт 2024

Комментарии • 11

  • @Bud4Ooz
    @Bud4Ooz 4 года назад +9

    This is great... but how does it work

    • @JBF-GST-Tanda
      @JBF-GST-Tanda 10 месяцев назад +1

      When a sprinkler head pops under high temperature, pressure above the valve plate starts to drop, which causes the valve plate to open up, allowing water to flow through a previously covered slot port which is plumbed to a bottle called "retard chamber". The bottle would be filled up in about 30 seconds, and then water coming out from its top flows into a water motor gong (mechanical bell driven by a turbine) for local alarm and a pressure switch for remote alarm and sprinkler pump activation.

  • @abdulghanihasan844
    @abdulghanihasan844 3 года назад +1

    Please do you have a partner in Saudi Arabia - Riyadh? Thanks a lot

  • @conqwiztadore2213
    @conqwiztadore2213 5 лет назад +3

    woow great animation

  • @MariaJimenez-jg1rh
    @MariaJimenez-jg1rh 3 года назад +1

    nice

  • @sterlingbrower6702
    @sterlingbrower6702 Год назад

    Nice