Cable Testing | VLF Test Settings |MV cable Fault test | Cable Fault detecting
In this video we are explain the settings of VLF Cable Test.
‼️‼️‼️‼️‼️ PRECAUTIONS ‼️‼️‼️‼️‼️
Its a high voltage test, so before pressing the start button, please make sure your colleagues are away from the both end of the cable.
‼️‼️‼️‼️‼️ PRECAUTIONS ‼️‼️‼️‼️‼️
For that we have to apply VRMS(RMS voltage) for testing. Its calculation added below.
VRMS = (Rated Volt of The Cable * Number of phases )/ (√2 *√3)
• For an 13.8 KV Cable the calculation is👇
{ 13.8 * 3 } / { √6 }= 16.9 Kvrms
=17 kvrms
For an 33 KV Cable the calculation is👇
{ 33 * 3 } / { √6 }= 40.4 Kvrms
If you have any doubts in the settings or calculations, feel free to ask in the comment section
#cable #automobile #voltage #cableprote...
‼️‼️‼️‼️‼️ PRECAUTIONS ‼️‼️‼️‼️‼️
Its a high voltage test, so before pressing the start button, please make sure your colleagues are away from the both end of the cable.
‼️‼️‼️‼️‼️ PRECAUTIONS ‼️‼️‼️‼️‼️
For that we have to apply VRMS(RMS voltage) for testing. Its calculation added below.
VRMS = (Rated Volt of The Cable * Number of phases )/ (√2 *√3)
• For an 13.8 KV Cable the calculation is👇
{ 13.8 * 3 } / { √6 }= 16.9 Kvrms
=17 kvrms
For an 33 KV Cable the calculation is👇
{ 33 * 3 } / { √6 }= 40.4 Kvrms
If you have any doubts in the settings or calculations, feel free to ask in the comment section
#cable #automobile #voltage #cableprote...
Просмотров: 622
Видео
Underground Cable Test | VLF Test | Cable Fault Detecting | Cable Capacity Test
Просмотров 2733 месяца назад
In this video, we are shown 2 methord of connections for a VLF Test. 1- if its an old cable- we can apply the voltage to single phase, and other Two phases can keep short woth earth. 2- If we are Testing a new cable- we can test by shorting the 3 phases of a cable, then apply the voltage to any phases. ( In this method, we can save our time. No need to repeat the test 3 times). NOTE : if you ar...
NorTroll/LineTroll programming |Earth Fault Indicator | intelligent fault indicator | OH indicator
Просмотров 1726 месяцев назад
Earth Fault indicator. its used to monitor overhead line Faults. it consider of 1 transmitter and 3 reciever. these 3 reciever should arrange in the order of 1,2,3... by arranging inside by removing the cover. only after arranging the 1,2,3 order need to connect the battery. *Transmitter* For transmitter we have to do programming. by connecting the battery (1 is inough while programming) using ...
Cable splicing 3x240 mm | 33 kv XLPE Armoured cable Heat shrinkable splicing kit | 3x240mm joint kit
Просмотров 8209 месяцев назад
@wattwmedia5962 Cable splicing 3x240 mm | 33 kv XLPE Armoured cable Heat shrinkable splicing kit | 3x240mm joint kit its an High voltage cable joint. the capacity of the cable is 33KV. The splicing kit is from saudi electricity company. Each steps for the splicing is mentioned in the manual, which is available with the joint kit. cleaning is an very important thing, while working with mv cables...
Replacement of Ring Main Unit To Smart RMU (Ring Main Unit) | RMU | Installation of Smart RMU |
Просмотров 1,6 тыс.11 месяцев назад
Here in this vedeo, there is replacing an existing Old type normal RMU(Ring main unit) to a new type Smart RMU (ring main Unit). *One of The main advantage of smart RMU is, we can operate it Remotely. *it consist of a motor, which can do the ON-OFF operations, while we are giving an instruction, both on remote & by the switch as well as, instead of using the handle.
VLF Test For Single Phase Of MV Cable | HVA60 | Verry Low Frequency Test| Cable Test| MV Cable Test
Просмотров 8 тыс.Год назад
VLF Test For Single Phase Of MV Cable | HVA60 | Verry Low Frequency Test| Cable Test| MV Cable Test @wattwmedia5962 ITS COMPLETELY A MV CABLE QUALITY CHECKING,DOING THIS TEST FOR CONFIRMING THE QUALITY OF THE UNDERGROUND CABLES, BEFORE ENERGIZATION. #vlf #vlfngp #cable #mvcable #electricity #seco #saudielectricity #network #distribution #rmu #3*500cable #termination #overhead #voltage #electric...
Recloser installation | installation of recloser on an Existing OH Line | Recloser on Double pole
Просмотров 193Год назад
We are going to install a recloser on double pole, in an live existing transmission line, During b shutdown. NOTE: 1-all other wiring and pole erections should be complete before the shutdown. 2- The new pole erection should be lessthan or equal to 3 Meter,from the Existing line for avoiding jointing of conductor. #electrical #cable #electricity #termination #recloser #overhead #voltage #hvac
MV Cable Fault Detecting | UG cable fault detector | Cable Damage detector | Fault Detector |
Просмотров 12 тыс.Год назад
MV Cable Fault Detecting | UG cable fault detector | Cable Damage detector | Fault Detector |
MV Cable joint | 33KV cable joint | 300mm-185mm Cable Transition joint | Aluminium copper joint
Просмотров 1 тыс.Год назад
MV Cable joint | 33KV cable joint | 300mm-185mm Cable Transition joint | Aluminium copper joint
Operation Of RMU(For Making earth Making ON&OFF) | Use of SF6 in RMU | what is RMU | Ring main Unit
Просмотров 8 тыс.Год назад
Operation Of RMU(For Making earth Making ON&OFF) | Use of SF6 in RMU | what is RMU | Ring main Unit
Voltage changing in a transformer | Transformer Voltage Changing | Dual Tap Change in Transformer
Просмотров 349Год назад
Voltage changing in a transformer | Transformer Voltage Changing | Dual Tap Change in Transformer
Inside Grid-Station| saudi arebia Grid-Station| Grid-Station termination HT cable
Просмотров 5992 года назад
Inside Grid-Station| saudi arebia Grid-Station| Grid-Station termination HT cable
Inside Grid-Station wiring& MV Cable Termination| Inside Grid-Station Underground wiring
Просмотров 5122 года назад
Inside Grid-Station wiring& MV Cable Termination| Inside Grid-Station Underground wiring
3*300-3*500 Cast Resin PU type transition joint (HT Cable transition Joint)
Просмотров 1,5 тыс.2 года назад
3*300-3*500 Cast Resin PU type transition joint (HT Cable transition Joint)
HT Cable Transition Joint (3*500 mm to 3*300mm)
Просмотров 4,4 тыс.2 года назад
HT Cable Transition Joint (3*500 mm to 3*300mm)
Re-Tightening of a existing pin insulator. 33kv OH line
Просмотров 1832 года назад
Re-Tightening of a existing pin insulator. 33kv OH line
Energization of new RMU/Energisation of new substation
Просмотров 1,9 тыс.2 года назад
Energization of new RMU/Energisation of new substation
preporation of termination (3x500mm & 3x70) cable to the RMU.and installation of RMU
Просмотров 6 тыс.2 года назад
preporation of termination (3x500mm & 3x70) cable to the RMU.and installation of RMU
Removing of Overhead transformer (on sight vedeo).after completing UG cable installation.
Просмотров 4202 года назад
Removing of Overhead transformer (on sight vedeo).after completing UG cable installation.
Terminations Removing from existing RMU, Transformer grounding, and Replacing of new RMU
Просмотров 3 тыс.2 года назад
Terminations Removing from existing RMU, Transformer grounding, and Replacing of new RMU
INSTALLATION OF SMART RMU,Replacement of Normal RMU to SMART RMU
Просмотров 4,6 тыс.2 года назад
INSTALLATION OF SMART RMU,Replacement of Normal RMU to SMART RMU
kitan time hua hai bhai ye
i am work saudi arebia eletitcity sir plz nest video tel mejarment
way dont tel mejarment
I am Zeeshan from mastoura co.i need mobile number of this man speaking in this video thanks
Please use my mail id mohammadshihabph@gmail.com for any communication
Brother how are you
Great informations, valuable lesson thank you bro.
Who is this guy talking
Bro how to communicate you pls send your email or phone
Thank u dear
Thanks a lot man, Good video, but what about the report !??
🩷
There is a software for submitting the report, but you have to purchase the software
Please injection Relay test video
Very good video
Thanks bro
❤❤❤❤❤
Nice shihab
🩷
Where is the setting procedure video bro
I was busy with my works, thats why it got delayed. Will update today
Very useful brother 🎉
😍
Your company name
Al jeel al thalith con.co.ltd
Next video jaldi upload kariye
Okay brother 😊🩷
Miller Shirley Thomas Jennifer Miller Richard
يعنى هنستفيد ايه من الموسيقى دى والصوت مش ظاهر !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
I will remove it
Thompson Jennifer Wilson Scott Martin Brenda
how can i download the software
You cannot download the software brother. Its a paid software
Martin John Hall Daniel Hall Maria
Johnson Jason Garcia Kevin Hernandez Cynthia
Wilson Edward Hall Brian Young Betty
Sir your company name pls
Al Jeel Al Thalith. Con. Co ltd
Want to contact you regarding business. Kindly share contact detail if available
Hello, how much it costs for installation replacement of single rmu? Can you share your company contact. We are based here in Saudi Arabia too. Ty
Its depends upon the site conditions. We have to make excavations, some times we have to change the foundaation of RMU, sometimes we can use the same termination to new RMU. Just need to remove and fix in to new RMU. But if the cable short, we have fo replace the rermination.....
Good job 👍👍👍
ممكن بس سؤال في الورقة اللي بتكون موجوده مع النهايات بيختلف مقاسات الأبعاد تقشير الكابل وعمل الفايل ازاي نعرف نحسب بالظبط الأبعاد من القراءة من الورقة
Es gas??
Its normal LPG Gas, controlling by using a throttle
الموسيقى عاليه ليه وش الفايده من الموسيقى؟ والله مااستفدنا شى ويليت تحذفون المقطع
I removed the music. You can watch it now without music
@@wattwmedia5962 thank you Bro ,i will do
Thank you so much for the video❤
Its my pleasure. Keep supporting us. Thank you
Cable jonta
Its not accurate fault located, Graph is not actual
❤❤❤❤❤
Bro your contact number
Belle prestation électrique.❤❤❤.
Where is cat 4 & safer work procedure & risk assessment during enegization new trfm?
😂😂😂
I'm Electric store keeper
What is the name of the company and where is it located?
We are working in saudi arabia
We need people
@@pakmechanicalchannel85 for what
Watt keep it up
لماذا الموسيقي يا اخي
Sorry brother. Now i removed it
Which company are u? Are u based in KSA???
Yes. Works in saudi arabia
Bro please give me your contact number or email
Well-done brother
😍🩷
Where is location
Saudi arebia
Useful information
احزف الموسيقى الصوت غير واضح
I will remove it
Look like huge HT leads