Fire Pump Sensing Line: Summary of Requirements from NFPA 20
A Certified Fire Protection Specialist (CFPS) briefly explains the proper installation of fire pump sensing lines, and answers the following important questions:
0:18 What is a fire pump sensing line?
0:42 Why do fire pumps need to monitor pressure?
0:48 Fire pumps vs Jockey pump
01:00 How do automatic sprinkler and fire pump systems operate?
1:45 Fire pump pressure settings (Cut-in and Cut-out pressures)
02:20 Sample cut-in and cut-out pressure settings tabulation
02:54 Can sensing lines be combined?
03:10 Why it shouldn't be tapped above the alarm check valve
03:40 Sensing line tapping point connection
03:54 Pressure actuated sensing line piping size and material
04:24 Pressure snubbers: Inverted ...
Просмотров: 791

Видео

How to conduct a fire pump churn test
Просмотров 3,2 тыс.3 месяца назад
A Certified Fire Protection Specialist (CFPS) teaches how to conduct a fire pump churn test, its frequency and duration, and best practices. This video answers the following questions and more: 0:14 What is a fire pump churn test? 0:28 Should return lines be opened during no-flow tests? 0:55 How often should fire pump churn tests need to be conducted? 1:13 Duration of the no-flow test 1:28 Chur...
Fire Protection Contractor Philippines: The First and Only Certified Internationally 🇵🇭 🥇🔥
Просмотров 2735 месяцев назад
Flameguard is a fire protection company in the Philippines that specializes in the supply and installation of FDAS, fire sprinklers, FM200, Novec1230, kitchen suppression, deluge system, and other fire protection systems. Still haven’t subscribed to Flameguard on RUclips? ► www.youtube.com/@Flameguard?sub_confirmation=1 Please also follow our socials ► flameguardph ► ...

Комментарии

  • @mohamedismayil8893
    @mohamedismayil8893 Месяц назад

    Nice and simple

  • @Mgorkiacademy
    @Mgorkiacademy Месяц назад

    Sir keep it up po. Hello from Nigeria am in the oil and gas industry dito sa main bansa. hehe

  • @jeneriofernandez682
    @jeneriofernandez682 Месяц назад

    Not showing any valve to close

    • @Flameguard
      @Flameguard Месяц назад

      Hi Jenerio, NFPA does not require closing the system isolation valves before conducting the fire pump churn test. It's optional but not necessary. Some operators prefer to close the system isolation valves if they have a high head (more than 175 psi) fire pump churn, but leave them open otherwise.

  • @MayaMaya-qx2mo
    @MayaMaya-qx2mo Месяц назад

    Do we need to close any valve before churn test?

    • @Flameguard
      @Flameguard Месяц назад

      Not necessarily. The NFPA does not require closing the system isolation valves before conducting the fire pump churn test. Both practices have opposing advantages. Case A) If you close the system isolation valve, you keep the rest of the system safe from any unwanted incidents. This might be advantageous for high-churn fire pumps (more than 175 psi) and systems where you are not confident to have been fully compliant with appropriate installation standards. Case B) If you keep the system isolation valve open, it ensures that your whole system is capable of handling your fire pump operation, which btw is the intent of NFPA in the first place. This is advantageous for properly installed systems, compliant to NFPA 13, 14, 20 and other standards, whether or not the fire pump has a high or low head.

    • @MayaMaya-qx2mo
      @MayaMaya-qx2mo Месяц назад

      @@Flameguard Your explanation's very helpful. thanks you

    • @Flameguard
      @Flameguard Месяц назад

      @@MayaMaya-qx2mo welcome! Please support us by subscribing to our channel and following our socials😇

  • @MrLuigipy
    @MrLuigipy 2 месяца назад

    Very informative video, thanks!

    • @Flameguard
      @Flameguard Месяц назад

      Thanks for your feedback! You might want to check our newly uploaded video: ruclips.net/video/hdBO_yhNOJg/видео.html

  • @Flameguard
    @Flameguard 3 месяца назад

    [FREE] Fire Protection Maintenance Book link: flameguardph.com/fire-protection-maintenance-book

  • @Flameguard
    @Flameguard 4 месяца назад

    Hi viewers, here's the link for the free fire protection maintenance book where you can get exclusive checklists and more: flameguardph.com/fire-protection-maintenance-book

  • @jccaloy
    @jccaloy 5 месяцев назад

    master ko yan 🤭

    • @Flameguard
      @Flameguard 4 месяца назад

      Thanks jccaloyski❤️

    • @Fredengle
      @Fredengle День назад

      So can you think of any reason that a smoke heat alarm combo could not be installed 4 inches horizontally from the tip of an in ward swinging door thoughts please thank you ( in case I was unclear my idea was to install it on a side wall) Salamat PO!!